2903000

https://www.phoenixcontact.com/us/products/2903000
07/02/2014Page1/5
Power supply unit-UNO-PS/1AC/15DC/30W-2903000
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Primary-switched UNO power supply for DIN rail mounting, input: single-phase, output: 15 V DC/30 W
Product description
UNO POWER power supplies – compact with basic functionality
Thanks to their high power density, compact UNO POWER power supplies offer the ideal solution for loads up to 100 W, particularly in compact control
boxes. The power supply units with 5 V DC, 12 V DC, and 24 V DC output voltage are available in various performance classes and design widths. Their
high degree of efficiency and low idling losses ensure a high level of energy efficiency. 
Product Features
Flexible mounting by simply snapping onto the DIN rail
More space in the control cabinet with up to 20 % higher power density
Maximum energy efficiency, thanks to over 90 % efficiency and extremely low idling losses under 0.3 W
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 180.0 GRM
Custom tariff number 85044030
Country of origin Germany
Technical data
Dimensions
Width 22.5 mm
Height 90 mm
Depth 84 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 55° C derating)
https://www.phoenixcontact.com/us/products/2903000
07/02/2014Page2/5
Power supply unit-UNO-PS/1AC/15DC/30W-2903000
Technical data
Ambient conditions
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Noise immunity EN 61000-6-2:2005
Input data
Input voltage range 85 V AC ... 264 V AC
AC frequency range 45 Hz ... 65 Hz
Current consumption 0.6 A (120 V AC)
0.4 A (230 V AC)
Inrush surge current < 30 A (typical)
Power failure bypass > 20 ms (120 V AC)
> 115 ms (230 V AC)
Input fuse 2 A (slow-blow, internal)
Choice of suitable fuses 6 A ... 16 A (Characteristics B, C, D, K)
Type of protection Transient surge protection
Protective circuit/component Varistor
Output data
Nominal output voltage 15 V DC ±1%
Output current 2 A (-25°C ... 55°C)
Derating 55 °C ... 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series Yes
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple
< 40 mV
PP
(with nominal values)
Maximum power dissipation NO-Load < 0.3 W
Power loss nominal load max. < 4.6 W
General
Net weight 0.15 kg
Efficiency > 87 % (for 230 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
3 kV AC (routine test)
Protection class II (in closed control cabinet)
MTBF (IEC 61709, SN 29500) 911000 h (According to EN 29500)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions Alignable: 0 mm horizontally, 30 mm vertically
https://www.phoenixcontact.com/us/products/2903000
07/02/2014Page3/5
Power supply unit-UNO-PS/1AC/15DC/30W-2903000
Technical data
General
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines EN 60204-1
Standard - Electrical safety IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204 (PELV)
Standard - Safe isolation DIN VDE 0100-410
Standard – Protection against electric shock DIN 57100-410
Standard – Limitation of mains harmonic currents EN 61000-3-2
Approval - requirement of the semiconductor industry with regard to mains
voltage dips
EN61000-4-11
Information technology equipment - safety (CBscheme) CB Scheme
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950
Connection data, input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 14
Stripping length 8 mm
Screw thread M3
Connection data, output
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.2 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 24
Conductor cross section AWG/kcmil max 14
Stripping length 8 mm
Signaling
Output name LED status indicator

2903000

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
DIN Rail Power Supplies UNO-PS/1AC/15DC/30W PRIM SWCH SNGL PHASE
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet