2906318

https://www.phoenixcontact.com/us/products/2906318
09/07/2016Page1/5
Type 2 surge protection device-VAL-MS+TE-AR 75 VF/P-FM-2906318
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Why buy this product
With floating remote indication contact
Separate field and house wire termination.
Tool-free field wire disconnect and test point.
Isolated field and house wire (4-post equivalent)
IP20 touch safe when connected.
Zero leakage current
Key Commercial Data
Packing unit 1 STK
Weight per Piece (excluding packing) 300.000 g
Custom tariff number 85363030
Country of origin Germany
Technical data
Dimensions
Height 113 mm
Width 17.7 mm
Depth 78 mm
Ambient conditions
Degree of protection IP20
IP20 (when disconnect closed)
Ambient temperature (operation) -40 °C ... 80 °C
https://www.phoenixcontact.com/us/products/2906318
09/07/2016Page2/5
Type 2 surge protection device-VAL-MS+TE-AR 75 VF/P-FM-2906318
Technical data
Ambient conditions
Altitude max. 3000 m
Permissible humidity (operation) 5 % ... 95 %
Permissible humidity (storage/transport) 5 % ... 95 %
Shock (operation) 10g
Vibration (operation) 2g (0... 200Hz)
General
Housing material PA
Flammability rating according to UL 94 V0
Color black
Total surge current (8/20) µs 25 kA
Total surge current (10/350) µs 3 kA
Mounting type DIN rail mounting with additional retaining screw
Type DIN rail module, two-section, divisible
Surge protection fault message Optical, remote indicator contact
Optical, remote indicator contact
Direction of action 1L-N/PE
Protective circuit
IEC test classification II
T2
EN type T2
T2
Maximum continuous operating voltage U
C
100 V DC
75 V AC
Nominal frequency f
N
50 Hz (60 Hz)
Rated load current I
L
55 A (with 6 AWG)
Max. discharge current I
max
(8/20) µs
20 kA
Nominal discharge current I
n
(8/20) µs
10 kA
Voltage protection level U
p
≤ 1.4 kV
Residual voltage ≤ 350 V (at 5 kA)
≤ 300 V (at 3 kA)
≤ 450 V
Max. backup fuse with branch wiring 63 A (gG)
63 A (gG)
Short-circuit resistance I
P
with max. backup fuse (effective)
10 kA
10 kA
Connection, protective circuit
https://www.phoenixcontact.com/us/products/2906318
09/07/2016Page3/5
Type 2 surge protection device-VAL-MS+TE-AR 75 VF/P-FM-2906318
Technical data
Connection, protective circuit
Conductor cross section AWG 15 ... 2 (UL)
20 ... 6
12 ... 4
Remote indication contact
Connection name Remote fault indicator contact
Switching function PDT, 1-pos.
Connection method Screw connection
Screw thread M2
Tightening torque 0.25 Nm
2 lb
f
-in. ... 4 lb
f
-in. (UL)
Stripping length 7 mm
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section AWG min. 28
Conductor cross section AWG max. 16
Maximum operating voltage U
max.
AC
250 V AC
Max. operating current I
max
1.5 A AC (250 V AC)
1.5 A DC (30 V DC)
Drawings
Dimensional drawing
77,8
112,3
53
35,3
Classifications
eCl@ss
eCl@ss 5.1 27130801
eCl@ss 6.0 27130802
eCl@ss 8.0 27130805

2906318

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
VAL-MS+TE-AR 75 VF/P-FM
Lifecycle:
New from this manufacturer.