3900-P10-SI-10A

Thermal-Magnetic Circuit Breakers 3600/3900
www.e-t-a.de
1646
1
1
Description
Typical applications
Ordering information
Technical data
Single pole thermal-magnetic circuit breaker with tease-free, trip-free,
snap action mechanism and two button operation (M-type TM CBE
to EN 60934). Designed for plug-in mounting with E-T-A sockets
17-P10-Si, 23-P10-Si, 63-P10-Si; or panel mounting using E-T-A clips.
Featuring an unprotected shunt tap terminal and optional auxiliary
contacts. Type 3900 offers lower internal resistance values and is fitted
as standard with auxiliary contacts and an intermediate reset position
in which all contacts are isolated.
Approved to CBE standard EN 60934 (IEC 60934).
Process control systems, instrumentation, communications systems,
rail vehicles.
3600 3900
standard type low-resistance type
For further details please see chapter: Technical Information
Voltage rating AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 65 V)
Current rating range 3600: 0.05...16 A
3900: 0.05...10 A
Auxiliary circuit 1 A, AC 240 V / DC 65 V
Typical life 5,000 operations at 1 x I
N
, inductive
5,000 operations at 2 x I
N
, resistive
Ambient temperature -30...+60 °C (-22...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
main/aux. circuit AC 1,500 V
aux. circuit 4-5/6-7 AC 840 V
Insulation resistance >100 MΩ (DC 500 V)
Interrupting capacity I
cn
3600 3900
0.05...0.8 A 0.05...0.2 A self-limiting
1...2 A 0.3...2 A 200 A
2.5...16 A 2.5...10 A 400 A
Interrupting capacity I
N
U
N
(UL 1077) 0.05...16 A AC 250 V 1,000 A
type 3600: 0.05...16 A DC 80 V 1,000 A
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration 5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock 25 g (11 ms) to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass approx. 45 g
Type No.
3600 standard version with shunt tap terminal -3
3900 low-resistance version
Terminal design
P10 blade terminals 6.3-0.8 (QC .250)
Auxiliary contacts (3900: intermediate position as standard)
Si with blade terminals 6.3-08,one each NO/NC,
Current ratings
0.05...16 A (type 3600)
0.05...10 A (type 3900)
3600 - P10 - Si - 10 A ordering example
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Standard current ratings and typical internal resistance values
Current
ratings
(A)
Internal resistance
(Ω)
Current
ratings
(A)
Internal resistance
(Ω)
3600 3900 3600 3900
0.05 447 211 3 0.19 0.054
0.1 131 48 4 0.090 0.035
0.2 40 12.4 5 0.061 0.025
0.3 19.3 5.4 6 0.041 ≤ 0.02
0.4 10.4 3.1 7 0.034 ≤ 0.02
0.5 7.1 2.0 8 ≤ 0.02 ≤ 0.02
0.6 4.3 1.32 10 ≤ 0.02 ≤ 0.02
0.8 2.5 0.76 12 ≤ 0.02
1 1.67 0.49 14 ≤ 0.02
1.5 0.61 0.21 15 ≤ 0.02
2 0.38 0.101 16 ≤ 0.02
2.5 0.24 0.078
Preferred types Standard current ratings (A)
0.5 1 2 4 8 10 16
3600-P10-Si-
x x x x x x x
3900-P10-Si-
x x x x
Preferred types
Thermal-Magnetic Circuit Breakers 3600/3900
www.e-t-a.de
1646
2
1
Dimensions Internal connection diagrams
14 63752
20
2
38
12.5
operating area
(reinforced insulation)
mounting area
.787
.079
1.50
.492
ø11.5
ø6.5
ø4
ø8.5
6.8
6 x 6.8 = 40.8
10
19
51
2
5
ON
11
OFF
blade terminals
DIN 46244-A6.3-0.8
(QC .250)
8.5
50
20
13
43
11.5
current rating in A
2
14 63752
.157
.079
.256
.453
.335
.433
.197
2.01
.394
.268
6 x .268 = 1.61
.748
.787
1.69
.512
.335
1.97
.453
-P10-Si
3 (from I
N
=8 A)
3 (from I
N
=8 A)
7
6
line 1
2
line 1
3
2
5
4
I
>
3
I
>
with shunt terminal (standard)
and auxiliary contacts (-Si) only 3600
123
Terminal design -P10
Installation drawing
Typical time/current characteristics
+60 °C
+140 °F
+23 °C
+73.4 °F
