3211469

https://www.phoenixcontact.com/pi/products/3211469
08/21/2018Page1/4
Double-level terminal block-PTTB 2,5-LA 60 RD-3211469
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Double-level terminal block, nom. voltage:500 V, nominal current:20 A, connection method: Push-in
connection, cross section:0.14 mm²-4 mm², AWG:26-12, length:68 mm, width:5.2 mm, color:gray,
mounting: NS 35/7,5, NS 35/15, nom. voltage:500 V
Why buy this product
The Push-in connection terminal blocks are characterized by the system features of the CLIPLINE complete system and by easy and tool-free
wiring of conductors with ferrules or solid conductors
The compact design and front connection enable wiring in a confined space
In addition to the testing facility in the double function shaft, all terminal blocks provide an additional test connection
Key Commercial Data
Packing unit 50 STK
Minimum order quantity 50 STK
GTIN
GTIN 4046356433778
Technical data
General
Note The operating voltage is determined by the LED version.
Number of levels 2
Number of connections 4
Nominal cross section 2.5 mm²
Color gray
Insulating material PA
Flammability rating according to UL 94 V0
Rated surge voltage 4 kV
Overvoltage category III
Insulating material group I
Maximum power dissipation for nominal condition 0.77 W (the value is multiplied when connecting multiple levels)
Nominal current I
N
20 A
https://www.phoenixcontact.com/pi/products/3211469
08/21/2018Page2/4
Double-level terminal block-PTTB 2,5-LA 60 RD-3211469
Technical data
General
Maximum load current 24 A (with 4 mm² conductor cross section)
Nominal voltage U
N
500 V (the operating voltage is determined by the selected LED version)
Open side panel Yes
Relative insulation material temperature index (Elec.; UL 746 B) 130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE
0304-21))
130 °C
Static insulating material application in cold -60 °C
Behavior in fire for rail vehicles (DIN 5510-2) Test passed
Flame test method (DIN EN 60695-11-10) V0
Oxygen index (DIN EN ISO 4589-2) >32 %
NF F16-101, NF F10-102 Class I 2
NF F16-101, NF F10-102 Class F 2
Surface flammability NFPA 130 (ASTM E 162) passed
Specific optical density of smoke NFPA 130 (ASTM E 662) passed
Smoke gas toxicity NFPA 130 (SMP 800C) passed
Calorimetric heat release NFPA 130 (ASTM E 1354) 28 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
Dimensions
Width 5.2 mm
Length 68 mm
Height NS 35/7,5 47.5 mm
Height NS 35/15 55 mm
Connection data
Connection method Push-in connection
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 12
Conductor cross section flexible, with ferrule without plastic sleeve min. 0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max. 2.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min. 0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max. 2.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with
plastic sleeve, max.
0.5 mm²
Stripping length 10 mm
https://www.phoenixcontact.com/pi/products/3211469
08/21/2018Page3/4
Double-level terminal block-PTTB 2,5-LA 60 RD-3211469
Technical data
Connection data
Internal cylindrical gage A3
Standards and Regulations
Connection in acc. with standard CSA
Flammability rating according to UL 94 V0
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3 HL 1 - HL 3 HL 1 - HL 3 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3 HL 1 - HL 3 HL 1 - HL 3 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3 HL 1 - HL 3 HL 1 - HL 3 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3 HL 1 - HL 3 HL 1 - HL 3 HL 1 - HL 3
Drawings
Circuit diagram
Approvals
Approvals
Approvals
CSA / UL Recognized / cUL Recognized / LR / ABS / NK / BV / DNV GL / cULus Recognized
Ex Approvals
Approval details
CSA
http://www.csagroup.org/services-industries/product-listing/ 13631
B C
Nominal voltage UN 60 V 60 V
Nominal current IN 20 A 20 A
mm²/AWG/kcmil 26-12 26-12
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 60425
B C
Nominal voltage UN 300 V 300 V
Nominal current IN 20 A 20 A

3211469

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
DIN Rail Terminal Blocks PTTB 2,5-LA 60 RD
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet