2902832

https://www.phoenixcontact.com/pi/products/2902832
08/19/2018Page1/6
Frequency transducer-MINI MCR-SL-F-UI-NC-2902832
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
The configurable frequency transducer is suitable for the connection of NAMUR proximity sensors as well as
for sensors with NPN and PNP outputs. Configurable via DIP switch and teach-in wheel. Screw connection,
standard configuration.
Product Description
The configurable 3-way isolated frequency transducer is suitable for the connection of NAMUR proximity sensors (IEC 60947-5-6 and EN 50227) as
well as for sensors with NPN and PNP outputs that generate a frequency signal.
The measured values are converted into a linear current or voltage signal.
The device is configured via DIP switches. Alternatively, the frequency range can be configured with extended options via the teach-in wheel. The
measuring transducer supports fault monitoring.
Key Commercial Data
Packing unit 1 STK
GTIN
GTIN 4046356682367
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 6.2 mm
Height 93.1 mm
Depth 102.5 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Input data
Frequency input Frequency input
https://www.phoenixcontact.com/pi/products/2902832
08/19/2018Page2/6
Frequency transducer-MINI MCR-SL-F-UI-NC-2902832
Technical data
Input data
Configurable/programmable Yes
Frequency measuring range 0.002 Hz ... 20 kHz (DIP switch)
Available input sources NPN/PNP transistor outputs
NAMUR initiators
Floating relay contact (dry contact)
Max. input amplitude 30 V (incl. DC voltage)
Output data
Output name Voltage output / current output
Number of outputs 1
Configurable/programmable Yes
Voltage output signal 0 V ... 5 V
1 V ... 5 V
0 V ... 10 V
10 V ... 0 V
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. output voltage approx. 12.3 V
Max. output current 24.6 mA
Load/output load voltage output ≥ 10 kΩ
Load/output load current output 500 Ω (at 20 mA)
Ripple
< 20 mV
PP
< 20 mV
PP
(at 500 Ω)
Step response (0–99%) < 35 ms (At f > 500 Hz)
Power supply
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail according to
EN60715))
Typical current consumption
< 28 mA (at I
OUT
= 20 mA, 24 V DC, load 500 Ω)
Power consumption
< 800 mW (at I
OUT
= 20 mA, 9.6 V DC, load 500 Ω)
Connection data
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 12
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
https://www.phoenixcontact.com/pi/products/2902832
08/19/2018Page3/6
Frequency transducer-MINI MCR-SL-F-UI-NC-2902832
Technical data
Connection data
Stripping length 12 mm
Screw thread M3
General
No. of channels 1
Transmission error in the set measuring range 0.1 %
Maximum temperature coefficient 0.01 %/K
Status display LED red
Operating elements Press/slide button
Protective circuit Transient protection
Electrical isolation Basic insulation according to EN 61010
Overvoltage category II
Degree of pollution 2
Rated insulation voltage 50 V AC/DC
Test voltage, input/output/supply 1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color green
Housing material PBT
Mounting position any
Assembly instructions
The T connector can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715.
Conformance CE-compliant
ATEX  II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC
Certificate of classification DNV GL 14085-15HH
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2
EMC data
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 0.1 %
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 2 %
Designation Conducted interferences

2902832

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Terminal Block Interface Modules MINI MCR-SL-F-UI-NC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet