SPLFA-10
SPLFA150F
AC-DC Power Supplies Open Frame/Enclosed Value-added Type
SPLF A 150 F -O -O
Ordering information
1 2 3 4 5 6
1 Series name
2 Single output
3 Output wattage
4 Universal input
5 Output voltage
6 Optional
C
: with Coating
MODEL SPLFA150F-12 SPLFA150F-24
MAX OUTPUT WATTAGE[W] 150 151.2
DC OUTPUT 12V 12.5A 24V 6.3A
SPECIFICATIONS
MODEL SPLFA150F-12 SPLFA150F-24
INPUT
VOLTAGE[V]
AC85 - 264 1f (Refer to Instruction Manual 1.1 and 3.1)
*3
CURRENT[A]
ACIN 100V
2.0typ (Io=100%)
ACIN 200V
1.0typ (Io=100%)
FREQUENCY[Hz] 50 / 60 (47 - 63)
EFFICIENCY[%]
ACIN 100V
81.0typ 84.0typ
ACIN 200V
84.0typ 86.5typ
POWER FACTOR (Io=100%)
ACIN 100V
0.97typ
ACIN 200V
0.90typ
INRUSH CURRENT[A]
ACIN 100V
15typ (Io=100%) (At cold start) (Ta=25C)
ACIN 200V
30typ (Io=100%) (At cold start) (Ta=25C)
LEAKAGE CURRENT[mA] 0.40 / 0.75max (ACIN 100V / 240V 60Hz, Io=100%, According to IEC60950-1 and DEN-AN)
OUTPUT
VOLTAGE[V] 12 24
CURRENT[A] 12.5 6.3
LINE REGULATION[mV]
*4
48max 96max
LOAD REGULATION[mV]
*4
150max 150max
RIPPLE[mVp-p]
0 to +50C
*1
120max 120max
-10 - 0C
*1
160max 160max
RIPPLE NOISE[mVp-p]
0 to +50C
*1
250max 250max
-10 - 0C
*1
300max 300max
TEMPERATURE REGULATION[mV]
0 to +50C
120max 240max
-10 to +50
C
150max 290max
DRIFT[mV]
*
2
48max 96max
START-UP TIME[ms] 350typ (ACIN 100V, Io=100%)
HOLD-UP TIME[ms] 20typ (ACIN 100V, Io=100%)
OUTPUT VOLTAGE SETTING[V]
11.50 to 12.50 23.00 to 25.00
PROTECTION
CIRCUIT AND
OTHERS
OVERCURRENT PROTECTION
Works over 105% of rating and recovers automatically
OVERVOLTAGE PROTECTION[V]
13.80 to 16.80 27.60 to 33.60
OPERATING INDICATION LED (Green)
REMOTE SENSING Not provided
REMOTE ON/OFF Not provided
ISOLATION
INPUT-OUTPUT
AC3,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature)
INPUT-FG
AC2,000V 1minute, Cutoff current = 10mA, DC500V 50MW min (At Room Temperature)
OUTPUT-FG
AC500V 1minute, Cutoff current = 25mA, DC500V 50MW min (At Room Temperature)
ENVIRONMENT
OPERATING TEMP.,HUMID.AND ALTITUDE
-10 to +50C, 20 - 90%RH (Non condensing) (Refer to DERATING CURVE), 3,000m (10,000feet) max
*3
STORAGE TEMP.,HUMID.AND ALTITUDE
-20 to +75C, 20 - 90%RH (Non condensing), 9,000m (30,000feet) max
VIBRATION 10 - 55Hz, 19.6m/s
2
(2G), 3minutes period, 60minutes each along X, Y and Z axis
IMPACT 196.1m/s
2
(20G), 11ms, once each X, Y and Z axis
SAFETY AND
NOISE
REGULATIONS
AGENCY APPROVALS DEN-AN
CONDUCTED NOISE/POWER
Complies with DEN-AN
HARMONIC ATTENUATOR
*
5
Complies with IEC61000-3-2 (class A)
OTHERS
CASE SIZE/WEIGHT
86X47X202mm [3.39X1.85X7.95 inches] (WXHXD) / 850g max
COOLING METHOD Convection
*1 Measured by 20MHz oscilloscope or Ripple-Noise meter (Equivalent to KEISOKU-GIKEN: RM103).
*2 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C, with the input voltage held constant at the rated input/output.
*3 Derating is required.
*4 Please contact us about dynamic load and input response.
*5 When two or more units are operating it may not comply with the IEC61000-3-2. Please contact us about another class.
* To meet the specifi cations. Do not operate over-loaded condition.
* Parallel operation is not possible.
* Derating is required when operated with chassis and cover.
* Sound noise may be generated by power supply in case of pulse load.
SPLFA
me_splfa.indd 10me splfa indd 10 2015/06/18 15:01:042015/06/18 15:01:04