FN510-33-33

DATASHEET
dv/dt filters FN 510
Output Filter for Motor Drives
Reduction of drive output voltage dv/dt
Restriction of overvoltages on motor cables
Reduction of motor temperature
Increase of motor service life
Improvement of system reliability
Performance indicators
Technical specifications
Nominal operating voltage
3x 500/288 VAC
Motor frequency
0 to 400 Hz (4 to 24 A)
0 to 200 Hz (33 to 66 A)
Switching frequency
2 to 16 kHz
Rated currents
4 to 66 A @ 50°C
Motor cable length
80 m max. @ 16 kHz
Voltage drop
≤10 V @ 50 Hz
Typical dv/dt reduction
Factor 8 to 12
Typical reduction of overvoltages
≤1000 V
High potential test voltage
P –> E 2500 VDC for 2 sec
P –> P 1100 VDC for 2 sec
Protection category
IP 20, if temperature auxiliary contact is connected
with IP 20 faston connector
Overload capability
1.4x rated current for 1 minute, every 15 minutes
Temperature range (operation and storage)
-25°C to +70°C (25/070/21)
Flammability corresponding to
UL 94 V-2 or better
Design corresponding to
UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939
MTBF @ 50°C/400 V (Mil-HB-217F)
>100,000 hours
Approvals
Features and benefits
Efficient reduction of high output voltage dv/dt
from IGBT motor drives (as per DIN VDE 0530)
Restriction of overvoltages caused by line
reflections on motor cables (as per DIN VDE 0530)
Protection of motor coil insulation from premature
aging and destruction
Significant increase of service life of electric motors
High reliability and production up time for mission
critical applications
Less interference propagation towards neighboring
equipment or lines
Output filter with low impedance, ideal for
processes requiring exceptional precision and
reproducibility of movements
IP 20 housing and touch-safe terminal blocks
contribute to overall equipment safety
Temperature monitoring and internal fan cooling
protect the filter from thermal overload
Typical applications
Servo drives
Close loop vector drives
Motor drive applications with short to medium
motor cable length
Machinery comprising servo or torque motors
Robots
Pick and place machines
Applications where sine wave filters are not
applicable
Typical electrical schematic
2 Output filters Schaffner Group Datasheets 2017
Filter selection table
Filter Rated current Typical motor Typical Input/Output Weight
@ 50ºC power rating* power loss** connections
[A] [kW] [W] [kg]
FN 510-4-29 4 1.5 90 -29 2.1
FN 510-8-29 8 3.7 90 -29 2.1
FN 510-12-29 12 5.5 90 -29 4
FN 510-16-29 16 7.5 90 -29 4.8
FN 510-24-33 24 11 100 -33 7.7
FN 510-33-33 33 15 110 -33 10
FN 510-50-34 50 22 130 -34 21
FN 510-66-34 66 30 130 -34 22
**General purpose four-pole (1500 r/min) AC induction motor rated 400 V/50 Hz.
**Power loss at 16 kHz switching frequency/80m motor cable length. Exact value depends upon the motor cable type and length, switching frequency and further stray
**parameters within the system.
Typical measurement results
dv/dt without FN 510
dv/dt with FN 510
Overvoltages without FN 510
Overvoltages with FN 510
dv/dt reduction: maximum dv/dt at the motor terminals, measured with the motor drive operating at 14 kHz switching frequency, 5 m of shielded cable, motor with 100% load.
Overvoltage limitation: maximum overvoltages at the motor terminals, measured with the motor drive operating at 14 kHz switching frequency, 80 m of shielded cable, motor idling.
Typical application range at different operating conditions
The power loss in the filter depends mainly on the switching frequency (fs) of the motor drive and the length of the motor cable. FN 510 have been designed for an
ambient temperature of 50ºC.
Other conditions can, however, occur in practice. In such cases, care must be taken to limit the maximum cable length and/or the switching frequency of the motor
drive, depending on the real ambient temperature conditions.
FN 510 are designed for:
Tamb.
Max. fs Max. cable
50ºC
10 kHz 80 m
Possible application, e.g.:
50ºC 16 kHz 50 m
40ºC 16 kHz 80 m
Temperature monitoring function
The temperature monitoring device opens a potential-free contact in the case of filter overtemperature (>120ºC). The maximum switching capability is 5 A/240 V.
The switch can be used, for example, in the input of a CNC controller or as the trip of a circuit breaker in order to interrupt the mains power supply.
3 Output filters Schaffner Group Datasheets 2017
Mechanical data
4 to 16 A types 24 to 66 A types
Dimensions
4 A 8 A 12 A 16 A 24 A 33 A 50 A 66 A
A 220 220 260 260 350 350 470 470
B 65 65 85 85 110 110 140 140
C 140 140 160 160 190 190 235 235
D 180 180 220 220 310 310 420 420
E 200 200 240 240 330 330 440 440
F 40 40 60 60 70 70 100 100
G 5.3 5.3 6.5 6.5 6.5 6.5 8.3 8.3
H 1.5 1.5 1.5 1.5 2 2 5 5
I 10.9 10.9 10.9 10.9 25 25 39 39
J M4 M4 M4 M4 M6 M6 M8 M8
K 10 10 12.5 12.5 20 20 20 20
L 56 56 65 65 80 80 125 125
All dimensions in mm; 1 inch = 25.4 mm
Tolerances according: ISO 2768-m / EN 22768-m
Filter input/output connector cross sections
-29 -33 -34
Solid wire
6 mm
2
16 mm
2
35 mm
2
Flex wire
4 mm
2
10 mm
2
25 mm
2
AWG type wire AWG 10 AWG 6 AWG 2
Recommended torque 0.6-0.8 Nm 1.5-1.8 Nm 4.0-4.5 Nm
Please visit www.schaffner.com
to find more details on filter connectors.
For additional information please ask for FN 510 installation instructions and the Schaffner application note „Output Filters for Use with Frequency Inverters in Motor
Drive Applications“.

FN510-33-33

Mfr. #:
Manufacturer:
Description:
AC Power Line Filters Power Line Filters 33A SFTY TERM BLOCK OUTPUT FLT-FRQ INVRT
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union