CRD4510-150

Data Stream
17
B
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
The Professional
Energy Monitoring
Company
ISO 9001:2008 Quality Management System
M
N
T
I
Data Stream RS485 Digital Voltage Transducer
CRD4510
Single Element
150 to 300 VAC Input Range
CRD4550
Two Element
150 to 300 VAC Input Range
CRD4570
Three Element - .26” Window
150 to 300 VAC Input Range
The CRD4500 Series Data Stream Digital Transducers are
designed for applications where AC current waveforms are not
purely sinusoidal.
The digital technology is used to measure voltage,
current, power frequency and energy in single and three phase
designs. The data is streamed over an RS485 IEEE bus which enables
multiple transducers to communicate thru a single master connection.
These advanced sensors are ideal for entire plant or zone monitoring.
Also, the communication alagorithm can be pre-ordered with ASCII
based control or modified MODBUS based control.
Sensing
True RMS Voltage, Each Phase
Applications
Sub-Metering
Motor Loads
Uninterruptible Power Systems
Remote Monitoring
Load Shedding
Energy Management
Features
35mm DIN Rail or Panel Mount
24 VDC powered
Use with external current transformers
Highest precision available
Connection diagram printed on case
Regulatory Agencies
150 - 0-150 VAC
300 - 0-300 VAC
Available up to and including 600 VAC
Note: Add an M at
the end for MODBUS
CRD4510-150-M
PART NUMBERS
CRD4510
-
Single Element, AC Voltage RS485 Digital Transducer
CRD4550
-
Two Element, AC Voltage RS485 Digital Transducer
CRD4570
-
Three Element, AC RS485 Digital Transducer
DIN RAIL / PANEL MOUNT
18
Data Stream
B
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
The Professional
Energy Monitoring
Company
ISO 9001:2008 Quality Management System
M
N
T
I
RS485 Digital Voltage Transducer
CRD4550 Dual Element, 3-Wire
CRD4550 Dual Element, 3-Wire
CRD4570 3 Element, 4-Wire
N
L3 L1
L2
1
3
4
2
LOAD
9
8
7
6
5
+
-
+
-
485
SUPPLY
1
2
3
4
5
6
7
8
9
-
-
+
+
SUPPLY
485
L1N
-
-
+
+
LOAD
8
7
9
5
6
1
4
2
3
L3 L1L2
SUPPLY
485
-
-
+
+
LOAD
8
7
9
5
6
1
4
2
3
L2 L1N
SUPPLY
485
CRD4510 Single Element, 2-Wire
Connection Diagram
LINE
LOAD
LOAD
LOAD
LOAD
SUPPLY
SUPPLY
SUPPLY
L3 L2 L1
L3 L2 L1
N
N
L2
L1
485
485
485
ASCII Simplified Programming Commands
A simplified data structure is used with only 6 commands required for full control of
the transducer. Commands are : Read Transducer Name, Read Configuration, Set
Configuration, Read Measurements, Read Energy Totalizer and Clear Energy
Totalizer. For illustration, the following commands are used to read data from a
CRD5170 3 Phase, 4 Wire Transducer with a device address of 00.
Command Transducer to Read Data: #00A<cr>
Transducers Response: >+[% FS Voltage
L1-N
]+[% FS Current
L1
]+[% FS
Voltage
L2-N
]+[% FS Current
L2
]+[% FS Voltage
L3-N
]+[% FS Current
L3
,][+/- % FS
Power][+/-% FS VARS][+/-Power Factor][Frequency]<cr>
Command Transducer to Read Energy Totalizer: #00W<cr>
Transducer Responds: 01[+/-KWHr]
{\[+/-KVHr][check sum]<cr>
Note: This is for illustration purposes only, See Applications Guides (Section I
for complete instructions.
SPECIFICATIONS
2.874
(73)
2.99
(76)
0.20
(5.1)
(83)
3.268
OUTLINE DRAWING
9
8
7
6
5
1
2
3
4
1.42
(36)
DIA.
0.14
(3.5)
1.06
(26.8)
2.874
(73)
DATA +
DATA-
GND
+5VDC
COM
RS232
CRD485-232
SUPPLY
5
6
7
9
8
+
-
DATA STREAM
TRANSDUCER
TX
RX
GND
DB 9, FEMALE
1
2
3
4
CRD485-232
RS485 to RS232 Converter Accessory
Connect PC to RS485 Bus
Basic Accuracy: .......................0.5%
Calibration: ..............................True RMS Sensing
Thermal Drift: ..........................500 PPM/°C
Operating Temperature
1
: ..........0°C to +60°C
Installation Category: ..............CAT II
Vibration Tested To: .................IEC 60068-2-6,1995
Pollution Degree: ....................2
Insulation Voltage: ..................2500 VDC
Altitude: ..................................2000 meter max
Frequency Range: .................20 Hz - 5 KHz
MTBF: ....................................Greater than 100K hours
Cleaning: ................................Water-dampened cloth
Supply Voltage
2
: ......................24 VDC ±10%
1) RH 5% to 95%, non-condensing 2) 0.4% max. ripple Vpp
3) Factory default settings: address 01, baud rate 9600, no parity,
Torque Specifications: ....................3.0 inch lbs (0.4Nm)
Response Time: .......................250 ms. max. 0-90% FS
Relative Humidity: ...............80% for temperatures up to
31°C and decreasing linearly to 50% at 40°C
Output Resolution: ..................................................16 bit
Transducer fanout on common bus: ...................64 max.
Baud Rate
3
: ...............1200, 2400, 4800, 9600,19.2K .bps
A/D Conversion Type: ..................4th order Delta Sigma
Device Address
3
: ............................................00 to FF
Data Format: .... .....................................................ASCII
Supply Current:..................Typical 30mA Max 30mA
Weight:.. ..............................................................0.5 lbs.
no flow control, 1 stop bit

CRD4510-150

Mfr. #:
Manufacturer:
Description:
TRANSDCR VLT AC RS485 0-150VAC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union