activity. To reduce power consumption, common-mode
stabilization is disabled. SPLIT becomes high imped-
ance, and CANH and CANL are biased to ground by
the termination resistors. INH goes high impedance,
disabling one or more external voltage regulators (see
Table 1.)
Flag Signaling
The MAX13041 uses a set of seven internal flags for
system diagnosis and to indicate faults. Five of the
flags are available at different times to the CAN proto-
col controller on ERR. A logic-low on ERR indicates a
set flag or a fault (see Table 3.) Allow ERR to stabilize
for at least 8µs after changing operating modes.
Supply Undervoltage: UV
NOM
UV
NOM
is set when supply voltage on V
CC
drops below
V
CC(SLEEP)
for longer than t
UV(Vcc),
or when voltage on
V
I/O
drops below V
I/O(SLEEP)
for longer than t
UV(VI/O)
.
When UV
NOM
is set, the MAX13041 enters low-power
sleep mode to reduce power consumption. The device
remains in sleep mode for a minimum waiting time
before allowing the UV
NOM
flag to be cleared. This
waiting time is determined by the same timer used for
setting UV
NOM
(t
UV(VCC)
or t
UV(VIO)
.) UV
NOM
is cleared
by a local wake-up request triggered by a level change
on WAKE or by a wake-on-CAN event. UV
NOM
is also
cleared by setting the PWON flag.
V
BAT
Undervoltage: UV
BAT
UV
BAT
is set when the voltage on V
BAT
drops below
V
BAT(STB)
. When UV
BAT
is set, the MAX13041 enters
standby mode to reduce power consumption. UV
BAT
is
cleared when the voltage on V
BAT
is restored and
exceeds V
BAT(STB)
. Upon clearing UV
BAT
, the
MAX13041 returns to the operating mode determined
by EN and STB.
Power-On Flag: PWON
PWON indicates the MAX13041 is in a power-on state.
PWON is set when V
BAT
has dropped below V
BAT(STB)
and has subsequently recovered. This condition occurs
MAX13041
±80V Fault-Protected High-Speed CAN Transceiver
with Low-Power Management and Wake-On CAN
______________________________________________________________________________________ 13
NORMAL MODEPWON/LISTEN-ONLY MODE
STANDBY MODE
GO-TO-SLEEP COMMAND MODE
SLEEP MODE
STB = H AND EN = H
STB = L AND
FLAG SET
FLAGS CLEARED
AND t > t
H(MIN)
NOTES: H AND L ARE
FLAG SET =
FLAGS CLEARED
LOGIC STATE OF EN OR STB
SETTING PWON AND/OR WAKE-UP FLAG.
PWON AND WAKE-UP FLAG BOTH CLEARED.
STB = H AND EN = L
STB = H
AND EN = H
STB = H
AND EN = H
STB = L
AND EN = H
STB = H AND EN = H
AND UV
NOM
CLEARED
STB = H AND EN = L
AND UV
NOM
CLEARED
STB = L AND
(EN = L OR FLAG SET)
STB = L AND EN = H
AND FLAGS CLEARED
STB = L AND EN = H
AND FLAGS CLEARED
STB = L
AND EN = L
STB = H
AND EN = L
STB = L
AND
(EN = L OR
FLAG SET)
STB = H
AND EN = L
Figure 4. State Diagram
MAX13041
when battery voltage is first applied to V
BAT
. When the
PWON flag is set, UV
NOM
is cleared and sleep mode is
disabled. The primary function of the PWON flag is to pre-
vent the MAX13041 from entering sleep mode (and there-
by disabling external voltage regulators) before the
protocol controller establishes control through EN and
STB. The PWON flag is externally indicated as a logic-low
on ERR when the MAX13041 is placed into PWON/listen-
only mode from standby mode, go-to-sleep command
mode, or sleep mode. The PWON flag is cleared when
the MAX13041 enters normal mode.
Wake-Up Flag
The wake-up flag is set when a local or remote wake-up
request is detected. A local wake-up request is gener-
ated when the logic level on WAKE changes and
remains stable for t
WAKE
. A remote wake-on CAN
request is generated upon the detection of two domi-
nant bus cycles, each followed by a recessive bus
cycle (see Figure 5.) Each bus cycle must exceed
t
BUS(DOM)
. The wake-up flag can only be set in stand-
by mode, go-to-sleep command mode, or sleep mode.
Setting the wake-up flag resets UV
NOM
, and wake-up
requests are not detected during the UV
NOM
flag wait-
ing time immediately after UV
NOM
has been set. The
wake-up flag is immediately available as a logic-low on
ERR and RXD, provided that V
I/O
and V
CC
are both
present. The wake-up flag is cleared when the
MAX13041 enters normal mode.
Wake-Up Source Flag
The wake-up source flag is set concurrently with the
wake-up source flag when a local wake-up event is
detected. The wake-up source flag can only be set
after the PWON flag has been cleared. The flag is
cleared when the MAX13041 leaves normal mode and
during initial power-on. The wake-up source flag is
externally indicated on ERR when the MAX13041 is in
±80V Fault-Protected High-Speed CAN Transceiver
with Low-Power Management and Wake-On CAN
14 ______________________________________________________________________________________
CANH
CANL
DOMINANT
RECESSIVE
DOMINANT
RECESSIVE
t
BUSDOM
t
BUSDOM
t
BUSDOM
t
BUSDOM
Figure 5. Wake-On-CAN Timing
INTERNAL FLAG FLAG AVAILABLE ON ERR CONDITIONS TO CLEAR FLAG
UV
NOM
No Set PWON or wake-up flags
UV
BAT
No Recovery of V
BAT
PWON
In PWON/listen-only mode (changing from
standby, go-to-sleep command, or sleep modes)
Entering normal mode
Wake-Up
In standby, go-to-sleep command, and sleep
modes (provided V
I/O
and V
CC
are present)
Entering normal mode or setting PWON or UV
NOM
flag
Wake-Up Source
In normal mode (before the fourth dominant to
recessive edge on TXD, Note 10)
Leaving normal mode or setting PWON flag
Bus Failure
In normal mode (after the fourth dominant to
recessive edge on TXD, Note 10)
Re-entering normal mode
Local Failure
In PWON/listen-only mode (coming from normal
mode)
Entering normal mode or whenever RXD is
dominant while TXD is recessive (and all local
failures are resolved)
Table 2. Flag Signaling on ERR
Note 10: Allow for a dominant time of at least 4µs per dominant-recessive cycle.
