PSC-60A

SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
Note.4
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
BATTERY CUT OFF
AC OK
BATTERY LOW
AC CURRENT (Typ.)
800ms, 50ms/230VAC 1600ms, 50ms/115VAC at full load
50ms/230VAC 10ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
84%
CH1:28.98 ~ 37.26V
84%
21 1V±
Battery low voltage : < 22V
1.6A/115VAC 1A/230VAC
COLD START 30A/115VAC 60A/230VAC
<1mA / 240VAC
105 ~ 150% rated output power
CH1:14.49 ~ 18.63V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
Protection type : Hiccup mode, recovers automatically after fault condition is removed
10.5 0.5V±
UL60950-1, TUV EN60950-1, approvedEAC TP TC 004
Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A, EAC TP TC 020
-20 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH
±℃0.03%/ (0~50 ) on CH1 output
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
589.7K hrs min. MIL-HDBK-217F (25 )
PCB:101.6*50.8*29mm (L*W*H) ; Enclosed type:103.4*62*37mm (L*W*H)
PCB:0.13Kg; 96pcs/13.5Kg/0.89CUFT ; Enclosed type:0.29Kg; 45pcs/14Kg/0.67CUFT
FUNCTION
TTL open collector output, ON : AC OK ; OFF : AC Fail ; Ice : max. 30mA@ 50VDC
TTL open collector output, ON : Battery Low ; OFF : Battery OK ; Ice : max. 30mA@ 50VDC
Battery low voltage : < 11V
PSC-60B
27.6V
CH1
1.4A
0 ~ 2.15A
59.34W
240mVp-p
CH1: 24 ~ 29V
±1.0%
±0.5%
±0.5%
27.6V
CH2
0.75A
--------
--------
--------
--------
--------
13.8V
CH2
1.5A
--------
--------
--------
--------
--------
PSC-60A
13.8V
2.8A
0 ~ 4.3A
59.34W
120mVp-p
CH1: 12 ~ 15V
±1.0%
±0.5%
±0.5%
60W Single Output with Battery Charger(UPS Function)
Universal AC input / Full range
Models with L-Bracket and cover available (PSC-60x-C, x=A,B)
Protections: Short circuit / Overload / Over voltage
Battery low / protection Battery reverse polarity protection by fuse
Alarm signal for AC OK and Battery reverse low
Cooling by free air convection
100% full load burn-in test
2 years warranty
Features :
PSC-60 series
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
ENVIRONMENT
PROTECTION
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
SAFETY &
EMC
(Note 7)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
5. Heat sink HS1,HS2 can not be shorted.
6. Heat sink HS1 must have safety isolation distance with system case.
7. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.360 360 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
8. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
CH1
OUTPUT NUMBER
File Name:PSC-60-SPEC 2018-01-12
EMC IMMUNITY
EMC EMISSION
PSC-60A -C =Blank,-C ; Blank=PCB only, -C=Enclosed type=Blank,-C ; Blank=PCB only, -C=Enclosed type
Bauar
Sicherheit
egel gema
t gepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os
Mechanical Specification
Unit:mm
Mechanical Specification
Unit:mm
Block Diagram
CIRCUIT
CIRCUIT
DETECTION
ALARM
O.L.P.
EMI
FILTER
RECTIFIERS
&
FILTER
POWER
SWITCHING
FILTER
&
RECTIFIERS
+V
Bat. +
Battery Charger
&
Back Up Control
AC OK
Bat. Low
-V
Bat. -
I/P
FG
CONTROL
O.V.P.
AC Input Connector (CN1) : JST B3P-VH or equivalent
Pin No.
1
2
3
Assignment
AC/N
No Pin
AC/L
Mating Housing
JST VHR JST SVH-21T-P1.1
or equivalent or equivalent
Terminal
DC Output Connector (CN2) : JST B6P-VH or equivalent
Pin No. Pin No.
1
5
4
2
36
Assignment Assignment
DC Output +
Battery +
DC Output COM
AC OK
Bat. Low
Battery -
Mating Housing
JST VHR
or equivalent
Terminal
JST SVH-21T-P1.1
or equivalent
1.HS1,HS2 can not be shorted.
2.HS1 must have safety isolation distance with system case.
3.M1 is safety ground. For better EMC performance,Please
secure an electrical connection between M1,M2 and
chassis grounding.
CN1
2
3
1
AC FUSE
FS1
T2.5A/250V
1
4
5
6
SVR1
CN2
101.6
95.25
3.175
HS2
2
3
HS1
4- 3.3ψ
50.8
44.45
3.175
29
3 max.
60W Single Output with Battery Charger(UPS Function)
PSC-60 series
L-Bracket:
No.998A -D
Mylar film
Cover:
No.998A -T
18
14.5
4.2
95
78
2-M3
12.7
2-M3 L=4
2-M3 L=4
55
103.4
24.2
30.85
62
2- 3.5ψ
37
: Grounding Required
M1
M2
File Name:PSC-60-SPEC 2018-01-12
Suggested Application
Pin6 DC output com
External voltage and R
(The max. Sink is 30mA and 50V)
R
V
Output Derating VS Input Voltage
INPUT VOLTAGE (VAC) 60Hz
90 10095 120115 160140 200180 240220 264
LOAD (%)
90
100
80
70
60
50
40
Output Derating
AMBIENT TEMPERATURE ( )
LOAD (%)
-20 0 2010 30 35 40
20
40
80
60
100
6050 70
(HORIZONTAL)
Enclosed tpye
PCB only
DC-
DC+
Bat+
Bat-
Load
A : 12V
B : 24V
Battery
+
+
-
-
60W Single Output with Battery Charger(UPS Function)
PSC-60 series
1.Backup connection for AC interruption
2.Alarm Signal for AC OK and Battery Low
(1) Please refer to the Fig1.1 for suggested connection.
(1) Alarm Signal is sent out through " AC OK " & " Battery Low " pins.
(2) An external voltage source is required for this function. The maximum applied voltage is 50V and the maximum sink current is 30mA.
(3) Table2.1 explains the alarm function built in the power supply
AC OK (Battery low)
Function
Output of alarm
(0.3V max. at 30mA)
(0.3V max. at 30mA)
voltage 50V max.)
voltage 50V max.)
Low
Low
High or open(External applied
High or open(External applied
Description
The signal is "Low" when the power supply
The signal is "Low" when the voltage of
The signal is "High" when the voltage of
The signal turns to be "High" when the power
turns on
battery is under A:11V, B:22V
battery is above A:11V, B:22V
supply turns OFF
AC OK
Battery
Low
The power supply charges the battery and provides energy to the load at the same time when the AC main is OK.
The battery starts to supply power to the load when the AC mains fails.
Fig 1.1 Suggested system connection
Table 2.1 Explanation of Alarm Signal
Fig 2.2 Internal circuit of AC OK (Battery Low)
File Name:PSC-60-SPEC 2018-01-12

PSC-60A

Mfr. #:
Manufacturer:
Description:
Switching Power Supplies 13.8@2.8, 13.8V@1.5A 59.3W W/Batt Charge
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet