5101C 1
IB ST (ZF) 24 BDI 16/4
03/1999
Data Sheet 5101C
5101C 000
Figure 1 IB ST 24 BDI 16/4 module
This data sheet is intended to be used
in conjunction with the
IBS SYS PRO UM E Manual.
Ground the mounting rail. The module
is grounded by snapping it onto the
mounting rail.
The numbering of the yellow status
indicators corresponds to the screw-
or spring-clamp terminal. It does not
apply to the channel bit mapping.
Refer to page 4.
Terminal Assignment
Local Diagnostic and Status Indicators
Supply the I/O devices with voltage via terminals
65 (+Us) and 81 (
⊥).
The module then provides
the sensor supply voltage at the terminals 17 to
32.
17 18 19 20 21 22 23 24 25 26 27 28 29 30 3231
2345
6
7 8 9 10111213141516
33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64
I
NTER
B
US
IB S TM E 24 B D I 16/4 , O rd. N o.: 2751687
UL
CC
BA
US
16 digital Input, 24 V D C , M odule Ident.: 190
16
15
1413
1211
10
9
87
65
4
3
2
1
5101C 001
81 84
6865
1
00 01 02 03 04 05 06 07 08 09 10
F
U
S
E
Terminals Assignment
1 to 16 Signal inputs of the sensors
17 to 32 Sensor supply voltage (+ 24 V)
33 to 48 Ground contact of the sensors
49 to 64 Sensor grounding (conductive
connection to the mounting clamp
in the module base)
65 24 V I/O supply voltage
81 Ground of the supply voltage
Des. Color Meaning
UL Green Supply voltage for the
electronics module
CC Green Cable check
BA Green Bus active
US Green 24 V I/O supply voltage
1 to 16 Yellow Input status (for the channel
on terminal XX)
Digital Input Module With 16 Channels