USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options;
LED/LCD panel rotates for viewing in rack/tower formats (see manual)
Switches 2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and
execute scrolling LCD functions; bundled PDU includes bypass switch to enable hot-swap UPS power module
replacement
Alarm Cancel Operation Alarm cancel switch
Audible Alarm Unique audible alarms for all major UPS, environmental and power conditions (see manual)
LED Indicators 6 LEDs indicate line power, online mode, bypass mode, on-battery, charger and AC output status; LCD screen offers
additional information and control options
SURGE / NOISE SUPPRESSION
UPS AC Suppression Response
Time
Instantaneous
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Included Mounting Accessory
Description
4 sets of adjustable 4 post rack rails included (one for each included 3U module)
Installation Form Factors Supported
with Optional Accessories
2 post rackmount (2POSTRMKITHD); Tower (2-9USTAND)
Optional Mounting Accessory Notes Qty 4 <a class="productLink" href="//www.tripplite.com/2-Post-Rack-Mount-Installation-Kit-3U-Larger-UPS-
Transformer-Battery-Pack-Components~2POSTRMKITHD">2POSTRMKITHD</a> required; Qty 2 <a
class="productLink" href="//www.tripplite.com/2U-9U-Tower-Stand-Kit-select-Rack-Mount-UPS-Systems~2-
9USTAND">2-9USTAND</a> required
Primary Form Factor Rackmount
UPS Power Module Dimensions
(hwd, in.)
5.14 x 17.5 x 25.82
UPS Power Module Dimensions
(hwd, cm)
13.06 x 44.45 x 65.58
Rack Height (U Spaces) 12
Maximum Device Depth (in.) 32.5
Minimum Required Rack Depth
(inches)
37.5
Maximum Device Depth (cm) 82.55
Minimum Required Rack Depth (cm) 95.25
UPS Power Module Weight (lbs.) 43
UPS Power Module Weight (kg) 19.50
UPS Dimensions Details Includes 2 SU8000RT3UPM UPS/Power modules, 2 BP240V10RT3U Battery packs and SUPDMB20KHW parallel
bypass PDU; Listed weights and dimensions for UPS/Power module and Included battery pack each refer to a single
unit; MAXIMUM DEVICE DEPTH specification refers to the whole UPS installed depth with parallel bypass PDU
installed
Included Battery Pack Dimensions
(hwd / in.)
5.25 x 17.5 x 25
Included Battery Pack Weight (lbs.) 158.7
4 / 6