3
Technical Data 2092
Effective December 2015
1-Pole IEC Class II surge arresters for
75V-1000V TN and TT wind power systems
Eaton.com/bussmannseries
Ordering information:
System voltage (50-60Hz) / poles 75V / 1 230V / 1 400V / 1 400V†/690V†† / 1 1000V / 1
Max. Continuous Operating Voltage
(MCOV) [U
C
] AC (50-60Hz)
75V 255V 440V 600V 1000V
Catalog numbers
(base + modules)
W/ remote
signaling
BSPM175WE BSPG1230WE BSPM1400WE BSPM1690WE BSPM11000WE
W/ remote
signaling
BSPM175WER BSPG1230WER BSPM1400WER BSPM1690WER BSPM11000WER
Replacement modules BPM75WE BPG255NPEWE* BPM440WE BPM750WE N/A
Specifications
Line system type TN / TT TT TN / TT TN / TT TN / TT
Max. continuous operating DC voltage
[U
C
]
100V — 585 600V 1000V
Rated varistor voltage AC [U
mov
] — — — 750V 1000V
Nominal discharge current (8/20μs) [I
n
] 10kA 20kA 20kA 15kA 15kA
Max. discharge current (8/20μs) [I
max
] 40kA 40kA 40kA 25kA 30kA
Follow current extinguishing capability [I
fi
] — 100 Arms — — —
Lightning impulse current (10/350μs) [I
imp
] — 12kA — — —
Voltage protection level [U
P
] ) 0.4kV ) 1.5kV ) 2.0kV ) 3kV ) 4.2kV
[U
P
] at 5kA ) 0.35kV — ) 1.7kV ) 2.5kV ) 3.5kV
Response time [t
A
] ) 25 ns ) 100 ns ) 25 ns ) 25 ns ) 25 ns
Max. mains-side overcurrent protection 125A gG — 125A gG 100A gG 100A aM**
Short-circuit withstand capability for max.
mains-side overcurrent protection (I
SCCR
)
50kA
rms
— 25kA
rms
25kA
rms
25kA
rms
Temporary Overvoltage
(TOV) [U
T
]
Withstand 90V / 5 sec. 1200V / 200ms 580V / 5 sec. 900V / 5 sec. 1000V / 5 sec.
Safe failure
Agency information KEMA, CSA KEMA KEMA, CSA KEMA, CSA —
Capacity (DIN 43880) 1 Mod. 1 Mod. 1 Mod. 1 Mod. 2 Mod.
SPD according to EN 61643-11 Type 2, IEC 61643-11 Class II
Operating environment [T
U
] -40°C to +80°C, 5% to 95% RH
Operating state/fault indication Green (good) / Red (replace)
Number of ports 1
Cross-Sectional Area
Min. 1.5mm
2
/ 14AWG solid / flexible
Max. 35mm
2
/ 2AWG stranded-25mm
2
/ 4AWG flexible
Mounting 35mm DIN-Rail per EN 60715
Enclosure material Thermoplastic, UL 94V0
Location category Indoor
Degree of protection IP20 (built-in)
Product warranty Five years***
Remote contact signaling
Remote contact signaling type Changeover contact
Switching capacity
(volts/mps)
AC 250V / 0.5A
DC 250V / 0.1A; 125V / 0.2A; 75V / 0.5A
Conductor ratings and cross-sectional area 60/75°C Max. 1.5mm
2
/ 14AWG solid / flexible
Ordering information Order from catalog numbers above
* N-PE surge arrester for location between neutral conductor and protective conductor in TT systems.
** 125A gG @ 690Vac.
*** See Eaton’s Bussmann series SPD limited warranty statement (3A1502) for details at www.cooperbussmann.com/surge.
† 400V [L-N]
†† 690V [L-L]
Recommended Bussmann series NH DIN back up fuses
Size Fuse catalog number
00 100NHG00B-690
00 125NHG00B-690