89422118

CTH 46
-
CTD 43 / 46 CTD 46 Part number 89422118
CTH 46
Heating / cooling function
Measurement and setpoint display
CTD 43
Heating or cooling function
Measurement display
Measurement deviation display-Setpoint via LED
1 configurable alarm
CTD 46
Heating or cooling function
Measurement and setpoint display
1 configurable alarm
Part numbers
Specifications
Type
Output
Supply voltage
89 422 118
CTD 46
Logic
100→240VAC
Supply
100 to 240 VAC, 24 VACDC
Frequency (Hz)
50 / 60
Tolerance
-15 %
+10 % Un
Consumption
8 VA max.
Display measurement
red LEDs
-
4 digits, 7 segment, height 10 mm
Display setpoint
green LEDs
-
4 digits, 7 segment, height 7,5 mm
Control algorithm
PID with auto
-
tune and adaptive tune : SMART
Control type
heat or cool
heat / cool
Sampling time linear input
250 ms
Sampling time TC and RTD input
500 ms
Proportional band Pb heat or cool
1,0 to 100 % of scale amplitude
Proportional band Pb heat
- cool
1,5 to 100 % of scale amplitude
Proportional band Pb
Note : if Pb = 0 % discrete action
Hysteresis (during discrete action)
0,1 to 10 % of scale amplitude
Integral time ti
Note : if ti > 20 min
20 s to 20 min
integral action is inactive
Derivative time
td.
Note : if td=0
1 s to 10 min
derivative action is inactive
Cycle time heating
1s→200s
Cycle time cooling
1s→200s
Heat
-cool control
Cool proportional band
rC x heat proportional band
Heat
-cool control
rC : relative gain
0,20→1,00
Heat
-cool control
dead.overlap band
-20 % to + 50 % of the heat proportional band
Thermocouples J, K, R, S, and N
IEC 584
-1
Thermocouples L
DIN 43710
Reference junction
Automatic cold junction compensation : 0 to 50
o
C
(Thermocouples)
Reference junction drift
0,1 °C / °C
Input impedance (k
Ω
)
>
1 M
Ω
Calibration (IEC 584
-1)
Resist. temp. detector 3-
wire Pt 100 conforming to DIN
43760
Line resistance
20
Ω
max. (Resistance temperature detector)
Input type and standard range TC
L (0/400 °C)
(0/1650°F)
(0/900 °C)
J (0/400 °C)
(0/1830°F)
(0/1000 °C)
K (0/400 °C)
(0/2190°F)
(0/1200 °C)
N (0/1400 °C)
(0/2550°F)
R (0/1760 °C)
(0/3200°F)
S (0/1760 °C)
(0/3200°F)
Input types and standard rangeRTD Pt100
(-
199,9/400,0 °C)
(-
199,9/400,0°F)
(-
200/800 °C)
(-
330/1470°F)
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
02/11/2015 www.crouzet.com
Measurement range
-
1999→+4000
Decimal point
adjustable :
- - - -, - - -. -, - -. - -, -. - - -
Inputs
50 mAAC
Measurement range with transformer
10A→100A
Resolution
10 to 20 A : 0.1 A
21 to 100 A : 1 A
Measurement logic threshold
Relay output : NO or NC
Logic output : level 1 or 0
Measurement update period
50 ms
Setpoints
-
main setpoint : SP
-
auxiliary setpoint : SP2
Selection input
SP/SP2
50 mA AC
selection via external N/C type contact
Type of output
discontinuous
Action type
can be programmed for heating and/or cooling
Limitation of output power : SOFT
-
START
- heat action
adjustable from 0 to 100 %
Limitation of output power : SOFT
-
START
-heat/cool
action
adjustable from -100 to +100 %
OUT 1 Main output N/O contact
3A 250 V AC resistive (N/C contact is possible via a jumper)
OUT 1 Main output logic
Level 0 : <0,5 V DC
Level 1 :
14 V DC
±
20 % @ 20 mA max
24 V DC
±
20 % @ 1 mA max
Main output cycle time
1s→99s
OUT 2 Cool output or alarm 1 output
N/O
-2A contact, 250 V AC resistive
OUT 3 Load break output and/or alarm 2 output
N/O
-2A contact, 250 V AC resistive
Type of output
direct or reverse
Functions
absolute alarm
band alarm
deviation alarm
Reset to zero
Manual / automatic
Inhibition
Configuration
Alarm threshold -
absolute alarm
absolute value independent from SP
Alarm threshold -
band alarm
value relative to SP, adjustable from 0 to 500 °C/°F
Alarm threshold -
deviation alarm
value relative to SP, adjustable from
-
500 °C/°F (negative deviation) to + 500 °C/°F (positive deviation)
Alarm
0.1 to 10 % of scale amplitude
Type
RS485
Protocol
MODBUS, J.BUS
Address
1→255
Number of data bits
8
Transmission speed
600→19200Bauds
Parity
even, odd, no
Stop bit
1
Insulation resistance conforming to IEC 348
> 100 M
Ω
Insulation voltage according to IEC 348
1500 V
Immunity to interference conforming to IEC 801
-4
Level 3
Immunity to interference conforming to IEC 801
-2
8000 V
Accuracy
±
