CB
-
CD
-
XD10
-
XB10
-
XR06
-
XR10: 8 A
XD26
-XB26: 8 x 8 A relays, 2 x 5 A relays
XE10: 4 x 5 A relays
XR14: 4 x 8 A relays, 2 x 5 A relays
Electrical durability for 500 000 operating cycles
Usage category DC
-12: 24 V, 1.5 A
Usage category DC
-13: 24 V (L/R = 10 ms), 0.6 A
Usage category AC-12: 230 V, 1.5 A
Usage category AC-15: 230 V, 0.9 A
Minimum switching capacity
10 mA (at minimum voltage of 12 V)
Off load: 10 Hz
At operating current: 0.1 Hz
10,000,000 operations (cycles)
Voltage for withstanding shocks
In accordance with IEC/EN 60947
-
1 and IEC/EN 60664
-1: 4 kV
Against short-circuits: None
Against overvoltages and overloads: None
On LCD screen for CD and XD
Digital / PWM solid state output
CD12
-
XD10
-
XB10: O4
CD20
-
XD26
-
XB26:O4→O7
* Only available with "FBD" programming language
* Only available with "FBD" programming language
≤2VforI=0.5A(atstate1)
≤2VforI=0.5A(atstate1)
Make≤1ms
Release≤1ms
Make≤1ms
Release≤1ms
Against overloads and short-circuits: Yes
Against overvoltages (*) : Yes
Against inversions of power supply: Yes
(*) In the absence of a volt-free contact between the output of the
logic controller and the load
Against overloads and short-circuits: Yes
Against overvoltages (*) : Yes
Against inversions of power supply: Yes
(*) In the absence of a volt-free contact between the output of the
logic controller and the load
Maximum incandescent load
0,2 A / 12
V DC
0,1 A / 24 V DC
14.11 Hz
56.45 Hz
112.90 Hz
225.80 Hz
451.59 Hz
1806.37 Hz
14.11 Hz
56.45 Hz
112.90 Hz
225.80 Hz
451.59 Hz
1806.37 Hz
0→100%(256stepsforCD,XDand1024forXA)
0→100%(256stepsforCD,XDand1024forXA)
<5%(20%→80%)loadat10mA
<5%(20%→80%)loadat10mA
<10%(20%→80%)loadat10mA
<10%(20%→80%)loadat10mA
On LCD screen for CD and XD
On LCD screen for CD and XD
Multilingual programming software containing specific library functions (CD-
ROM)
3mseriallinkcable:PC→Millenium3
3mUSBlinkcable:PC→Millenium3
Millenium3→Bluetoothinterface(classA10m)
* to be marketed 1
st
quarter 2006
www.crouzet.com
14/10/2010