IB IL 24 DO 8 ...
5558_en_08 9
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
8 Programming data/
configuration data
8.1 Local bus (INTERBUS)
8.2 Other bus systems
9 Process data
Assignment of the terminal points to OUT process data
The following table applies to the IB IL 24 DO 8-PAC and
IB
IL 24 DO 8-2MBD-PAC terminals with the original con-
nector set and when using the IB IL DI/DO 8-PLSET and IB
IL DI/DO 8-PLSET/CP connector sets (see also
Figure 3 on
page 7, detail B).
The following table applies to the IB IL 24 DO 8-PAC/SN
and IB
IL 24 DO 8-2MBD-PAC/SN terminals with the origi-
nal connector set and when using the IB IL SCN-8 or IB IL
SCN-8-CP connectors (see also
Figure 3 on page 7,
detail A).
ID code BD
hex
(189
dec
)
Length code 81
hex
Process data channel 8 bits
Input address area 0 bytes
Output address area 1 byte
Parameter channel (PCP) 0 bytes
Register length (bus) 1 byte
For the programming data/configuration data of
other bus systems, please refer to the corre
-
sponding electronic device data sheet (GSD,
EDS).
For the assignment of the illustrated (byte.bit)
view to your INTERBUS control or computer sys
-
tem, please refer to the
DB
GB IBS SYS ADDRESS data sheet.
(Byte.bit)
view
Byte Byte 0
Bit 7 6 5 4 3 2 1 0
Assign-
ment
Slot 4 3 2 1
Terminal
point (signal)
8.1 7.1 6.1 5.1 4.1 3.1 2.1 1.1
Terminal point
(+24 V)
8.2 7.2 6.2 5.2 4.2 3.2 2.2 1.2
Terminal point
(GND)
8.3 7.3 6.3 5.3 4.3 3.3 2.3 1.3
Terminal point
(FE)
8.4 7.4 6.4 5.4 4.4 3.4 2.4 1.4
Status in-
dicator
Slot 4 3 2 1
LED 2 1 2 1 2 1 2 1
(Byte.bit)
view
Byte Byte 0
Bit 7 6 5 4 3 2 1 0
Assign-
ment
Slot 4 3 2 1
Terminal
point (signal)
2.1 1.1 2.1 1.1 2.1 1.1 2.1 1.1
Terminal point
(+24 V)
2.2 1.2 2.2 1.2 2.2 1.2 2.2 1.2
Terminal point
(GND)
2.3 1.3 2.3 1.3 2.3 1.3 2.3 1.3
Terminal point
(FE)
2.4 1.4 2.4 1.4 2.4 1.4 2.4 1.4
Status in-
dicator
Slot 4 3 2 1
LED 2 1 2 1 2 1 2 1