normal mode, prior to the fourth dominant-to-recessive
transition on TXD. A low level on ERR indicates a local
wake-up has occurred.
Bus Failure Flag
The bus failure flag is set when the MAX13041 detects
a CAN bus short-circuit to V
BAT
, V
CC,
or GND for four
consecutive dominant-recessive cycles on TXD. The
flag is cleared when the MAX13041 leaves normal
mode. The bus failure flag is externally indicated as a
logic low on ERR in normal mode, after the fourth domi-
nant-to-recessive transition on TXD.
Local Failure Flag
The local failure flag indicates five separate local failure
conditions (see
Fault Protection & Fail-Safes
section).
When one or more local failure conditions have
occurred, the local failure flag is set. The flag is cleared
when the MAX13041 enters normal mode or when RXD
goes logic-low while TXD is logic-high. The local failure
flag is externally indicated as a logic-low on ERR when
the MAX13041 is placed into PWON/listen-only mode
from normal mode.
Wake-On CAN
The MAX13041 provides wake-on-CAN capability from
sleep mode. When the MAX13041 detects two domi-
nant bus states, each followed by a recessive state
(Figure 5), the MAX13041 sets the wake-up flag and
enters an operating mode determined by the state of
EN and STB. Each CAN logic state must be at least 5µs
in duration. This wake-up detection criterion serves to
prevent unintentional wake-up events due to bus faults
such as V
BAT
to CANH or an open circuit on CANL. At
higher data rates (>125kbit/s), wake-up can not be
guaranteed for a single, arbitrary CAN data frame. Two
or more consecutive arbitrary CAN data frames may be
required to ensure a successful wake-on-CAN event.
External-Voltage Regulator Control
MAX13041 controls one or more external voltage regu-
lators through INH, a V
BAT
-referenced, open-drain out-
put. When INH is logic-high, any external voltage
regulators are active and power is supplied to the
node. When INH is high-impedance, the typical pull-
down characteristic of the voltage-regulator inhibit input
pulls INH to a logic-low and disables the external volt-
age regulator(s).
Fault Protection & Fail-Safes
The MAX13041 features ±80V tolerance on CAN bus
lines CANH, CANL, and SPLIT. Up to +76V operation is
possible on V
BAT
, allowing for use in +42V automotive
applications. Additionally, the device detects local and
remote bus failures and features fail-safe modes to
prevent damage to the device or interference with CAN
bus communication.
The MAX13041 detects five different local faults. When
any local fault is detected, the local failure flag is set.
Additionally, for faults other than bus dominant clamp-
ing, the transmitter is disabled to prevent possible dam-
age to the device. The transmitter remains disabled
until the local failure flag is cleared.
TXD Dominant Clamping
An extended logic-low level on TXD due to hardware or
software failure would ordinarily clamp the CAN bus to
a dominant state, blocking communication on the entire
bus. This condition is prevented by the TXD dominant
time-out feature. If TXD is held low for longer than
t
DOM(TXD)
, the local failure flag is set and the transmit-
ter is disabled until the local failure flag is cleared. The
TXD time-out value limits the minimum allowable bit rate
to 40kbps.
RXD Recessive Clamping
If a hardware failure clamps RXD to a logic-high level,
the protocol controller assumes the CAN bus is in a
recessive state at all times. This has the undesirable
effect that the protocol controller assumes the bus is
clear and may initiate messages that would interfere with
ordinary communication. This local failure is detected by
checking the state of RXD when the CAN bus is in a
dominant state. If RXD does not reflect the state of the
CAN bus, the local failure flag is set and the transmitter is
disabled until the local failure flag is cleared.
TXD-to-RXD Short-Circuit Detection
A short-circuit between TXD and RXD forces the bus
into a permanent dominant state upon the first transmis-
sion of a dominant bit because normally the low-side
driver of RXD is stronger than the microcontroller high-
side driver of TXD. The MAX13041 detects this condi-
tion and prevents the resulting bus failure by setting the
local failure flag and disabling the transmitter. The
transmitter remains disabled until the local failure flag is
cleared.
Bus Dominant Clamping
A short-circuit fault from the CAN bus to V
BAT
, V
CC
, or
GND could produce a differential voltage between
CANH and CANL greater than the receiver threshold,
resulting in a dominant bus state. If the bus state is
clamped dominant for longer than t
DOM(BUS)
, the local
failure flag is set. The transmitter is not disabled by this
fault and the local failure flag is cleared as soon as the
bus state becomes recessive.
MAX13041
±80V Fault-Protected High-Speed CAN Transceiver
with Low-Power Management and Wake-On CAN
______________________________________________________________________________________ 15

MAX13041ASD+T

Mfr. #:
Manufacturer:
Maxim Integrated
Description:
CAN Interface IC 80V Fault-Protected High-Speed
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet