Features
■ Size: 11.8 mm diameter,
17 mm length
■ 100 kA surge rating
■ High power handling
■ Low leakage
■ RoHS compliant*
■ UL Recognized
Applications
■ Telecommunications equipment
■ Industrial equipment/electronics
Characteristics
2063 Series High-Current 2-Electrode Gas Discharge Tube
Test Methods per ITU-T K.12 and IEC 61643-311.
Characteristic
Model No.
2063-23 2063-25 2063-30 2063-35 2063-42
DC Sparkover ±20 % @ 100 V/s 230 V 250 V 300 V 350 V 420 V
Impulse Sparkover
(1)
100 V/µs
1000 V/µs
< 600 V
< 700 V
< 600 V
< 700 V
< 700 V
< 800 V
< 800 V
< 900 V
< 900 V
< 1000 V
Insulation Resistance (IR)
(2)
....................................100 / 250 Vdc ........................................................ > 1 GΩ
Glow Voltage ...........................................................10 mA ..................................................................... ~ 70 V
Arc Voltage ..............................................................1 A .......................................................................... ~ 10 V
Glow-Arc Transition Current .................................................................................................................... < 1 A
Maximum Capacitance ............................................1 MHz ..................................................................... < 10 pF
Maximum Impulse Discharge Current .....................100,000 A, 8/20 µs ................................................ 1 operation
60,000 A, 8/20 µs ................................................... 5 operations
Nominal Alternating Discharge Current ...................60 A, 50 Hz, 1 second ............................................ 1 operation
300 A, 9 cycles ...................................................... 1 operation
Impulse Life ............................................................500 A, 10/1000 µs .................................................. > 400 operations
DC Holdover Voltage
(3)
........................................................................................................................... < 150 ms
Operating Temperature ............................................................................................................................ -30 to +85 ºC
Storage Temperature ............................................................................................................................... -40 to +115 °C
Climatic Category (IEC 60068-1)............................................................................................................. 40 / 90 / 21
Notes:
• UL Recognized component, UL File E313168.
• At delivery AQL 0.65, level II DIN ISO 2859
(2)
DC Sparkover Voltage IR Measuring Voltage
230–400 V 100 V
420–800 V 250 V
(3)
Network Applied
DC Sparkover Voltage DC Holdover Voltage
230–250 V 135 V
300–800 V 150 V
*RoHS COMPLIANT
Characteristic
Model No.
2063-47 2063-60 2063-70 2063-80
DC Sparkover ±20 % @ 100 V/s 470 V 600 V 700 V 800 V
Impulse Sparkover
(1)
100 V/µs
1000 V/µs
< 900 V
< 1100 V
< 1100 V
< 1300 V
< 1200 V
< 1400 V
< 1300 V
< 1500 V
*RoHS Directive 2002/95/EC Jan. 27, 2003 including annex and RoHS Recast 2011/65/EU June 8, 2011.
Specifi cations are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specifi c applications.
(1)
Impulse Sparkover voltage is defi ned as typical values of distribution.