0.2 % of the full measurement scale
±
1 digit at an ambient temperature of 25
o
C at Un
Operating temperature range (°C)
0→+50
Storage temperature range (°C)
-
20→+70°C
Relative humidity (no condensation)
20→85%Rh
Housing material
self-extinguishing UL94 grade VO
Front panel
Polycarbonate membrane
Protection class according to IEC 529 (IEC 70
-1)
IP 54
Connection
screw terminals
Weight (g)
250
UL / CSA
in progress
Safe-guard
detects a fault in the equipment caused by external interference and activates automatic reset without modification of the process.
Switch
the configuration and calibration are accessed via an internal switch, can only be accessed when the device is unplugged.
Supply
100 to 240 VAC
Frequency (Hz)
50 / 60
Tolerance
-15 %
+10 % Un
Consumption
5 VA
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
02/11/2015 www.crouzet.com
Display CTD 43
Measurement or setpoint : red LEDs, 3
-
digit, 7
-
segment, height 10 mm
Display CTH 47 / CTD 46
Measurement : red LEDs, 3
-
digit, 7
-
segment, height 10 mm
Setpoint : green LEDs, 3
-
digit, 7
-
segment, height 7,5 mm
Switch
the configuration and calibration are accessed via an internal switch, which can only be accessed when the equipment is
disconnected
Insulation resistance conforming to IEC 348
> 100 M
Ω
Insulation voltage according to IEC 348
1500 V
Immunity to interference conforming to IEC 801
-4
Level 3
Immunity to interference conforming to IEC 801
-2
8000 V
Accuracy
±
0.3 % of the full measurement scale at an ambient temperature of 25
o
C at Un
Operating temperature range (°C)
0→+50°C
Storage temperature range (°C)
-
30→+70°C
Relative humidity (Rh no condensation)
20→85%
Housing material
self-extinguishing UL94 VO grade
Front panel
polycarbonate membrane
Protection class according to IEC 529 (IEC 70
-1)
IP 54
Connection
screw terminals
Weight (g)
160
Approvals
UL/CSA
Thermocouples J, K, and N
IEC 584
-1
Thermocouples L
DIN 43710
Reference junction
Automatic cold junction compesation : 0 to 50
o
C (Thermocouples)
Reference junction drift
0,1 °C / °C
Line resistance
100
Ω
max
Calibration (IEC 584
-1)
IEC 584
- 1
Resist. temp. detector Pt 100 according to IEC 751
3-wire
Line resistance
< 4
Ω
Input type and standard range TC
L (0/800 °C)
(0/999°F)
J (0/800 °C)
(0/999°F)
K (0/999 °C)
(0/999°F)
N (0/999 °C)
(0/999°F)
Input types and standard rangeRTD Pt100
(-
199/500 °C)
(-
19,9/99,9°F)
(-
199/999 °C)
Type of output
discontinuous
Action type CTH 46
heating
-
cooling
Action type CTD 43
-
CTD 46
heating or cooling
Limitation of output power : SOFT
-
START
- heat action
adjustable from 0 to 100 %
Limitation of output power : SOFT
-
START
-heat/cool
action
adjustable from -100 to + 100 %
Main output changeover relay
3 A 250 V AC resistive
Main output
--
logic
Max. load : 700
Ω
Level 0 : < 0,5 V DC
Level 1 :
14 V DC
±
20 % @ 20 mA max
24 V DC
±
20 % @ 1 mA max
Main output cycle time
1s→200s
Cool output CTH 46 only
N/O
-1 A contact, 250 V AC resistive
Alarm output CTD 43
-
CTD 46 only
N/O
-1 A contact, 250 V AC resistive
Control algorithm
PID with auto
-
tune and adaptive tune : SMART
Control type CTD 43 CTD 46
heating or cooling
Control type CTH 46
heating
-
cooling
Sampling time
500 ms
Proportional band Pb CTD 43
-
CTD 46
1,0 % to 99,9 % of scale amplitude
Proportional band Pb CTH 46
1,5 % to 99,9 % of scale amplitude
Proportional band Pb
Note : if Pb = 0 % discrete action
Hysteresis (during discrete action)
0,1 % to 10 % of scale amplitude
Integral time ti
Note : if ti > 20 min
1 min 20 s to 20 min 0 s (10 s resolution)
Derivative time
td.
Note : if td=0
1 s to 9 min 59 s
Cycle time heating
1s→200s
Cycle time cooling (CTH46 only)
1s→200s
Heat
-
cool control CTH 46
Cool proportional band
rC x heat proportional band
Heat
-cool control
rC : relative gain
0,20→1,00
Heat
-
cool control CTH 46
dead.overlap band
-20 % to + 50 % of the heat proportional band
Type of output
direct or reverse
Functions
absolute alarm
. band alarm
. deviation alarm
Reset to zero
manual
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
02/11/2015 www.crouzet.com

89422118

Mfr. #:
Manufacturer:
Crouzet
Description:
Controllers 110-220VAC, LOGIC TEMP CTRL
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet