https://www.phoenixcontact.com/pi/products/2906838
08/19/2018Page2/4
Surge protection device-TTC-6-MOV-C-48DC-UT-I-2906838
Technical data
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
Mounting type DIN rail: 35 mm
Type DIN rail module, one-piece
Direction of action Line-Earth Ground
Protective circuit
IEC test classification C1
C2
C3
Nominal voltage U
N
48 V DC
Maximum continuous voltage U
C
60 V DC
42 V AC
Rated current 10 A (60 °C)
Operating effective current I
C
at U
C
≤ 100 µA
Residual current I
PE
≤ 100 µA
Nominal discharge current I
n
(8/20) µs (line-earth)
2 kA
Voltage protection level U
p
(line-earth)
≤ 200 V (C1 - 600 A)
≤ 220 V (C2 - 4 kV)
≤ 150 V (C3 - 25 A)
≤ 160 V (C3 - 35 A)
Response time t
A
(line-earth)
≤ 25 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 200 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system typ. 650 kHz
Capacity (line-earth) 5 nF
Resistance in series ≤ 100 mΩ
Surge protection fault message optical
Impulse durability (line-earth) C1 - 600 A
C2 - 2 kA
C3 - 35 A
Connection data
Connection method Screw connection
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Standards and Regulations