https://www.phoenixcontact.com/pi/products/1414358
04/29/2017Page2/4
Contact insert module-HC-M-03-CT-M-1414358
Technical data
Mechanical characteristics
Stripping length of the individual wire 9 mm (for 1.5 - 2.5 mm²)
9.6 mm (for 4 mm² ... 6 mm²)
15 mm (for 10 mm²/conductor ≥ 5 mm diameter)
18 mm (for 10 mm²/conductor ≥ 6.4 mm diameter)
Wire diameter including insulation 7.5 mm
Insertion/withdrawal cycles ≥ 500
Minimum housing height 52 mm
General
Series HC-M-03
Color light gray
Number of module slots 1
Connection method Crimp connection
Connection in acc. with standard IEC / EN
Flammability rating according to UL 94 V0
Degree of pollution 3
Overvoltage category III
Assembly instructions
Housing height ≥ 52 mm.
Plug-in connections may only be operated only when there is no load/
voltage.
Connection
The CK4,0-EWZ tool (order no. 1662735) is required for removing the
crimp contacts.
At every "C" contact chamber, the position of the contact retaining
springs is marked with two black markings on the connection side.
From the connection side, the tool is pushed over the contact in a
position-oriented manner, so that it touches both the retaining springs.
Then insert it up to the limit stop. Do not turn the inserted tool. Push
the conductor out of the insulating body along with the tool from the
connection side.
Material data
Contact material Copper alloy
Contact surface material Ag
Contact carrier material PC
Standards and Regulations
Connection in acc. with standard IEC / EN
Flammability rating according to UL 94 V0
Drawings