84870504

For more information www.crouzet.com
116
4
FN filling/emptying function with alarm
Level control
Automatic control and regulation of liquid levels.
2 sensitivity ranges.
Filling or emptying function selected via dip switch.
High or low alarm selected via dip switch.
Memory can be selected.
LEDs indicate state of power supply, output relay and
alarm relay.
Specifications
Type Voltages Code
FN LS 230 VAC
84 870 803
FN 24 VAC 84 870 501
48 VAC
84 870 502
120 VAC 84 870 503
230 VAC 84 870 504
General characteristics
Power supply characterisitcs
Supply voltage Un 230, 120, 48 and 24 V AC 50/60 Hz galvanic isolation via transformer
Operating range 0.85 to 1.15 Un except 120 V AC : 0.85 to 1.1 Un
Nominal power 3 VA at Un
Maximal power 4 VA at Un + 15 %
Immunity from micro power cuts 10 ms
Delay on pick-up T1 = approx. 2 s
Response time on power up T4 = 500 ms
Insulation coordination Category III, degree of pollution 2 conforming to IEC 664.1 / VDE0110 : 4
kV/2
Control technical characteristics
Sensitivity range FN 5 k 100 k
Sensitivity range FHLS 250 5 k
Display accuracy ± 30 % whith at maximum sensitivity
Electrode voltage 15 V AC (50/60 Hz)
Electrode current 1 mA
Response time on immersion T2 = 400 ms
Response time on emersion T3 = 700 ms
Output characteristics
Output 2 AgCdO changeover
Breaking capacity FN LS : 2000 VA
FN : 80 W
Maximum breaking current FN LS : 8 A AC
FN : 8 A DC
Minimum breaking current FN LS : 100 mA AC
FN : 100 mA DC
Max. breaking voltage FN LS : 250 V AC
FN : 250 V DC
Mechanical life (operations)
2 x 10
6
Electrical life AC 12
2000 VA - 10
5
operations
Electrical life AC 15 Cos ϕ = 0.3 - 6000 operations
Electrical life AC 13 L/R = 300 ms - 6000 operations
General characteristics
Material housing Self-extinguishing
Terminal capacity
2 x 1.5 mm
2
with ferrule
2 x 2.5 mm
2
without ferrule
Temperature limit operation (IEC 68.1.14) (°C) -20 +60
Temperature limits stored (IEC 68.1.1/2) (°C) -30 +70
Relative humidity (no condensation) 93 % (+2 % ; -3 %)
Weight (g) 280
To order, see page 6
anglais.book Page 116 Mardi, 28. octobre 2003 5:20 17
Cyan Quadrichromie 75,0° 120,0 LPP
anglais.book Page 116 Mardi, 28. octobre 2003 5:20 17
Magenta Quadrichromie 15,0° 120,0 LPP
anglais.book Page 116 Mardi, 28. octobre 2003 5:20 17
Jaune Quadrichromie 0,0° 120,0 LPP
anglais.book Page 116 Mardi, 28. octobre 2003 5:20 17
Noir Quadrichromie 45,0° 120,0 LPP
117
For more information www.crouzet.com
4
Dimensions
FN / FN LS
Connections
Regulating with "up" filling control
A1 - A2 : Supply voltage
11 - 12 - 14 : Output relay (R1)
21 - 22 - 24 : Alarm output relay (R2)
C - Min - Max - Al. : Probe inputs
Principles
Filling control with low alarm
On power-up, probe AI. is submerged, relays R1 and R2 are energised and the pump is ON : filling
starts, the LED for relay R1 is lit. When the level reaches the Max probe, relay R1 de-energises and
the pump is OFF : filling stops, the LED for relay R1 goes off. Relay R1 re-energises when the Min
probe emerges. In the event of a fault (level continues to fall) probe AI. emerges, relay R2 de-
energises and the alarm is triggered : the LED for relay R2 is lit.
This fault can be stored
B
Memory OFF
C
Memory ON
T1 : Delay on pick-up
T2 : Response time on immersion
T3 : Response time on emersion
T4 : Response time on power-down
Filling control with high alarm
On power-up, the level in the tank is low, relays R1 and R2 are energised and the pump is ON :
filling starts, the LED for relay R1 is lit. When the level reaches the Max probe, relay R1 de-
energises and the pump is OFF : filling stops, the relay LED goes off. If, in the event of a fault, the
level continues to rise and reaches proble AI., relay R2 de-energises and the alarm is triggered :
the LED for relay R2 is lit.
B
Memory OFF
C
Memory ON
T1 : Delay on pick-up
T2 : Response time on immersion
T3 : Response time on emersion
This fault can be stored.
5
77
23
3,5
57
100
78,5
89,7
99,3
45
4,2
L1
L3
L4
C
M
R1 R2
P
A1 11
A2 12 14 22 21 24
L2
Max.Min. Al.
Al.
Max.
Al.
T3 T2
T1 T2
T4
T3
Un
Al.
Max
Min
R1
R2
1
2
T2
T2
T3
T1
T3
Un
Al.
Max
Min
R1
R2
1
2
anglais.book Page 117 Mardi, 28. octobre 2003 5:20 17
Cyan Quadrichromie 75,0° 120,0 LPP
anglais.book Page 117 Mardi, 28. octobre 2003 5:20 17
Magenta Quadrichromie 15,0° 120,0 LPP
anglais.book Page 117 Mardi, 28. octobre 2003 5:20 17
Jaune Quadrichromie 0,0° 120,0 LPP
anglais.book Page 117 Mardi, 28. octobre 2003 5:20 17
Noir Quadrichromie 45,0° 120,0 LPP
For more information www.crouzet.com
118
4
Emptying control with low alarm
On power-up, probes Min, Max and AI. are submerged, relays R1 and R2 are energised and the
pump is ON : emptying starts, the LED for relay R1 is lit. When the Min probe emerges, relay R1
goes off. If, in the event of a fault, the level continues to fall and probe AI. emerges, relay R2 de-
energises and the alarm is triggered : the LED relay R2 is lit.
This fault can be stored.
B
Memory OFF
C
Memory ON
T1 : Delay on pick-up
T2 : Response time on immersion
T3 : Response time on emersion
Emptying control with high alarm
On power-up, probes Min, Max are submerged and probe AI. is above the level of the liquid. Relays
R1 and R2 are energised and the pump is ON : emptying starts, the LED for relay R1 is lit. When
the Min probe emerges, relay R1 de-energises and the pump if OFF : emptying stops, the LED for
relay R1 goes off. If, in the event of a fault, the level continues to rise and reaches proble AI., relay
R2 de-energises and the alarm is triggered : the LED for relay R2 is lit.
This fault can be stored.
B
Memory OFF
C
Memory ON
T1 : Delay on pick-up
T2 : Response time on immersion
T3 : Response time on emersion
T4 : Response time on power-down
Programming
Operating principle
Control of the level of a conductive liquid at specific points (high and low levels) with an alarm for a
level which is abnormally high or low.
The principle is based on measurement of the apparent resistance of the liquid between
submerged probes. When this value is lower than the present threshold on the unit front face, the
output relay R1 and/or the alarm relay R2 change state.
The avoid electrolytic phenomena, an AC current runs across the probes.
Adjusting sensitivity
Set the sensitivity so that the relay will change state when the probes are in contact with the liquid.
Then check that the relay returns to its initial position as soon as the probes emerge.
In certain applications, fine-tuning the sensitivity prevents inappropriate detection, such as the
presence of foam or bubbles on the surface or the occurrence of leakage impedance between
probes (extended line capacity, humidity, etc).
Note :
Latching of the alarm relay R2 in de-energised state if a fault occurs can the programmed via a
switch on the underside of the underside of the unit (only when the unit is switched off). To reset
alarm relay R2, cut the power, as long as the levels are reset.
Programming
The FN level controller can be programmed using 3 switches on the lower panel :
Note :
Memory, Alarm and Function must only be selected when the unit is switched off.
B
Memory
C
Alarm
D
Function
E
Low
F
Emptying
G
High
H
Filling
1
2
T3T3 T2
T1
T2
Un
Al.
Max
Min
R1
R2
T2
T1 T3
T3
T4
T2
Un
Al.
Max
Min
R1
R2
1
2
1
3
4
5
7
6
2
10
OFF ON
10
anglais.book Page 118 Mardi, 28. octobre 2003 5:20 17
Cyan Quadrichromie 75,0° 120,0 LPP
anglais.book Page 118 Mardi, 28. octobre 2003 5:20 17
Magenta Quadrichromie 15,0° 120,0 LPP
anglais.book Page 118 Mardi, 28. octobre 2003 5:20 17
Jaune Quadrichromie 0,0° 120,0 LPP
anglais.book Page 118 Mardi, 28. octobre 2003 5:20 17
Noir Quadrichromie 45,0° 120,0 LPP

84870504

Mfr. #:
Manufacturer:
Crouzet
Description:
Controllers 8A 230VAC SPDT DIN Rail
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet