MAX6622
ALERT
Response Address
The SMBus alert response interrupt pointer provides
quick fault identification for simple slave devices that
lack the complex logic needed to be a bus master.
Upon receiving an interrupt signal, the host master can
broadcast a receive byte transmission to the alert
response slave address (see the
Slave Address
sec-
tion). Then, any slave device that generated an inter-
rupt attempts to identify itself by putting its own
address on the bus.
The alert response can activate several different slave
devices simultaneously, similar to the I
2
C General Call.
If more than one slave attempts to respond, bus arbitra-
tion rules apply, and the device with the lower address
code wins. The losing device does not generate an
acknowledgment and continues to hold the ALERT line
low until cleared. (The conditions for clearing an alert
vary depending on the type of slave device.)
Successful completion of the alert response protocol
clears the output latch. If the condition that caused the
alert still exists, the MAX6622 reasserts the ALERT
interrupt at the end of the next conversion.
OVERT
Overtemperature Alarms
The MAX6622 has two overtemperature registers that
store remote alarm threshold data for the OVERT output.
OVERT is asserted when a channel’s measured temper-
ature is greater than the value stored in the correspond-
ing threshold register. OVERT remains asserted until the
temperature drops below the programmed threshold
minus 4°C hysteresis. An overtemperature output can
be used to activate a cooling fan, send a warning, initi-
ate clock throttling, or trigger a system shutdown to pre-
vent component damage. See Table 3 for the POR state
of the overtemperature threshold registers.
Command Byte Functions
The 8-bit command byte register (Table 3) is the master
index that points to the various other registers within the
MAX6622. This register’s POR state is 0000 0000.
Configuration Byte Functions
There are three read-write configuration registers
(Tables 4, 5, and 6) that can be used to control the
MAX6622’s operation.
Configuration 1 Register
The configuration 1 register (Table 4) has several func-
tions. Bit 7 (MSB) is used to put the MAX6622 either in
software standby mode (STOP) or continuous conver-
sion mode. Bit 6 resets all registers to their power-on-
reset conditions and then clears itself. Bit 5 disables the
SMBus timeout. Bit 4 enables more frequent conver-
sions on channel 1, as described in the
ADC
Conversion Sequence
section. Bit 3 enables resistance
cancellation on channel 1. See the
Series Resistance
Cancellation
section for more details. The remaining
bits of the configuration 1 register are not used. The
POR state of this register is 0000 0000 (00h).
Configuration 2 Register
The configuration 2 register functions are described in
Table 5. Bits [6:0] are used to mask the ALERT interrupt
output. Bit 6 masks the local alert interrupt and bit 5
through bit 2 mask the remote alert interrupts. The
power-up state of this register is 0000 0000 (00h).
Configuration 3 Register
Table 6 describes the configuration 3 register. Bits 5, 4,
3, and 0 mask the OVERT interrupt output for channels
4 and 1. The remaining bits, 7, 6, 5, 4, 2, and 1, are
reserved. The power-up state of this register is 0000
0000 (00h).
Status Register Functions
Status registers 1, 2, and 3 (Tables 7, 8, and 9) indicate
which (if any) temperature thresholds have been
exceeded and if there is an open-circuit or short-circuit
fault detected with the external sense junctions. Status
register 1 indicates if the measured temperature has
exceeded the threshold limit set in the ALERT registers
for the local or remote-sensing diodes. Status register 2
indicates if the measured temperature has exceeded
the threshold limit set in the OVERT registers. Status
register 3 indicates if there is a diode fault (open or
short) in any of the remote-sensing channels.
Bits in the alert status register clear by a successful
read, but set again after the next conversion unless the
fault is corrected, either by a drop in the measured tem-
perature or an increase in the threshold temperature.
The ALERT interrupt output follows the status flag bit.
Once the ALERT output is asserted, it can be deassert-
ed by either reading status register 1 or by successful-
ly responding to an alert response address. In both
5-Channel Precision Temperature Monitor
10 ______________________________________________________________________________________
cases, the alert is cleared even if the fault condition
exists, but the ALERT output reasserts at the end of the
next conversion. The bits indicating the fault for the
OVERT interrupt output clear only on reading the status 2
register even if the fault conditions still exist. Reading the
status 2 register does not clear the OVERT interrupt out-
put. To eliminate the fault condition, either the measured
temperature must drop below the temperature threshold
minus the hysteresis value (4°C), or the trip temperature
must be set at least 4°C above the current temperature.
MAX6622
5-Channel Precision Temperature Monitor
______________________________________________________________________________________ 11
REGISTER
ADDRESS
(hex)
POR STATE
(hex)
READ/
WRITE
DESCRIPTION
Local 07 00 R Read local temperature register
Remote 1 01 00 R Read channel 1 remote temperature register
Remote 2 02 00 R Read channel 2 remote temperature register
Remote 3 03 00 R Read channel 3 remote temperature register
Remote 4 04 00 R Read channel 4 remote temperature register
Configuration 1 41 00 R/W Read/write configuration register 1
Configuration 2 42 00 R/W Read/write configuration register 2
Configuration 3 43 00 R/W Read/write configuration register 3
Status1 44 00 R Read status register 1
Status2 45 00 R Read status register 2
Status3 46 00 R Read status register 3
Local ALERT High Limit 17 5A R/W Read/write local alert high-temperature threshold limit register
Remote 1 ALERT High Limit 11 6E R/W
Read/write channel 1 remote-diode alert high-temperature
threshold limit register
Remote 2 ALERT High Limit 12 7F R/W
Read/write channel 2 remote-diode alert high-temperature
threshold limit register
Remote 3 ALERT High Limit 13 64 R/W
Read/write channel 3 remote-diode alert high-temperature
threshold limit register
Remote 4 ALERT High Limit 14 64 R/W
Read/write channel 4 remote-diode alert high-temperature
threshold limit register
Remote 1 OVERT High Limit 21 6E R/W
Read/write channel 1 remote-diode overtemperature threshold
limit register
Remote 4 OVERT High Limit 24 7F R/W
Read/write channel 4 remote-diode overtemperature threshold
limit register
Remote 1 Extended
Temperature
09 00 R Read channel 1 remote-diode extended temperature register
Manufacturer ID 0A 4D R Read manufacturer ID
Table 3. Command Byte Register Bit Assignment
MAX6622
5-Channel Precision Temperature Monitor
12 ______________________________________________________________________________________
Table 6. Configuration 3 Register
BIT NAME
POR
STATE
FUNCTION
7 (MSB) Reserved 0
6 Reserved 0
5 Reserved 0
4 Reserved 0
3 Mask OVERT 4 0
Channel 4 Remote-Diode OVERT Mask Bit. Set to logic 1 to mask channel 4
OVERT.
2 Reserved 0
1 Reserved 0
0 Mask OVERT 1 0
Channel 1 Remote-Diode OVERT Mask Bit. Set to logic 1 to mask channel 1
OVERT.
BIT NAME
POR
STATE
FUNCTION
7 (MSB) STOP 0
Standby Mode Control Bit. If STOP is set to logic 1, the MAX6622 stops
converting and enters standby mode.
6 POR 0
Reset Bit. Set to logic 1 to put the device into its power-on state. This bit is self-
clearing.
5 TIMEOUT 0 Timeout Enable Bit. Set to logic 0 to enable SMBus timeout.
4 Fast remote 1 0
Channel 1 Fast Conversion Bit. Set to logic 1 to enable fast conversion of
channel 1.
3
Resistance
cancellation
0
Resistance Cancellation Bit. When set to logic 1, the MAX6622 cancels series
resistance in the channel 1 thermal diode.
2 Reserved 0
1 Reserved 0
0 Reserved 0
Table 4. Configuration 1 Register
Table 5. Configuration 2 Register
BIT NAME
POR
STATE
FUNCTION
7 (MSB) Reserved 0
6 Mask Local ALERT 0 Local Alert Mask. Set to logic 1 to mask local channel ALERT.
5 Reserved 0
4 Reserved 0
3 Mask ALERT 4 0 Channel 4 Alert Mask. Set to logic 1 to mask channel 4 ALERT.
2 Mask ALERT 3 0 Channel 3 Alert Interrupt Mask. Set to logic 1 to mask channel 3 ALERT.
1 Mask ALERT 2 0 Channel 2 Alert Mask. Set to logic 1 to mask channel 2 ALERT.
0 Mask ALERT 1 0 Channel 1 Alert Mask. Set to logic 1 to mask channel 1 ALERT.

MAX6622UE9A+T

Mfr. #:
Manufacturer:
Maxim Integrated
Description:
Board Mount Temperature Sensors 5Ch Precision Temperature Monitor
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet