11-2016, Rev. 1116
www.te.com
© 2015 Tyco Electronics Corporation,
a TE Connectivity Ltd. company
Datasheets and product specification
according to IEC 61810-1 and to be used
only together with the ‘Definitions’ section.
Datasheets and product data is subject to the
terms of the disclaimer and all chapters of
the ‘Definitions’ section, available at
http://relays.te.com/definitions
Datasheets, product data, ‘Definitions’ sec-
tion, application notes and all specifications
are subject to change.
1
SCHRACK
General Purpose Relays
Force Guided Relays
Force Guided Relay SR2M
Coil Data (continued)
Coil versions, DC-coil
Coil Rated Operate Release Coil Rated coil
code voltage voltage voltage resistance power
VDC VDC VDC Ω±10%
1)
mW
005 5 3.8 0.5 35.7 700
006 6 4.5 0.6 51 706
009 9 6.8 0.9 116 698
012 12 9 1.2 206 699
015 15 11.3 1.5 321 701
018 18 13.5 1.8 483 671
021 21 16 2.1 630 700
024 24 18 2.4 823 700
036 36 27 3.6 1851 700
040 40 30 4.0 2286 700
048 48 36 4.8 3291
1)
700
060 60 45 6 5142
1)
700
080 80 60 8 9143
1)
700
110 110 83 11 17285
1)
700
1)
Coil resistance ±12%.
All figures are given for coil without pre-energization, at ambient temperature +23°C.
Insulation
Initial dielectric strength
between open contacts 1500V
rms
between contact and coil 4000V
rms
between adjacent contacts 3000V
rms
Clearance/creepage
between open contacts microdisconnection
between contact and coil ≥8/8mm
between adjacent contacts ≥5.5/5.5mm
Insulation to EN 50178, type of insulation
between contact and coil reinforced
between adjacent contacts reinforced
n
2 pole relay with force guided contacts according to EN 50205
n
Reinforced insulation between poles
n
Version P1 for use in sockets
Typical applications
Emergency shut-off, press control, machine control, elevator and escalator
control, safety relays
Approvals
VDE 116064, UL E214025, TUV 968/EZ 111, CCC 2014010305743065
Technical data of approved types on request
Contact Data
Contact arrangement 1 form A + 1 form B contacts
(1 NO + 1 NC) or
2 form C contacts (2 CO)
According EN50205 only 1NO / 1NC (11-14 and 22-21 or 12-11 and
21-24) shall be used as force guided contacts.
Rated voltage 250VAC
Max. switching voltage 400VAC
Rated current 6A
Contact material AgNi
Contact style single contact, force guided
1 form A + B, 1 NO + 1NC type A according to EN 50205
2 form C, 2CO type B according to EN 50205
Min. recommended contact load 5V/10mA
Initial contact resistance ≤100mΩ at 1A, 24VDC
≤20Ω at 10mA, 5VDC
Frequency of operation, with/without load 6/300min
-1
Contact ratings, IEC60947-5-1,
on 1 form A (NO) contact AC15 - 250V/3A
DC13 - 24V/3A
on the basis of DC13 - 24V/6A
under conditions specified in
product spec. 2158001
Mechanical endurance 10x10
6
operations
Coil Data
Coil voltage range 5 to 110VDC
F0188-D