ELR H5-ES-SC-230AC/500AC-9 Order No.: 2900562
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2900562
PHOENIX CONTACT Inc., USA Page 2 / 6
http://www.phoenixcon.com May 9, 2011
Rated control supply voltage range with reference
to U
S
0.4 ... 1.1
Rated control supply current I
S
3.5 mA
Rated actuating voltage U
C
230 V AC
Rated actuating voltage range with reference to
U
C
0.4 ... 1.1
Rated actuating current I
C
7 mA
Switching threshold "0" signal, voltage 44 V AC
Switching threshold "1" signal voltage 85 V AC
Protective circuit Surge protection
Typical response time < 35 ms
Typical turn-off time < 80 ms
Operating voltage display Green LED
Status display Yellow LED
Indication Red LED
Output data, load relay
Output name AC output
Nominal output voltage 500 V AC
Nominal output voltage range 48 V AC ... 550 V AC
Load current max. 9 A (see derating curve)
Leakage current 0 mA
Residual voltage < 0.3 V
Surge current 100 A (t = 10 ms)
Type of protection Surge protection
Output name Acknowledge output
Note Confirmation 01: Floating PDT contact
Nominal output voltage max. 253 V AC 0% ... 100% (300 V DC)
Continuous load current 2 A
Output data, signaling contact
Measuring via Current transformer for line current on L1 and L3
Connection data
Connection method Screw connection
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 2.5 mm²