2800186

https://www.phoenixcontact.com/pi/products/2800186
04/30/2017Page1/7
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 335/12.5/1+1-
FM-2800186
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Universal varistor-based plug-in lightning/surge arrester for 1-phase power supply networks with separate N
and PE (3-conductor system: L1, N, PE), with remote indication contact.
Why buy this product
Plugs can be checked with CHECKMASTER
With floating remote indication contact
Secure hold of plugs in the event of high lightning current loads and strong vibrations thanks to new latching
Thermal disconnect device for each individual plug
Pluggable
Thermal disconnect device for each individual plug
Mechanical coding of all slots
Key Commercial Data
Packing unit 1 STK
GTIN
GTIN 4046356518574
Technical data
Dimensions
Height 99 mm
Width 35.6 mm
Depth 77.5 mm
Horizontal pitch 2 Div.
Ambient conditions
Degree of protection IP20 (only when all terminal points are used)
Ambient temperature (operation) -40 °C ... 80 °C
https://www.phoenixcontact.com/pi/products/2800186
04/30/2017Page2/7
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 335/12.5/1+1-
FM-2800186
Technical data
Ambient conditions
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
Shock (operation) 30g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
IEC test classification I / II
T1 / T2
T1
EN type T1 / T2
T1
IEC power supply system TT
TN-S
Mode of protection L-N
L-PE
N-PE
Mounting type DIN rail: 35 mm
Color jet black RAL 9005
Housing material PA 6.6
PBT
Degree of pollution 2
Flammability rating according to UL 94 V-0
Design DIN rail module, two-section, divisible
Surge protection fault message Optical, remote indicator contact
Protective circuit
Nominal voltage U
N
240V AC (TN-S)
240V AC (TT)
Nominal frequency f
N
50 Hz (60 Hz)
Maximum continuous operating voltage U
C
(L-N)
335 V AC
Maximum continuous operating voltage U
C
(L-PE)
335 V AC
Maximum continuous voltage U
C
(N-PE)
264 V AC
Rated load current I
L
80 A
Residual current I
PE
≤ 5 µA
Standby power consumption P
C
≤ 270 mVA
Nominal discharge current I
n
(8/20) µs (L-N)
12.5 kA
Nominal discharge current I
n
(8/20) µs (L-PE)
12.5 kA
Nominal discharge current I
n
(8/20) µs (N-PE)
50 kA
Maximum discharge current I
max
(8/20) µs
50 kA
https://www.phoenixcontact.com/pi/products/2800186
04/30/2017Page3/7
Lightning/surge arrester type 1/2-VAL-MS-T1/T2 335/12.5/1+1-
FM-2800186
Technical data
Protective circuit
Impulse discharge current (10/350)µs (L-N), charge 6.25 As
Impulse discharge current (10/350) µs (L-N), specific energy 39 kJ/Ω
Impulse discharge current (10/350)µs (L-N), peak current value I
imp
12.5 kA
Impulse discharge current (10/350) µs (L-PE), charge 6.25 As
Impulse discharge current (10/350)µs (L-PE), specific energy 39 kJ/Ω
Impulse discharge current (10/350) µs (L-PE), peak current value I
imp
12.5 kA
Impulse discharge current (10/350) µs (N-PE), charge 25 As
Impulse discharge current (10/350) µs (N-PE), specific energy 625 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), peak current value I
imp
50 kA
Total discharge current I
total
(8/20)µs
50 kA
Total discharge current I
total
(10/350)µs
25 kA
Follow current interrupt rating I
fi
(N-PE)
100 A (264 V AC)
Short-circuit current rating I
SCCR
25 kA
Voltage protection level U
p
(L-N)
≤ 1.2 kV
≤ 1.6 kV (30 kA - 8/20 µs)
Voltage protection level U
p
(L-PE)
≤ 2 kV
Voltage protection level U
p
(N-PE)
≤ 1.7 kV
Residual voltage U
res
(L-N) ≤ 1.2 kV (at I
n
)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
Residual voltage U
res
(L-PE) ≤ 2 kV (at I
n
)
≤ 1.5 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1.1 kV (at 3 kA)
Residual voltage U
res
(N-PE) ≤ 0.6 kV (at I
n
)
≤ 0.5 kV (at 10 kA)
≤ 0.5 kV (at 5 kA)
≤ 0.4 kV (at 3 kA)
TOV behavior at U
T
(L-N)
415 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
TOV behavior at U
T
(N-PE)
1200 V AC (200 ms / withstand mode)
Response time t
A
(L-N)
≤ 25 ns
Response time t
A
(L-PE)
≤ 100 ns
Response time t
A
(N-PE)
≤ 100 ns
Max. backup fuse with branch wiring 160 A (gG)
Max. backup fuse with V-type through wiring 80 A (gG - 16 mm²)
Indicator/remote signaling