Thermal-Magnetic Circuit Breaker 2210-T2...
www.e-t-a.de
1812
1
1
Description
Typical applications
Ordering information
Technical data
One, two and three pole thermal-magnetic circuit breakers with trip-free
mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934).
Featuring a combi-foot design for both symmetric and asymmetric rail
mounting. Available with auxiliary contact (1 x N/O or 1 x N/C) for status
signalling. Two and three pole models are internally linked to ensure that
both/all poles trip in the event of an overload on one pole, even if the
actuator is held in the ON position. This CBE can be supplied in current
ratings up to 32 A with a choice of characteristic curves. All screw
terminals are recessed for safety. Approved to CBE standard EN 60934
(IEC 60934).
Process control equipment, robotics, machine tool control,
communications systems, instrumentation.
2210-T2..
1-pole 3-pole
Type No.
2210 single and multipole thermal-magnetic circuit breaker
Mounting
T rail mounting
Actuator design
2 toggle
Number of poles
1 single pole protected
2 2-pole protected
3 3-pole protected
Accessories
0 without accessories
Terminal design (main contacts)
K0 screw terminals
Characteristic curve
F1 fast acting: therm.1.01-1.4xI
N
;
magn.2-4xI
N
DC (DC only)
F2 fast acting: therm.1.01-1.4xI
N
;
magn.3,5-6,5xI
N
AC/4,5-8,5xI
N
DC
M1 standard delay: therm. 1.01-1.4xI
N
;
magn. 6-12xI
N
AC, 7.8-15.6xI
N
DC
T1 delayed: therm. 1.01-1.4xI
N
; magn. 10-20xI
N
AC
Auxiliary contact design
H without intermediate position
Auxiliary contacts
1 with auxiliary contacts
2 auxiliary contacts on pole 1 only
(multipole devices)
Auxiliary contact function (see diagrams)
2 1 N/O contact
3 1 N/C contact
Auxiliary contact - terminal design
1 screw terminals
Current ratings
0.1...32 A
2210 - T 2 1 0 - K0 M1- H 1 2 1 - 10 A ordering example
For further details please see chapter: Technical Information
Voltage rating AC 250 V; 3 AC 433 V (50/60 Hz); DC 65 V
(UL: AC 277/480 V; DC 65 V)
Current rating range 0.1...32 A for curves M1, T1
0.1...16 A for curves F1, F2
Auxiliary circuit 1 A, AC 240 V / DC 65 V, resistive
(min. 10 V / 10 mA)
Typical life
3 AC 433 V; AC 250 V: 0.1...25 A
10,000 operations at 1 x I
N
, inductive
DC 65 V: 0.1...32 A
10,000 operations at 1 x I
N
, inductive
3 AC 433 V; AC 250 V: 32 A
6,000 operations at 1 x I
N
, resistive
Ambient temperature -30...+60 °C (-22...+140 °F) T 60
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
main/aux. circuit AC 3,000 V
pole/pole AC 1,500 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity I
cn
0.1...5 A 400 A
6...32 A 800 A
curves F1, F2, M1, T1: 0.1...16 A 2,500 A (at DC 32 V)
Interrupting capacity (UL 1077)
Degree of protection operating area IP30
(IEC 60529/DIN 40050) terminal area IP20
Vibration curves F1, F2: 3 g (57-500 Hz), ± 0.23 mm (10-57 Hz)
curves M1, T1: 5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock curves F1, F2: 25 g (11 ms), directions 1, 2, 3, 4, 5
10 g (11 ms), direction 6
curves M1, T1: 25 g (11 ms), directions 1, 2, 3, 4, 5
20 g (11 ms), direction 6
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass approx. 60 g per pole
I
N
0.1...16 A 20...25 A
AC 277 V 1-pole 5,000 A 2,000 A
AC 277/480 V
2-/3-pole 5,000 A 2,000 A
DC 65 V 2,000 A 2,000 A
Preferred types Standard current ratings (A)
1-pole 0.5 1 2 3 4 5 6 8 10 16 20
2210-T210-K0M1-H121-
x x x x x x x x x x x
2-pole 0.5 1 2 3 4 5 6 8 10 16 20
2210-T220-K0M1-H221-
x x x x x x
Preferred types