4411.0087

4
Thermal (T- and TA-Line)
T13-211
https://www.schurter.com /PG17_20
Circuit Breakers
Typical internal resistance
Rated Current [A] Internal Resistance []
0.05 376.500
0.50 4.40
1.00 1.10
2.00 0.31
3.00 0.14
4.00 0.068
5.00 0.048
6.00 0.033
8.00 0.026
9.00 0.0125
10.00 0.0125
11.00 0.0085
12.00 0.0085
13.00 0.0085
14.00 0.007
15.00 0.007
16.00 0.007
17.00 0.0047
18.00 0.0047
19.00 0.0047
20.00 0.004
21.00 0.0035
22.00 0.003
23.00 0.003
24.00 0.003
25.00 0.003
26.00 0.0022
27.00 0.002
28.00 0.002
29.00 0.002
30.00 0.002
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated cur-
rent for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient Temperature [°C] Correction factor
-5 0.88
0 0.90
10 0.95
23 1.00
30 1.05
40 1.10
50 1.18
60 1.26
Example: Rated current = 5 A, Environmental temperature = 40 °C, --> Correction factor =
1.1, Resulting current = 5.5 A --> Fount to next higher rated current: 6 A
5
Thermal (T- and TA-Line)
T13-211
https://www.schurter.com /PG17_20
Circuit Breakers
Time-Current-Curves
Time in Seconds
< 7,0 A
>
7,0 A
10'000
60
2`000
1`000
500
200
100
50
20
10
5
2
1
0,5
0, 3
0, 2
0,1
[ sec ][ min ]
10
5
1
30
20
1,05 10854321,32
Multiple of Rated Current In
Reference Temperature +23°
Config. Code
T13|-|1|2|3|B|-|1.23|
The characters are placeholders for the correspondingly keys of selections from the key tables.
T13|-| 1 |2|3|B|-|1.23| = Mounting
Mounting Configuration
key
Threaded neck type with knurled nut 2
T13
|-|1| 2 |3|B|-|1.23| = Actuation Type
Actuation Type Configuration
key
Reset type 1
T13
|-|1|2| 3 |B|-|1.23| = Terminal
Terminal Configuration
key
Quick connect terminal 6.3x0.8mm 1
T13
|-|1|2|3| B |-|1.23| = Setting indication
Setting indication Configuration
key
Setting indication R
T13
|-|1|2|3|B|-| 1.23 | = Rated current
Rated current Configuration
key
0.05 A 0.05
0.1 A 0.1
0.15 A 0.15
0.2 A 0.2
0.3 A 0.3
0.4 A 0.4
0.5 A 0.5
0.6 A 0.6
0.7 A 0.7
0.8 A 0.8
0.9 A 0.9
1.0 1
1.1 A 1.1
1.2 A 1.2
1.3 A 1.3
1.4 A 1.4
1.5 A 1.5
1.6 A 1.6
1.7 A 1.7
1.8 A 1.8
1.9 A 1.9
2.0 A 2
2.1 A 2.1
2.3 A 2.3
Other rated currents on request
6
Thermal (T- and TA-Line)
T13-211
https://www.schurter.com /PG17_20
Circuit Breakers
Rated current Configuration
key
2.5 A 2.5
2.8 A 2.8
3.0 A 3
3.3 A 3.3
3.5 A 3.5
4.0 A 4
4.5 A 4.5
5.0 A 5
5.5 A 5.5
6.0 6
6.5 A 6.5
7.0 A 7
7.5 A 7.5
8.0 A 8
8.5 A 8.5
9.0 A 9
Other rated currents on request
Rated current Configuration
key
9.5 A 9.5
10.0 A 10
11.0 A 11
12.0 A 12
13.0 A 13
14.0 A 14
15.0 A 15
16.0 A 16
17.0 A 17
18.0 A 18
19.0 A 19
20.0 A 20
22.0 A 22
25.0 A 25
28.0 A 28
30.0 A 30
Other rated currents on request
Variants
Rated current Setting indication Config. Code Order Number
15.0 A T13-211-15 4411.0007
20.0 A T13-211-20 4411.0010
30.0 A T13-211-30 4411.0017
18.0 A T13-211-18 4411.0019
25.0 A T13-211-25 4411.0073
30.0 A
l
T13-211R-30 4411.0221
Most Popular.
Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-
Check/Stock-Check-SCHURTER
Packaging Unit
20 Pcs
Accessories
Description
T-Line Accessories
Accessories to T-Line
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
11.04.2018

4411.0087

Mfr. #:
Manufacturer:
Schurter
Description:
Circuit Breakers CBE T13-211R-1
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union