SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
Note.4
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
BATTERY CUT OFF
AC OK
BATTERY LOW
AC CURRENT (Typ.)
800ms, 50ms/230VAC 1600ms, 50ms/115VAC at full load
50ms/230VAC 10ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
84%
CH1:28.98 ~ 37.26V
84%
21 1V±
Battery low voltage : < 22V
1.6A/115VAC 1A/230VAC
COLD START 30A/115VAC 60A/230VAC
<1mA / 240VAC
105 ~ 150% rated output power
CH1:14.49 ~ 18.63V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
Protection type : Hiccup mode, recovers automatically after fault condition is removed
10.5 0.5V±
UL60950-1, TUV EN60950-1, approvedEAC TP TC 004
Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A, EAC TP TC 020
-20 ~ +70 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH℃
±℃℃0.03%/ (0~50 ) on CH1 output
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
589.7K hrs min. MIL-HDBK-217F (25 )℃
PCB:101.6*50.8*29mm (L*W*H) ; Enclosed type:103.4*62*37mm (L*W*H)
PCB:0.13Kg; 96pcs/13.5Kg/0.89CUFT ; Enclosed type:0.29Kg; 45pcs/14Kg/0.67CUFT
FUNCTION
TTL open collector output, ON : AC OK ; OFF : AC Fail ; Ice : max. 30mA@ 50VDC
TTL open collector output, ON : Battery Low ; OFF : Battery OK ; Ice : max. 30mA@ 50VDC
Battery low voltage : < 11V
PSC-60B
27.6V
CH1
1.4A
0 ~ 2.15A
59.34W
240mVp-p
CH1: 24 ~ 29V
±1.0%
±0.5%
±0.5%
27.6V
CH2
0.75A
--------
--------
--------
--------
--------
13.8V
CH2
1.5A
--------
--------
--------
--------
--------
PSC-60A
13.8V
2.8A
0 ~ 4.3A
59.34W
120mVp-p
CH1: 12 ~ 15V
±1.0%
±0.5%
±0.5%
60W Single Output with Battery Charger(UPS Function)
Universal AC input / Full range
Models with L-Bracket and cover available (PSC-60x-C, x=A,B)
Protections: Short circuit / Overload / Over voltage
Battery low / protection Battery reverse polarity protection by fuse
Alarm signal for AC OK and Battery reverse low
Cooling by free air convection
100% full load burn-in test
2 years warranty
■
Features :
PSC-60 series
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
ENVIRONMENT
PROTECTION
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
SAFETY &
EMC
(Note 7)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
5. Heat sink HS1,HS2 can not be shorted.
6. Heat sink HS1 must have safety isolation distance with system case.
7. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.360 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
8. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
CH1
OUTPUT NUMBER
File Name:PSC-60-SPEC 2018-01-12
EMC IMMUNITY
EMC EMISSION
PSC-60A -C =Blank,-C ; Blank=PCB only, -C=Enclosed type=Blank,-C ; Blank=PCB only, -C=Enclosed type
Bauar
Sicherheit
egel gema
t gepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os