K8AB-VS3 24VAC/DC

4 Single-phase Voltage Relay K8AB-VS Cat. No. N143-E1-01
Connections
Wiring Diagram
Overcurrent Operation Diagram
(Output: Normally Closed)
Note: The power ON lock prevents unnecessary alarms from being
generated during the instable period when the power is first
turned on. There is no relay output during timer operation.
Undercurrent Operation Diagram
(Output: Normally Open)
Note: The power ON lock prevents unnecessary alarms from being
generated during the instable period when the power is first
turned on. There is no relay output during timer operation.
Nomenclature
Front
Indicators
Setting Knobs
T1
T
Input
Hysteresis
(5% to 50% of operating value)
Lit
Flashing
Operating value
Control power
Relay
Alarm indicator
T: Operating time (0.1 to 30 s)
T1: Startup lock time (1 or 5 s)
Control power
Relay
Operating value
Alarm indicator
Input
Lit
Flashing
T1
T1: Power ON lock (1 or 5 s)
T
T: Operating time (0.1 to 30 s)
Hysteresis
(5% to 50% of operating value
)
Model Measuring range Connection
K8AB-VS1 6 to 60 mV AC/DC V1-COM
10 to 100 mV AC/DC V2-COM
30 to 300 mV AC/DC V3-COM
K8AB-VS2 1 to 10 V AC/DC V1-COM
3 to 30 V AC/DC V2-COM
15 to 150 V AC/DC V3-COM
K8AB-VS3 20 to 200 V AC/DC V1-COM
30 to 300 V AC/DC V2-COM
60 to 600 V AC/DC V3-COM
Output
COM
A1
A2
V1
V2
V3
14
12
11
Single-phase power
Operating
power
Alarm
Input
Load
Power indicator
Relay status indicator
Voltage knob (SV)
Hysteresis knob (HYS.)
Operating time knob (T
)
Alarm indicator
Item Meaning
Power indicator (PWR:
Green)
Lit when power is being supplied.
Relay status indicator (RY:
Yellow)
Lit when relay is operating.
Alarm indicator (ALM: Red) Lit when there is an overvoltage or
undervoltage.
The indicator flashes to indicate the
error status after the input has
exceeded the threshold value while the
operating time is being clocked.
Item Usage
Current knob (SV) Used to set the current to 10% to 100%
of maximum rated input current.
Hysteresis knob (HYS.) Used to set the rest value to 5% to 50%
of the operating value.
Operating time knob (T) Used to set the operating time to 0.1 to
30 s.
Cat. No. N143-E1-01 Single-phase Voltage Relay K8AB-VS 5
Function Selection DIP Switch
DIP Switch Functions
Dimensions
ON
SW2
DIP Switch
SW3
SW4
SW1
Function Default
SW1 Power ON lock
time
OFF 1 s OFF
ON 5 s
SW2 Resetting method OFF Manual reset OFF
ON Automatic reset
SW3 Relay drive
method
OFF Normally open (normally
OFF)
OFF
ON Normally closed (normally
ON)
SW4 Operating mode OFF Overvoltage monitoring OFF
ON Undervoltage monitoring
22.5
5
90
100
5
K8AB-VS
6 Single-phase Voltage Relay K8AB-VS Cat. No. N143-E1-01
Safety Precautions
Precautions for Safe Use
Make sure to follow the instructions below to ensure safety.
1. Do not use or keep this product in the following environments.
Outdoors, or places subject to direct sunlight or wearing
weather.
Places where dust, iron powder, or corrosive gases (in
particular, sulfuric or ammonia gas) exist.
Places subject to static electricity or inductive noise.
Places where water or oil come in contact with the product.
2. Make sure to install this product in the correct direction.
3. There is a remote risk of electric shock. Do not touch terminals
while electricity is being supplied.
4. Make sure to thoroughly understand all instructions in the
Instructions Manual before handling this product.
5. Make sure to confirm terminal makings and polarity for correct
wiring.
6. Tighten terminal screws firmly using the following torque.
Recommended torque: 0.54 N·m
7. Operating ambient temperature and humidity for this product
must be within the indicated rating when using this product.
8. There is a remote risk of explosion. Do not use this product where
flammable or explosive gas exists.
9. Make sure that no weight rests on the product after installation.
10.To enable an operator to turn off this product easily, install
switches or circuit breakers that conform to relevant requirements
of IEC60947-1 and IEC60947-3, and label them appropriately.
11.For DC input, use a SELV power-supply capable of overcurrent
protection. Specifically, a SELV power-supply has a double or
reinforced insulation for input and output, and output voltage of
30 Vr.m.s with 42.4 V at peak or DC60V maximum.
Recommended power-supply: Model S8VS-06024@. (Omron
product)
Precautions for Correct Use
For Proper Use
1. Do not use the product in the following locations.
Places subject to radiant heat from heat generating devices.
Places subject to vibrations or physical shocks.
2. Make sure to use setting values appropriate for the controlled
object. Failure to do so can cause unintended operation, and may
result in accident or corruption of the product.
3. Do not use thinner or similar solvent for cleaning. Use commercial
alcohol.
4. When discarding, properly dispose of the product as industrial
waste.
5. Only use this product within a board whose structure allows no
possibility for fire to escape.
About Installation
1. When wiring, use only recommended crimp terminals.
2. Do not block areas around the product for proper dissipation of
heat. (If you do not secure space for heat dissipation, life cycle of
the product will be compromised.)
3. To avoid electrical shocks, make sure that power is not supplied to
the product while wiring.
4. To avoid electrical shocks, make sure that power is not supplied to
the product when performing DIP switch settings.
Noise Countermeasures
1. Do not install the product near devices generating strong high
frequency waves or surges.
2. When using a noise filter, check the voltage and current and
install it as close to the product as possible.
3. In order to prevent inductive noise, wire the lines connected to the
product separately from power lines carrying high voltages or
currents. Do not wire in parallel with or on the same cable as
power lines.
Other measures for reducing noise include running lines along
separate ducts and using shield lines.
To avoid faulty operations,
malfunctions, or failure, observe the
following operating instructions.
1. When turning on the power, make sure to realize rated voltage
within 1 second from the time of first supply of electricity.
2. Make sure to use power supply for operations, inputs, and
transformer with the appropriate capacity and rated burden.
3. Maintenance and handling of this product may only be performed
by qualified personnel.
4. Distortion ratio of input wave forms must be 30% or less. Use of
this product with circuits that have large distortion in wave forms
may result in unwanted operations.
5. Using this product for thyristor controls or inverters will result in
errors.
6. When setting the volume, adjust the control from the minimum
side to the maximum side.