External Battery Pack Compatibility <a class="productLink" href="//www.tripplite.com/External-48V-2U-Rack-Tower-Battery-Pack-Enclosure-DC-
Cabling-select-UPS-Systems-BP48V24-2U~BP48V24-2U">BP48V24-2U</a> (limit 1); <a
class="productLink" href="//www.tripplite.com/External-48V-3U-Rack-Tower-Battery-Pack-Enclosure-DC-Cabling-
select-UPS-Systems-BP48V60RT-3U~BP48V60RT-3U">BP48V60RT-3U</a> (multi-pack compatible);
<a class="productLink" href="//www.tripplite.com/External-48V-2U-Rack-Tower-Battery-Pack-for-UPS-
Systems-BP48V27-2US~BP48V27-2US">BP48V27-2US</a> (multi-pack compatible)
DC System Voltage (VDC) 48
Battery Recharge Rate (Included
Batteries)
Less than 6 hours from 10% to 80% (typical, full load discharge)
Internal UPS Replacement Battery
Cartridge
<a class="productLink" href="//www.tripplite.com/2U-UPS-Replacement-48VDC-Battery-Cartridge-1-set-4-
select-Tripp-Lite-SmartPro-UPS~RBC94-2U">RBC94-2U</a>
Battery Access Front panel battery access door
Battery Replacement Description Hot-swappable, user replaceable batteries
Expandable Runtime Yes
VOLTAGE REGULATION
Voltage Regulation Description Online, double-conversion power conditioning
Overvoltage Correction 2% output voltage regulation during overvoltages to 150
Undervoltage Correction 2% output voltage regulation during undervoltages to 80
Severe Undervoltage Correction 2% output voltage regulation during undervoltages to 65 (under 70% load only)
USER INTERFACE, ALERTS & CONTROLS
Switches 2 switches control off/on power status and alarm-cancel/self-test operation
Alarm Cancel Operation Power-fail alarm can be silenced using alarm-cancel switch
Audible Alarm Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown
conditions
LED Indicators 14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery
and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in
rack/tower formats
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating 600
UPS AC Suppression Response
Time
Instantaneous
UPS Dataline Suppression 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
EMI / RFI AC Noise Suppression Yes
PHYSICAL
Included Mounting Accessory
Description
Includes 4 post rackmount installation accessories
Installation Form Factors Supported
with Optional Accessories
2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)
Primary Form Factor Rackmount
4 / 6