3215000

https://www.phoenixcontact.com/us/products/3215000
02/19/2016Page1/6
High-current terminal block-PTPOWER 150-3215000
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
High-current terminal block, Connection method:Power-Turn connection, Number of positions:1, Cross section:
50 mm²-150 mm², AWG:1/0-300 kcmil, Width:31 mm, Color:gray, Mounting type:NS 35/15
Product Features
Quick and easy connection is now also possible for large conductors with the high-current terminal block
The Push-in connection terminal blocks are characterized by the system features of the CLIPLINE complete system and by easy and tool-free wiring
of conductors with ferrules or solid conductors
The compact design enables wiring in a confined space
In addition to using the existing test connection, pick-off terminal blocks can be connected, each of which can also accommodate two test cables
Key Commercial Data
Packing unit 1 pc
Minimum order quantity 3 pc
Weight per Piece (excluding packing) 340.0 g
Custom tariff number 85369010
Country of origin Poland
Technical data
General
Number of levels 1
Number of connections 2
Nominal cross section 150 mm²
Color gray
Insulating material PA
Flammability rating according to UL 94 V0
Rated surge voltage 8 kV
Degree of pollution 3
Overvoltage category III
https://www.phoenixcontact.com/us/products/3215000
02/19/2016Page2/6
High-current terminal block-PTPOWER 150-3215000
Technical data
General
Insulating material group I
Connection in acc. with standard IEC 60947-7-1
Maximum load current 309 A (with 150 mm² conductor cross section)
Nominal current I
N
309 A
Nominal voltage U
N
1500 V
Open side panel No
Number of positions 1
Shock protection test specification DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection guaranteed
Finger protection guaranteed
Result of surge voltage test Test passed
Surge voltage test setpoint 14.8 kV
Result of power-frequency withstand voltage test Test passed
Power frequency withstand voltage setpoint 6 kV
Result of the test for mechanical stability of terminal points (5 x conductor
connection)
Test passed
Result of bending test Test passed
Bending test rotation speed 10 rpm
Bending test turns 135
Bending test conductor cross section/weight 50 mm² / 9.5 kg
150 mm² / 15 kg
Tensile test result Test passed
Conductor cross section tensile test 50 mm²
Tractive force setpoint 236 N
Conductor cross section tensile test 150 mm²
Tractive force setpoint 427 N
Result of tight fit on support Test passed
Tight fit on carrier NS 35/15-2,3 UNGELOCHT
Setpoint 15 N
Result of voltage-drop test Test passed
Requirements, voltage drop ≤ 3.2 mV
Result of temperature-rise test Test passed
Short circuit stability result Test passed
Conductor cross section short circuit testing 150 mm²
Short-time current 18 kA
Result of aging test Test passed
Ageing test for screwless modular terminal block temperature cycles 192
https://www.phoenixcontact.com/us/products/3215000
02/19/2016Page3/6
High-current terminal block-PTPOWER 150-3215000
Technical data
General
Result of thermal test Test passed
Proof of thermal characteristics (needle flame) effective duration 30 s
Oscillation, broadband noise test result Test passed
Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2008-03
Test spectrum Service life test category 1, class B, body mounted
Test frequency
f
1
= 5 Hz to f
2
= 150 Hz
ASD level
0.964 (m/s
2
)
2
/Hz
Acceleration 0.58 g
Test duration per axis 5 h
Test directions X-, Y- and Z-axis
Shock test result Test passed
Test specification, shock test DIN EN 50155 (VDE 0115-200):2008-03
Shock form Half-sine
Acceleration 5 g
Shock duration 30 ms
Number of shocks per direction 3
Test directions X-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B) 130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 125 °C
Static insulating material application in cold -60 °C
Dimensions
Width 31 mm
Length 116.4 mm
Height NS 35/15 116.5 mm
Connection data
Connection method Power-Turn connection
Connection in acc. with standard IEC 60947-7-1
Conductor cross section solid min. 50 mm²
Conductor cross section solid max. 150 mm²
Conductor cross section AWG min. 1/0
Conductor cross section AWG max. 300 kcmil
Conductor cross section flexible min. 50 mm²
Conductor cross section flexible max. 150 mm²
Min. AWG conductor cross section, flexible 1/0
Max. AWG conductor cross section, flexible 300 kcmil
Conductor cross section flexible, with ferrule without plastic sleeve min. 50 mm²