https://www.phoenixcontact.com/us/products/2900345
10/28/2014Page2/6
Relay Module-PLC-RPT-230UC/21-21AU/RWF-2900345
Technical data
Ambient conditions
Ambient temperature (storage/transport) -40 °C ... 85 °C
Coil side
Nominal input voltage U
N
230 V AC
Input voltage range in reference to U
N
see diagram
Typical input current at U
N
4.8 mA (with AC)
Typical response time 20 ms
Typical release time 60 ms
Operating voltage display Yellow LED
Protective circuit Bridge rectifier
Contact side
Contact type 2 PDT
Contact material AgNi, hard gold-plated
Maximum switching voltage 30 V AC
36 V DC
Minimum switching voltage 100 mV
Maximum inrush current 50 mA
Min. switching current 1 mA
Limiting continuous current 50 mA
Interrupting rating (ohmic load) max. 1.2 W (at 24 V DC)
Switching capacity in acc. with DIN VDE 0660/IEC 60947 2 A (24 V (DC13), in acc. with DIN VDE 0660/IEC 60947)
0.2 A (220 V DC / 230 V AC (DC13), in acc. with DIN VDE 0660/IEC
60947)
3 A (220 V DC / 230 V AC (AC15), in acc. with DIN EVDE 0660/IEC
60947)
Note the following values are applicable if a gold layer is destroyed
Maximum switching voltage
250 V AC/DC (Separating plate PLC-ATP must be installed for voltages
larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent
modules.)
Minimum switching voltage 5 V AC/DC
Limiting continuous current 6 A
Maximum inrush current 8 A
Min. switching current 10 mA
Interrupting rating (ohmic load) max. 140 W (at 24 V DC)
85 W (at 48 V DC)
60 W (at 60 V DC)
44 W (at 110 V DC)
60 W (at 220 V DC)