RSC-AAM60

Specifications are subject to change without notice (26.03.2010) 1
Solid State Relay
Soft starting/stopping
Control module
Output module
Control input type
Multivoltage
Rated operational voltage
Rated operational current
Control and output modules for analogue
control of 3-phase induction motors or heaters
Rated operational current: 3 x 10, 25, 50, 90, 110 AACrms
Rated operational voltage: Up to 600 VACrms
Supply voltage range: 10 to 32 VDC
Control current range: 0 to 20 mA/4 to 20 mA
LED-indication for line ON and load ON
Varistor protection
Approvals: CE, CCC, UL, CSA
Product Description Ordering Key
Type Selection, Output Module
Type Selection, Control Module
Control current Mains Max. operational voltage Type Number
0-20 mA/4-20 mA Multivoltage 600 VAC RSC-AA M 60
Motor Controllers
3-Phase Analog Power Controller
Types RSC-AAM60/RSO .....
The micro processor based
control module RSC-AAM60
is used with output modules
RSO... to achieve a voltage
controlled soft start/soft stop
of 3-phase motors and a pos-
sibility for energy reduction
when e.g. a fan is running with
a variable capacity. This func-
tion is achieved by controlling
the control module with a cur-
rent between 4 and 20 mA (0
and 20 mA). The output mod-
ule can be selected according
to the rated operational volt-
age and the size of the load.
This phase angle controlled
soft-start unit can be used for
pumps, fans, heaters, lights
and many other applications.
LED indications for line ON
and load ON gives a clear sta-
tus indication.
Rated operational voltage Rated operational current
10 A 25 A 50 A 90 A 110 A
3 x 220 VAC RSO 2210 RSO 2225 RSO 2250 RSO 2290 RSO 22110
3 x 400 VAC RSO 4010 RSO 4025 RSO 4050 RSO 4090 RSO 40110
3 x 480 VAC RSO 4810 RSO 4825 RSO 4850 RSO 4890 RSO 48110
3 x 600 VAC RSO 6050 RSO 6090 RSO 60110
RSC-AA M 60
RSO 4050
General Spec., Control Module Control Specifications
Minimum output voltage Power supply minus 8 VDC
Output current
short-circuit protected 150 mA DC
Operating temperature -20° to +70°C (-4° to +15F)
Storage temperature
-40° to +10C (-40° to +212°F)
Thermal Specifications
Operational voltage range
Line to line 150 to 660 VACrms
Operational frequency range 45 to 65 Hz
Supply current
@ no output current < 30 mA
@ max. output current < 180 mA
Supply voltage range 10 to 32 VDC
CE-marking Yes
Approvals UL, CSA, CCC
2 Specifications are subject to change without notice (26.03.2010)
RSC -AAM60/RSO.....
Control current
A-input 0 to 20 mA
B-input 4 to 20 mA
I
nput impedance 250
Power supply reset time 300 ms
Response time
(input to trigger outputs) 1 cycle
Control Input Specifications
Rated isolation voltage
Input to trigger outputs 4000 VACrms
Isolation Control Module
Mode of Operation
The control module RSC-
AAM60 is used with the out-
put module RSO..... to
achieve analog control of 3-
phase induction motors.
Soft starting is achieved by
increasing the motor voltage
in accordance with the input
current. Soft stopping is
achieved by decreasing the
motor voltage in accordance
with the input current.
When the motor is running
idle, the motor voltage can
be reduced by lowering the
input current, whereby ener-
gy is saved.
Heating elements can also
be controlled with the
RSC/RSO with the use of
appropriate filters.
General Specifications, Output Module
Output Specifications, Output Module
RSO 22... RSO 40... RSO 48... RSO 60...
Operational voltage range
Line to line 150 to 250 VACrms 220 to 420 VACrms 400 to 510 VACrms
400 to 625
VACrms
Blocking voltage 1200 V
p
1200 V
p
1200 V
p
1600 V
p
Varistor voltage 275 VAC 420 VAC 510 VAC 625 VAC
CE-marking Yes Yes Yes Yes
RSO ..10 RSO ..25 RSO ..50 RSO ..90 RSO ..110
IEC and CCC
Rated Operational Current
AC 51 16 Arms 25 Arms 50 Arms 90 Arms 110 Arms
IEC and CCC rated
operational current
AC 53a 3 Arms 5 Arms 15 Arms 30 Arms 40 Arms
Number of starts/hr @40˚C 7* 7* 7* 50* 50*
Overload cycle according to
EN/ IEC 60947-4-2 @ 40˚C 3A: AC53a: 3A: AC53a: 3A: AC53a: 3A: AC53a: 3A: AC53a:
4 - 4:100 - 7* 4 - 4:100 - 7* 4 - 4: 100 - 7* 4 - 4:100 - 50* 4 - 4: 100 - 50*
Off-state leakage current 10 mArms 10 mArms 10 mArms 25 mArms 25 mArms
On-state voltage drop 1.6 Vrms 1.6 Vrms 1.6 Vrms 1.8 Vrms 1.8 Vrms
I
2
t for fusing t=10 ms 130 A
2
s 525 A
2
s 1800 A
2
s 6600 A
2
s 18000 A
2
s
Non-rep. surge current
t=10 ms 160 A
p
325 A
p
600 A
p
1150 A
p
1900 A
p
* Mounted on RHS 301
Operation Diagram
Output as a function of control current @cos(ø) = 0.9
100
80
60
40
20
0
[%]
[mA]
0 5 10 15 20
4 8 12 16 20
Urms/Un
P/Pn
Specifications are subject to change without notice (26.03.2010) 3
RSC -AAM60/RSO.....
RSO ..10 RSO ..25 RSO ..50 RSO ..90 RSO ..110
Operating temperature -20° to +70°C -20° to +70°C -20° to +70°C -20° to +70°C -20° to +70°C
(
-4° to +158°F) (-4° to +158°F) (-4° to +158°F) (-4° to +158°F) (-4° to +158°F)
Storage temperature -40° to +100°C -40° to +100°C -40° to +100°C -40° to +100°C -40° to +100°C
(-40° to +212°F) (-40° to +212°F) (-40° to +212°F) (-40° to +212°F) (-40° to +212°F)
Junction temperature 125°C 125°C 125°C 125°C 125 °C
R
th
junction to case 0.7 K/W 0.5 K/W 0.25 K/W 0.1 K/W 0.09 K/W
Thermal Specifications Output Module
Wiring Diagram
Mounting and connection of control module
Functional Diagram
2
4
6
1
3
5
A
B
M
Mains input
L
oad output
C
ontrol input
and output
0
to
20 mA
4
to
20 mA
S
upply
L
oad ON
Supply/
Control input
Dimensions
RSO .....
RSC-AAM60
2
39
***
***
***
**
**
**
**
**
** = ± 0.4 mm
*** = ± 0.5 mm
Heat
sink
compound
All dimensions in mm
All dimensions in mm
Temperature limit switch
***
***
Heatsinks
Fuses
Temperature limit switch
Power supply
For further information refer
to “General Accessories”.
Accessories

RSC-AAM60

Mfr. #:
Manufacturer:
Description:
MTR SFT STRT CNT MOD MULTI
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet