MINI-SYS-PS-100-240AC/24DC/1.5
102050_01_en PHOENIX CONTACT 4
Conformance with EMC directive 89/336/EEC
Immunity to interference in acc. with EN 61000-6-2
Discharge of static electricity in acc. with EN 61000-4-2
Housing Level 3
Contact discharge 6 kV
Discharge in air 8 kV
Comments Criterion B
Electromagnetic HF field in acc. with EN 61000-4-3
Housing Level 3
Frequency range 80 MHz ... 2 GHz
Field intensity 10 V/m
Comments Criterion A
Fast transients (burst) in acc. with EN 61000-4-4
Input 4 kV (level 4 - asymmetrical: conductor to ground)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
Signal 1 kV (level 2 - asymmetrical: conductor to ground)
Comments Criterion B
Surge voltage capacities (surge) in acc. with EN 61000-4-5
Input 4 kV (level 4 - asymmetrical: conductor to ground)
2 kV (level 4 - symmetrical: conductor to conductor)
Output 0.5 kV (level 1 - asymmetrical: conductor to ground)
0.5 kV (level 1 - symmetrical: conductor to conductor)
Signal 0.5 kV (level 1 - asymmetrical: conductor to ground)
Comments Criterion B
Conducted disturbance in acc. with EN 61000-4-6
Input/Output/Signal Level 3 - asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V
Comments Criterion A
Voltage dips in acc. with EN 61000-4-11
Input (mains buffering > 20 ms)
Comments Criterion B
Emitted interference in acc. with EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Note:
Criterion A: Normal operating behavior within the defined limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself
EN 55011 corresponds to CISPR11 / EN 55022 corresponds to CISPR22
EN 61000 corresponds to IEC 1000