NDR-240-24

Description
NDR-240 is one economical slim 240W Din rail power supply series, adapt to be installed on TS-35/7.5
or TS-35/15 mounting rails. The body is designed 63mm in width, which allows space saving inside the
cabinets. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to
EN61000-3-2, the norm the European Union regulates for harmonic current.
NDR-240 is designed with metal housing that enhances the unit's power dissipation. With working efficiency
up to 90%, the entire series can operate at the ambient temperature between -20 and 70 under air ℃℃
convection. It is equipped with constant current mode for over-load protection, fitting various inductive
or capacitive applications. The complete protection functions and relevant certificates for industrial control
apparatus (UL508, TUV EN60950-1, and etc.) make NDR-240 a very competitive power supply solution
for industrial applications.
Model Encoding
Universal AC input / Full range
Built-in active PFC function
Protections: Short circuit / Overload / Over voltage
/ Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
Industrial control system
Semi-conductor fabrication equipment
Factory automation
Electro-mechanical
Features Applications
240W Single Output Industrial DIN RAIL
NDR-240 series
Output voltage
Output wattage
Series name
-48NDR - 240
Bauar
Sicherheit
egel gema
t gepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os
File Name:NDR-240-SPEC 2018-01-12
SPECIFICATION
240W Single Output Industrial DIN RAIL
NDR-240 series
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.4
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
1500ms, 100ms/230VAC 3000ms, 100ms/115VAC at full load
28ms/230VAC 22ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
2.5A/115VAC 1.3A/230VAC
29 ~ 33V
88.5%
56 ~ 65V
90%
20A/115VAC 35A/230VAC
<1mA / 240VAC
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
UL508, TUV EN60950-1, approvedEAC TP TC 004
Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A,
EAC TP TC 020
-20 ~ +70 (Refer to "Derating Curve")
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
±℃ 0.03%/ (0 ~ 50 )
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
230.2K hrs min. MIL-HDBK-217F (25 )
63*125.2*113.5mm (W*H*D)
1Kg; 12pcs/13Kg/1.1CUFT
NDR-240-24 NDR-240-48
24V 48V
10A 5A
0 ~ 10A 0 ~ 5A
240W 240W
150mVp-p 150mVp-p
24 ~ 28V 48 ~ 55V
±1.0% ±1.0%
±0.5% ±0.5%
±1.0% ±1.0%
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
ENVIRONMENT
SAFETY &
EMC
(Note 4)
PROTECTION
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltage. Please check the derating curve for more details.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
7. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than ℃℃
2000m(6500ft).
(as available on http://www.meanwell.com)
EMC IMMUNITY
EMC EMISSION
105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
POWER FACTOR (Typ.) PF>0.98/115VAC, PF>0.95/230VAC at full load
;(meet EN60204-1)
File Name:NDR-240-SPEC 2018-01-12
AMBIENT TEMPERATURE ( )
LOAD (%)
-20010203040506070
20
40
50
60
80
100
(VERTICAL)
INPUT VOLTAGE (V) 60Hz
90 100 125 135 145 155 165 175 180 200 230 264
100
90
80
70
60
50
40
LOAD (%)
175
LOAD (%)
DETECTION
PWM & PFC
CIRCUIT
O.L.P.
O.T.P.
EMI FILTER
RECTIFIERS
POWER
SWITCHING
FILTER
&
RECTIFIERS
+V
-V
I/P
FG
CONTROL
O.V.P.
&
O.C.P.
PFC
CIRCUIT
fosc : 70KHz
240W Single Output Industrial DIN RAIL
NDR-240 series
Derating Curve Output derating VS input voltage
Block Diagram
File Name:NDR-240-SPEC 2018-01-12

NDR-240-24

Mfr. #:
Manufacturer:
Description:
DIN Rail Power Supplies 240W 24V 10A Industrial Din Rail
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet