IB ST 24 AO 4/BP Order No.: 2752521
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2752521
PHOENIX CONTACT Deutschland GmbH Page 2 / 5
http://www.phoenixcontact.de Feb 8, 2011
- In the event of failure or malfunction, the electronics of the module can be easily replaced. The passive termination
block remains mounted on the rail. This means that the replacement process can be carried out in a just a few seconds
and without the need for tools.
- The fuses are accessible from outside, so that a fault can be cleared quickly.
- The connection to protective earth ground is made directly via the DIN rail.
- The conventional labeling materials (Zack strip ZB-6, etc.) can be used to label the termination blocks.
Technical data
Interfaces
Interface ST local bus
Type of connection ST local bus connector
Power supply
Communications power U
L
9 V DC (from the ST local bus)
Typical current consumption 150 mA (at Us)
I/O voltage ± 24 V DC 5 % (ripple)
Peripherals voltage range 18.5 V DC ... 30.2 V DC
Max. power consumption from the local bus 130 mA (from the ST local bus)
100 mA (from the ST local bus)
Electrical isolation
Test section Bus/Outputs 500 V AC 50 Hz 1 min
Supply voltage/Outputs 500 V AC 50 Hz 1 min
Supply voltage/Ground conductor 500 V AC 50 Hz 1 min
I/O voltage/Ground conductor 500 V AC 50 Hz 1 min
Outputs
No. of channels 4
Connection method 2-wire
Type of connection Screw connection
Voltage output signal 0 V ... 10 V (max. 5 mA)
Load/output load voltage output > 2 kΩ
Basic error limit 0.05 %
Representation of output values 16 bit complement on two
Transmission of output values from the control
system
All channels simultaneously in 4 process data words
DAC resolution 12 Bit
Process data update 1 ms (incl. slew rate)