Thermal-Magnetic Circuit Breakers 3600/3900
www.e-t-a.de
1646
1
1
Description
Typical applications
Ordering information
Technical data
Single pole thermal-magnetic circuit breaker with tease-free, trip-free,
snap action mechanism and two button operation (M-type TM CBE
to EN 60934). Designed for plug-in mounting with E-T-A sockets
17-P10-Si, 23-P10-Si, 63-P10-Si; or panel mounting using E-T-A clips.
Featuring an unprotected shunt tap terminal and optional auxiliary
contacts. Type 3900 offers lower internal resistance values and is fitted
as standard with auxiliary contacts and an intermediate reset position
in which all contacts are isolated.
Approved to CBE standard EN 60934 (IEC 60934).
Process control systems, instrumentation, communications systems,
rail vehicles.
3600 3900
standard type low-resistance type
For further details please see chapter: Technical Information
Voltage rating AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 65 V)
Current rating range 3600: 0.05...16 A
3900: 0.05...10 A
Auxiliary circuit 1 A, AC 240 V / DC 65 V
Typical life 5,000 operations at 1 x I
N
, inductive
5,000 operations at 2 x I
N
, resistive
Ambient temperature -30...+60 °C (-22...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
main/aux. circuit AC 1,500 V
aux. circuit 4-5/6-7 AC 840 V
Insulation resistance >100 MΩ (DC 500 V)
Interrupting capacity I
cn
3600 3900
0.05...0.8 A 0.05...0.2 A self-limiting
1...2 A 0.3...2 A 200 A
2.5...16 A 2.5...10 A 400 A
Interrupting capacity I
N
U
N
(UL 1077) 0.05...16 A AC 250 V 1,000 A
type 3600: 0.05...16 A DC 80 V 1,000 A
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration 5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock 25 g (11 ms) to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass approx. 45 g
Type No.
3600 standard version with shunt tap terminal -3
3900 low-resistance version
Terminal design
P10 blade terminals 6.3-0.8 (QC .250)
Auxiliary contacts (3900: intermediate position as standard)
Si with blade terminals 6.3-08,one each NO/NC,
Current ratings
0.05...16 A (type 3600)
0.05...10 A (type 3900)
3600 - P10 - Si - 10 A ordering example
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Standard current ratings and typical internal resistance values
Current
ratings
(A)
Internal resistance
(Ω)
Current
ratings
(A)
Internal resistance
(Ω)
3600 3900 3600 3900
0.05 447 211 3 0.19 0.054
0.1 131 48 4 0.090 0.035
0.2 40 12.4 5 0.061 0.025
0.3 19.3 5.4 6 0.041 ≤ 0.02
0.4 10.4 3.1 7 0.034 ≤ 0.02
0.5 7.1 2.0 8 ≤ 0.02 ≤ 0.02
0.6 4.3 1.32 10 ≤ 0.02 ≤ 0.02
0.8 2.5 0.76 12 ≤ 0.02
1 1.67 0.49 14 ≤ 0.02
1.5 0.61 0.21 15 ≤ 0.02
2 0.38 0.101 16 ≤ 0.02
2.5 0.24 0.078
Preferred types Standard current ratings (A)
0.5 1 2 4 8 10 16
3600-P10-Si-
x x x x x x x
3900-P10-Si-
x x x x
Preferred types