DS1831C/D/E
7 of 15
OPERATION—PUSHBUTTON STATUS
The DS1831E provides a master pushbutton status open drain output. The PBST output indicates the
status of the most recent reset condition. If the last reset was generated by the master pushbutton input it
would maintain a low condition until cleared by another event (except the master pushbutton) generating
a reset. Once cleared it will remain high until the master pushbutton is pulled low generating a reset
condition. The PBST output is open drain and will require a pull-up resistor on the output to maintain a
valid condition. The value of the pull up resistor is not critical in most cases but must be set low enough
to pull the output to a high state. A common value used is 10kW (see Figure 6).
DS1831E APPLICATION EXAMPLE Figure 6
OUTPUT VALID CONDITIONS
The DS1831 can maintain valid outputs as long as one input remains above 1.0V. Accurate voltage
monitoring additionally requires that either the 3.3V IN or 2.5V IN input be above 1.5V. If this condition
is not met and at least one of the supply inputs are at or above 1.0V all outputs are maintained in the
active condition. The DS1831 requires pull-up resistors on the outputs to maintain a valid output. The
value of the pull up resistor is not critical in most cases but must be set low enough to pull the output to a
high state. A common pull-up resistor value used is 10kW (see Figure 7).
PBRST
2.5V
GND
NMI2
IN1
NMI1
V
SENSE1
IN2
MPBRST
V
SENSE2
V
CC
10
k
W
DS1831E
RST
2.5V
TD
2.5V
IN
2.5V
TOL
2.5V
2.5V
PBST
IN
3.3V
RST
3.3V
TOL
3.3V
TD
3.3V
3.3V Supply
V
CC
10
k
W
1
2
3
4
5
6
7
8
16
15
14
13
12
11
10
9
DS1831C/D/E
8 of 15
APPLICATION DIAGRAM—OPEN DRAIN OUTPUTS Figure 7
NOTE: If outputs are at different voltages the outputs can not be connected to form a wired AND.
OPERATION—NON-MASKABLE INTERRUPT
The DS1831 has two referenced comparators (DS1831D has only one referenced comparator) that can be
used to monitor upstream voltages or other system specific voltages. Each comparator is referenced to the
1.25V internal band gap reference and controls an open-drain output. When a voltage being monitored
decays to the voltage sense point, the DS1831 pulses the NMI output to the active state for a minimum
10µs. The comparator detection circuitry also has built-in hysteresis of 100µV. The supply must be below
the voltage sense point for approximately 2µs before a low NMI will be generated. In this way, power
supply noise is minimized in the monitoring function, reducing false interrupts. See Figure 8 for the non-
maskable timing diagram.
Versatile trip voltages can be configured by the use of an external resistor divider to divide the voltage at
a sense point to the 1.25V trip levels of the referenced comparators. See Figure 9 for an example circuit
diagram and sample equations. The equations demonstrate a design process to determine the resistor
values to use.
Connecting one or both
NMI outputs to one of the reset specific PBRST s allows the non-maskable
interrupt to generate an automatic reset for the reset time period when an out-of-tolerance condition
occurs in a monitored supply. An example is shown in Figure 9.
The output associated with the specific input will be held low if the voltage on the input pin is less than
1.25V. If the voltage is above 1.25V the output will not sink current and will be pulled up by the required
pull-up resistor. The value of the resistors is not critical in most cases but must be set low enough to pull
the output to a high state. A common value used is 10kW. If an NMI output is connected to a pushbutton
input an additional pull-up resistor can be used (to improve speed of transitions) but is not required.
During a power-up, any detected IN pin levels above V
TP
by the comparator are disabled from generating
an inactive (high) interrupt until at least one supply on the V
IN
inputs rises above 1.5V. All NMI outputs
will be held active (low) until at least one V
IN
reaches 1.5V at which point the NMI outputs will be based
on the value of the associated IN input.
RST
2.5V
PBRST
3.3V
GND
TD
2.5V
IN
3.3v
IN
2.5V
RST
3.3V
TOL
3.3V
PBRST
2.5V
TOL
2.5V
DS1831C
TD
3.3V
2.5V Supply
3.3V Supply
1
2
3
4
5
16
15
14
13
12
10
K
W
10 KW
DS1831C/D/E
9 of 15
TIMING DIAGRAM—NON-MASKABLE INTERRUPT Figure 8
NON-MASKABLE INTERRUPT CIRCUIT EXAMPLE Figure 9
Example: V
SENSE1
= 11.50 volts trip point V
SENSE1
=
R2
R2R1
+
X 1.25V
Therefore: 11.50V =
k 100
k 100R1 +
X 1.25V
Resulting In: R1 = 820 kW
Repeat the same steps to solve for R3 and R4 with V
SENSE2
.
V
IN
>1.25 V
V
TP
V
TP(min)
V
TP(max)
t
IPD
NMI
V
OL
V
TP
V
TP(min)
V
TP(max)
V
OH
t
NMI
R1
DS1831C
GND
IN1
V
SENSE1
R2
IN2
R3
V
SENSE2
R4
V
CC
10 kW
PBRST
2.5V
PBRST
3.3V
NMI1
NMI2
MPBRST
W
W

DS1831C

Mfr. #:
Manufacturer:
Maxim Integrated
Description:
Supervisory Circuits 3.3/5V Multisupply MicroMonitor
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet