PSP-600-24

SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.5
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY(Typ.)
AC CURRENT (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
1500ms, 50ms at full load
20ms at full load
88 ~ 264VAC 124 ~ 370VDC
47 ~ 63Hz
84%79% 85% 85% 86% 86%
6.8A/115VAC 3.4A/230VAC
20A/115VAC 40A/230VAC
<1.3mA/240VAC
105 ~ 135% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
UL60950-1, TUV EN60950-1, CCC GB4943.1 EAC TP TC 004 approved
,
-20 ~ +60 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
non-condensing
±℃ 0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
116.4K hrs min. MIL-HDBK-217F (25 )
170*120*93mm (L*W*H)
File Name:PSP-600-SPEC 2018-01-15
12V5V 13.5V 15V 24V 27V
50A80A 44.5A 40A 25A 22.2A 12.5A
0 ~ 50A0 ~ 80A 0 ~ 44.5A 0 ~ 40A 0 ~ 25A 0 ~ 22.2A 0 ~ 12.5A
600W400W 600.75W 600W 600W 599.4W 600W
240mVp-p180mVp-p 240mVp-p 240mVp-p 240mVp-p 240mVp-p 300mVp-p
10 ~ 13.2V4.75 ~ 5.5V 12 ~ 15V 13.5 ~ 18V 20 ~ 26.4V 24 ~ 30V 41 ~ 56V
±1.0%±2.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%
±0.5%±1.0%
±0.5%±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
PSP-600-12PSP-600-5 PSP-600-13.5 PSP-600-15 PSP-600-24 PSP-600-27 PSP-600-48
1.9Kg; 8pcs/15.5Kg/1.06CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.360 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. The operating altitude is 2000 meters for CCC, 3000 meters for UL,TUV. The ambient temperature derating of 5 /1000m is needed for operating altitude
greater than 2000m (6500ft).
OVER VOLTAGE
13.8 ~ 16.2V5.75 ~ 6.75V 15.5 ~ 18.2V 18 ~ 21V 27.6 ~ 32.4V 31 ~ 36.5V 57.6 ~ 67.2V
Universal AC input / Full range
Built-in active PFC function
Protections: Short circuit / Overload / Over voltage / Over temperature
Forced air cooling by built-in DC fan
With DC OK Signal output
Current sharing up to 2400W(3+1)
Built-in remote ON-OFF control
Built-in remote sense function
Fixed switching frequency at PFC:88KHz PWM:100KHz
Operating altitude up to 3000 meters ( )Note.6
3 years warranty
Features :
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
ENVIRONMENT
PROTECTION
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, GB9245, GB17625.1, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, light industry level, criteria A, EAC TP TC 020
0.95/230VAC 0.99/115VAC at full load
SAFETY &
EMC
(Note 4)
PSP-600 series
Protection type : Shut down o/p voltage, re-power on to recover
REMOTE CONTROL
POK SIGNAL
FUNCTION
RC+/RC-: Short = power on ; Open = power off
PSU turn on: 3.3V ~ 5.6V PSU turn off: 0V ~ 1V
OVER TEMPERATURE
Shut down o/p voltage, re-power on to recover
600W with PFC and Parallel Function
87%
48V
EMC IMMUNITY
EMC EMISSION
( except for 5V,12V,13.5V )
File Name:PSP-600-SPEC 2018-01-15
Mechanical Specification
Derating Curve Output Derating VS Input Voltage
Case No.910A Unit:mm
AMBIENT TEMPERATURE ( ) INPUT VOLTAGE (V) 60Hz
11588 100 135 155 230 264
90
100
80
70
60
50
40
LOAD (%)
-2001020304540 50 60 (HORIZONTAL)
20
40
50
60
80
100
LOAD(%)
PWM
CIRCUIT
DETECTION
O.L.P.
EMI
FILTER
RECTIFIERS
&
P.F. C .
POWER
SWITCHING
FILTER
&
RECTIFIERS
+V
RS+
R-S
-V
I/P
FG
CONTROL
O.V.P.
O.T.P.
INRUSH
CURRENT
ACTIVE
LIMITING
FAN
O.C.P.
RC
RC.G.
POK
SIGNAL CONTROL
CURRENT
SHARING CIRCUIT
P
PFC fosc : 88KHz
PWM fosc : 100KHz
12V
Others
RS Connector(CN5) : JST B-XH or equivalent
Pin No.
1
2
Assignment Mating Housing
JST XHP
JST SXH-001T
or equivalent
or equivalent
Terminal
RS+
RS-
Terminal Pin No. Assignment
Pin No.
1
3
4
5
6
7
8~11
12~15
2
Assignment
FG
P(Current Share)
POK
R.C.G
R.C.
DC OUTPUT +V
DC OUTPUT -V
AC/N
AC/L
14 max.
PSP-600 series
600W with PFC and Parallel Function
Block Diagram
9.5
CN5
11.5
8
11.5
120
15
14
13
1211
1098
76
5
4
3
21
170
185
150
150
2-M3 L=4mm max.
93
100
50
58.3
2-M3 L=4mm max.
2-M3 L=4mm max.
Air flow
direction
2-M3 L=4mm max.
12
Control Terminal Instruction Manual
POK Signal
POK Signal is the voltage difference between
+V +V +V
LLLNNNFG FG FGPPP
POK POK POK
RCG RCG RCG
RC RC RC
RS+ RS+ RS+
RS- RS- RS-
+V +V +V
LOAD LOAD LOAD
+++---
+V +V +V+V +V +V-V -V -V-V -V -V-V -V -V-V
POK(+) RCG(-)
-V -V
"RCG" and "POK" pin output POK Signal for TTL level signal
PSU turn on: 3.3V ~ 5.6V
PSU turn off: 0V ~ 1V
Parallel Operation with Remote Sensing
Remote Sensing
Power ON: RCG and RC for short
Remote Control
Power OFF: RCG and RC for open
RCG RC
LOAD
PSU PSU PSU PSU
++++
----
PPPP
RCG RCG RCG RCG
RS+ RS+ RS+ RS+RS- RS- RS- RS-
+V
+S
-V
-S
(1)Parallel operation is available by connecting the units shown as below (+S,-S and P are connected mutually in parallel) :
(2)The voltage difference among each output should be minimized that less than 0.2V is required.
(3)The total output current must not exceed the value determined by the following equation (Output current at parallel operation)
=(The rated current per unit) x (Number of unit) x 0.9.
(4) In parallel operation 4 units is the maximum, please consult the manufacture for other applications.
(5) When remote sensing is used in parallel operation, the sensing wire must be connected only to the master unit.
(6) When in parallel operation, the minimum output load should be greater than 3% of total output load.
(Min. load > 3% rated current per unit x number of unit)
File Name:PSP-600-SPEC 2018-01-15
PSP-600 series
600W with PFC and Parallel Function

PSP-600-24

Mfr. #:
Manufacturer:
Description:
Switching Power Supplies 600W 24V 25A PFC/Parallel Func
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union