https://www.phoenixcontact.com/pi/products/2814537
08/19/2018Page2/4
Signal conditioner-MCR-C-U-I- 4-DC-2814537
Technical data
Input data
Configurable/programmable no
Voltage input signal 0 V ... 10 V
max. input voltage 30 V
Input resistance of voltage input 100 kΩ
Output data
Output name Current output
Number of outputs 1
Configurable/programmable no
Current output signal 4 mA ... 20 mA
Max. output current 30 mA
Load/output load current output ≤ 500 Ω
Linear transmission range (in reference to the output range end value) -5 % ... 105 %
Power supply
Supply voltage range 20 V DC ... 30 V DC
Typical current consumption < 15 mA (without load)
Connection data
Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Stripping length 8 mm
Screw thread M3
General
No. of channels 1
Maximum transmission error ≤ 0.3 % (of final value)
Transmission error, typical < 0.2 % (of final value)
Maximum temperature coefficient < 0.015 %/K
Limit frequency (3 dB) 30 Hz
Step response (10-90%) 11 ms
Protective circuit Transient protection
Test voltage, input/output/supply 1.5 kV (50 Hz, 1 min.)
Color green
Housing material Polyamide PA non-reinforced
Mounting position any
Conformance CE-compliant