https://www.phoenixcontact.com/us/products/2902746
10/23/2014Page3/5
Hybrid motor starter-ELR H51-IESSC-24DC500AC-06-2902746
Technical data
Output data, signaling contact
Measuring via Current transformer for line current on L1 and L3
Connection data
Connection method Screw connection
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.14 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 26
Conductor cross section AWG/kcmil max 14
General
Test voltage input/output
4 kV
rms
Mounting position Vertical (horizontal DIN rail)
Assembly instructions Can be aligned with spacing = 20 mm
Operating mode 100% operating factor
Designation Air and creepage distances between the power circuits
Standards/regulations DIN EN 50178
Insulation safe isolation
Pollution degree 2
Surge voltage category III
Designation Standards/regulations
Standards/regulations EN 60947
Safety integrity level according to IEC 61508-1 SIL 3 (safe shutdown)
SIL 2 (motor protection)
Category as per ISO 13849-1 3
Performance Level as per ISO 13849-1 e
Category in acc. with EN 954-1 3
Dimensions
Width 22.5 mm
Height 160 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -25 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Degree of protection IP20