INTERBUS-ST counter module, 4 counter inputs, 24 V or 5 V DC signal level, IP20 protection, consisting of:
Terminal part with screw connection and module electronics
Product description
INTERBUS ST counter module
The IB ST 24 CNT module is designed for counting pulses, measuring frequencies and periods, and generating square-wave pulses.
The module has 4 channels which can be operated independently of one another. The counter then has a 16-bit resolution. Cascading is possible by
simply connecting several counters in a row.
Each channel has a digital output that can be set according to the event. Simple applications can use a single device.
The module is available with either screw or spring-cage connection. 
Product Features
Connection of actuators in 2-wire technology
Connection of sensors in 2 or 3-wire technology
Short-circuit-proof and overload-protected outputs
Key commercial data
Packing unit 1 pc
GTIN
Weight per Piece (excluding packing) 737.4 GRM
Custom tariff number 85389091
Country of origin Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Interfaces
Interface ST local bus
Connection method ST local bus connector
Transmission speed 500 kBit/s
https://www.phoenixcontact.com/us/products/2750400
09/08/2014Page2/5
Special function module-IB ST 24 CNT-2750400
Technical data
Interfaces
Transmission physics Copper
Ambient conditions
Degree of protection IP20
Power supply
Communications power U
L
9 V DC (UI, from the ST local bus)
Max. current consumption 220 mA (from the local bus)
Typical current consumption 200 mA (from the local bus)
4 A (max., to Us)
I/O voltage 24 V DC (Us)
Ripple ± 1.2 V 5 %
I/O voltage range 20 V ... 30 V
Electrical isolation
Test section Bus/Outputs 500 V AC 50 Hz 1 min
Bus/Inputs 500 V AC 50 Hz 1 min
Bus/Ground conductor 500 V AC 50 Hz 1 min
I/O voltage/Ground conductor 500 V AC 50 Hz 1 min
Counter input
Number of inputs 4
Operating mode Event counting, frequency/time measurement
Input frequency 90 kHz (max. 300 kHz)
Input voltage 5 V DC
24 V DC
Input current 11 mA (typ., 24 V DC input)
8 mA (typ., 5 V DC input)
Control input
Number of inputs 4
Connection method 2, 3-wire
Outputs
Number of outputs 4
Connection method 2-wire
Output voltage
U
S
- 0.5 V DC U
Out LED
U
S
Output current 500 mA (per output, up to 300 Hz)
250 mA (per output, up to 10 kHz)
500 mA (per sensor)
https://www.phoenixcontact.com/us/products/2750400
09/08/2014Page3/5
Special function module-IB ST 24 CNT-2750400
Technical data
General
Weight 660 g
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Connection data Screw connection 0.2 mm² 2.5 mm² 0.2 mm² 2.5 mm² 24 12 8 mm
Classifications
eCl@ss
eCl@ss 4.0 27250304
eCl@ss 4.1 27250304
eCl@ss 5.0 27250304
eCl@ss 5.1 27242605
eCl@ss 6.0 27242605
eCl@ss 7.0 27242605
eCl@ss 8.0 27242605
ETIM
ETIM 2.0 EC001433
ETIM 3.0 EC001601
ETIM 4.0 EC001601
ETIM 5.0 EC001601
UNSPSC
UNSPSC 6.01 43172015
UNSPSC 7.0901 43201404
UNSPSC 11 43172015
UNSPSC 12.01 43201404
UNSPSC 13.2 43201404
Approvals
Approvals
Approvals
GOST
Ex Approvals

2750400