-30 °C
-22 °F
… times rated current
12468102040
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
Trip time in seconds
12468102040
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
Trip time in seconds
Trip time in seconds
12468102040
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
3900 0.05…10 A DC
2)
3600 8…16 A AC
1)
3600 0.05…7 A AC
1)
1)
Magnetic tripping currents are increased by 20 % on DC supplies.
2)
Magnetic tripping currents are decreased by 20 % on AC supplies.
This is a metric design and millimeter dimensions take precedence (
mm
)
inch
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the
circuit breaker current ratings by the derating factor shown below. See also
section Technical information.
Ambient temp. °F
°C
-22
-30
-4
-20
+14
-10
+32
0
+73.4
+23
+104
+40
+122
+50
+140
+60
Derating factor
0.76 0.79 0.83 0.88 1 1.08 1.16 1.24
Thermal-Magnetic Circuit Breakers 3600/3900
www.e-t-a.de
1646
3
1
Thermal-Magnetic Circuit Breakers 3600/3900
Accessories
blade terminal DIN 46244 part 2
C profile (2xA2.8-0.8) (QC 2x.110)
depth
10 mm
(.394 in.)
adapter X20040901
symmetrical rail
EN 50022-35x7.5
polarization recess
G-profile
EN 50035-G32
8.5
25.8
6.5
80
33.3
10
5
1.4
12.5
41.3
45.8
retaining clip
10
2.8
-P70
1
11
23
2(k)
12
24
2(i)
1
11
23
2(k)
12
24
2(i)
1.80
1.63
.335
.256
1.02
3.15
1.31
.055
.197
.492
.394
.394
.110
depth
10 mm
(.394 in.)
adapter X20040901
symmetrical rail
EN 50022-35x7.5
polarized blade terminal
DIN 46244-A6.3-0.8 (QC .250)
polarization recess
G-profile
EN 50035-G32
slot fitting labels from
Phoenix, Weidmüller
8.5
25.8
6.5
80
33.3
10
5
1.4
12.5
41.3
45.8
retaining clip
10
6.3
-P10
1
11
23
2(k)
12
24
2(i)
1
11
23
2(k)
12
24
2(i)
1.80
1.63
.335
.256
1.02
3.15
1.31
.055
.197
.492
.394
.394
.248
Sockets
23-P10-Si 63-P10-Si
(up to 16 A max. load)
Retaining clip Y 300 581 03 to special order.
Sockets
17-P10-Si
(up to 16 A max. load)
17-P10-Si-20025
mounted with adapter
Retaining clip Y 300 581 11 to special order.
Sockets
17-P70-Si
(up to 16 A max. load)
17-P70-Si-20025
mounted with adapter
Retaining clip Y 300 581 11 to special order.
6 x 6.8 = 40.8
6 x .268 = 1.61
retaining
clip
22.2
21
10
2
max. 30
6
3.5
6.8
7.4
4.4
64
50
57.4
25
12.5
4.4
7.4
12.5
6.25
64
50
75
12.5
polarized blade terminals
DIN 46244-A6.3-0.8 (QC .250)
polarized
recess
.173
.291
2.52
1.97
2.26
.492
.984
.291
.173
.394
.827
.874
.079
.236
max. 1.18
2.52
.492
1.97
2.95
50
1.97
2.26
57.4
.268
.138
.492
.246
slot fitting labels from
Phoenix, Weidmüller
63
EN 50022-35x7,5
EN 50035-G32
115
47
42,5
51 11,5
57
6
25
25
max. 38
11
14
17 plus
11
14
2.2
12.1
12.2
1.2
Line
1.1
Line
2.1
slot for fitting labels from
Phoenix, Weidmüller, Wieland
slot for busbar
module
right-side terminal block
left-side terminal block
symmetrical rail
G-profile
test socket
Module 17plus
For technical data see section Power Distribution Systems
Approvals
Authority Standard Voltage ratings Current ratings
3600:
VDE
IEC/EN 60934
AC 240 V
DC 65 V
0.05...16 A
0.05...16 A
UL
C22.2 No. 235
AC 250 V
DC 80 V
0.05...16 A
0.05...16 A
CSA UL 1077 AC 250 V
DC 80 V
0.05...16 A
0.05...16 A
3900:
VDE
IEC/EN 60934
AC 240 V
DC 65 V
0.05...10 A
0.05...10 A
Power-D-Box with sockets pre-wired 19BGT2 2U
for 18, 24 or 30 circuits.
For technical data see product group Power Distribution
Systems.

3900-P10-SI-10A

Mfr. #:
Manufacturer:
E-T-A Circuit Breakers
Description:
Circuit Breakers Thermal-magnetic circuit breaker with auxiliary contacts, socket mounting
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union