GLM50-24G

GLC50 Commercial/GLM50 Medical
Ac Input
90-264 Vac, 47-63 Hz single phase..
Input Current
Maximum input current at 120 Vac, 60 Hz with full rated output load: 1.5 A
Hold-Up Time
15 ms minimum from loss of ac input at full load, nominal line (115 Vac).
Output Power
50 W continuous, 60 W peak. Peak ratings are for 60 s maximum duration,
10% duty cycle. During peak load condition, output regulation may exceed
total regulation limits.
Output Regulation
To maintain specied regulation on multi-output models, output #1 load
power must be at least 1/5th of, and not greater than 5 times output #2 load
power.
Overload Protection
Fully protected against short circuit and output overload. Short circuit pro-
tection is cycling type power limit on outputs 1 & 2; foldback type on output
3. Recovery after fault is automatic. See output ratings chart for additional
notes or conditions.
Eciency
70-85% at full rated load, nominal input voltage, depending on model and
load distribution.
Minimum Load
Operating without minimum load will not degrade reliability, but regula-
tion may be aected. Multiple output models require 20% minimum load
on V1 for proper regulation. Single models require 5% minimum load when
a transient load greater than 30% is applied or removed, but will operate
without load.
Input Protection
Internal ac fuse provided. Designed to blow only if a catastrophic failure oc-
curs in the unit—fuse does not blow on overload or short circuit.
Inrush is limited by internal thermistors. Inrush at 240 Vac,
averaged over the rst ac half-cycle under cold start
conditions will not exceed 37 A.
50 WATT GLOBAL PERFORMANCE SWITCHERS
GLOBAL PERFORMANCE SWITCHERS
All specications are typical at nominal input, full load at 25
O
C unless otherwise stated
Features:
D C P o w e r S u p p l i e s
SPECIFICATIONS
Temperature Coecient
0.03%/°C typical on all outputs.
Output Noise
0.5% rms, 1% pk-pk, 20 MHz bandwidth, dierential mode. Measured with noise
probe directly across output terminals of the power supply.
Transient Response
500 μs typical response time for return to within 0.5% of nal value for a 50% load
step change. ∆i/∆t<0.2 A/μs. Maximum voltage deviation is 3.5%. Startup/shut-
down overshoot less than 3%.
Voltage Adjustment
Built-in potentiometer adjusts V1 ±5%.
EMI/EMC Compliance
All models include built-in EMI ltering to meet the following emissions require-
ments:
EMI SPECIFICATIONS COMPLIANCE LEVEL
Conducted Emissions GLC
Conducted Emissions GLM
Static Discharge
RF Field Susceptibility
Fast Transients/Bursts
Surge Susceptibility
EN55022 Class B; FCC Class B
EN55011 Class B; FCC Class B
EN61000-4-2, 6 kV contact, 8 kV air
EN61000-4-3, 3 V/meter
EN61000-4-4, 2 kV, 5 kHz
EN61000-4-5, 1 kV di., 2 kV com.
• Cost-eective power source
• Universal input 90-264 Vac
• 2-year warranty
• Compact (4.25” x 2.50” x 1.25”; meets
1U applications)
• Overload and overvoltage protection
• Conducted EMI exceeds FCC Class B and
CISPR 22 Class B (Commercial models) and
CISPR 11 Class B (Medical models)
• Commercial UL/CSA/IEC60950-1, EN60950 approvals
• Medical UL/EN/IEC60601-1, CSA22.2 No. 601,
• RoHS compliant models available (G sux)
• marked to LVD
Commercial Leakage Current
160 μA 254 Vac @ 60 Hz input (with no deviations).
Commercial Safety
All GLC models are approved to UL1950, CSA22.2 No.
234 Level 3, IEC950 and EN60950.
Medical Leakage Current
100 μA 264 Vac @ 60 Hz input (normal conditions).
Medical Safety
All GLM50 models are approved to UL/EN/IEC60601-1, CSA22.2 No. 601.
Notes:
A. Total regulation is dened as the maximum deviation from the nominal voltage for all steady-state conditions of initial voltage setting, input line voltage and output load.
B. To maintain specied regulation on multi-output models, output #1 load power must be at least 1/5th of, and not greater than 5 times output #2 load power.
C. Add “G” sux to model number for RoHS compliant model.
Commercial
Model
Medical
Model Output No. Output Current
Minimum
Load (B) OVP Setpoint Noise P-P
Total
Regulation (A)
GLC50A GLM50A 1 +5.05 V 4 A 0.8 A 6.2 ± 0.6 V 50 mV 2%
2 +12 V 2.5 A 120 mV +10%,-5%
3 -12 V 0.2 A 120 mV 3%
GLC50B GLM50B 1 +5.05 V 4 A 0.8 A 6.2 ± 0.6 V 50 mV 2%
2 +15 V 2.5 A 150 mV +10%,-5%
3 -15 V 0.2 A 150 mV 3%
GLC50D GLM50 D 1 +5.05 V 4 A 0.8 A 6.2 ± 0.6 V 50 mV 2%
2 +24 V 1.5 A 240 mV +10%,-5%
3 -12 V 0.2 A 120 mV 3%
GLC50G GLM50G 1 +3.3 V 4 A 0.8 A 4.2 ± 0.6 V 33 mV 2%
2 +12 V 2.5 A 120 mV +10%-5%
3 -12 V 0.2 A 120 mV 3%
GLC50-3.3 GLM50-3.3 1 3.3 V 8 A 0.2 4.2 ± 0.6 V 66 mV 2%
GLC50-5 GLM50-5 1 5.1 V 8 A 0.4 6.2 ± 0.6 V 75 mV 2%
GLC50-12 GLM50-12 1 12 V 4.2 A 0.2 14 ± 1.1 V 120 mV 2%
GLC50-15 GLM50-15 1 15 V 3.3 A 0.16 18.5 ± 1.5 V 150 mV 2%
GLC50-24 GLM50-24 1 24 V 2.1 A 0.1 28 ± 2.5 V 240 mV 2%
GLC50-28 GLM50-28 1 28 V 1.8 A 0.09 34.5 ± 2.8 V 280 mV 2%
GLC50-48 GLM50-48 1 48 V 1.1 A 0.05 54 ± 3.0 V 480 mV 2%
SL Power Electronics Corp, 6050 King Drive, Bldg. A, Ventura, CA 93003, USA. Phone:(805) 486 4565 Fax:(805) 487 8911 www.slpower.com. Rev. 1/07.
Data Sheet © 2007 SL Power Electronics Corp. The information and specications contained in this data sheet are believed to be correct at time of publication.
However, Condor accepts no responsibility for consequences arising from reproduction errors or inaccuracies. Specications are subject to change without notice.
GLC50 MECHANICAL SPECIFICATIONS
ENVIRONMENTAL SPECIFICATIONS OPERATING NON-OPERATING
Temperature (A) 0 TO 50°C -40 to +85°C
Humidity (A) 0 to 95% RH 0 to 95% RH
Shock (B) 20 g
pk
40 g
pk
Altitude -500 to 10,000 ft -500 to 40,000 ft
Vibration (C) 1.5 g
rms’
0.003 g
2
/Hz
5 g
rms’
0.026 g
2
/Hz
A. Units should be allowed to warm up/operate under non-condensing condi-
tions before application of power. derate output current and total output
power by 2.5% per °C above 50°C.
B. Shock testing—half-sinusoidal, 10 ± 3 ms duration, ± direction, 3 orthogonal
axes, total 6 shocks.
C. Random vibration—10 to 2000Hz, 6dB/octave roll-o from 350 to 2000Hz, 3
orthogonal axes. Tested for 10 min./axis operating and 1 hr./axis non-operating.