AXL E PB DI8 DO8 M12 6M
8430_en_03 PHOENIX CONTACT 10
7 Connection example
Figure 7 Example of connection of sensors and actua-
tors
8 Connection notes
IN 6
+24 V
IN 5
OUT 3
OUT 4
Note: data corruption or loss
Implement the FE connection using mounting
screws, in order to ensure immunity to inter-
ference.
NOTE: device damage
To ensure IP65/IP67 protection, cover unused
sockets with protective caps.
NOTE: Damage to the electronics
Only supply the sensors with the voltage U
S
provided at the terminal points.
NOTE: Damage to the electronics
Observe the correct polarity of the supply volt-
ages U
S
and U
A
in order to prevent damage to
the device.
NOTE: Malfunction
When connecting the sensors and actuators,
observe the assignment of the connections to
the PROFIBUS input and output data.
Secure the device to a level surface or to a
profile. Do not use this device to bridge gaps,
in order to prevent forces being transmitted
via the device.
Use standard M5 screws with toothed lock
washer and self-locking nuts. Observe the
maximum torque of the screws.
AXL E PB DI8 DO8 M12 6M
8430_en_03 PHOENIX CONTACT 11
9 Configuration via rotary encoding switch
Addresses are set using two rotary coding switches. Switch
x10 is used to set the position in tens (x10) and switch x1 is
used to set the position in units (x1). The address can be set
between 1 and 126.
Figure 8 PROFIBUS rotary encoding switch
S1 S2 Code Function
0000 Reserved
0 ... 12 1 ... 5 01 ... 125 Manual address assignment
12 6 126 Setting the slave address
(set slave address com-
mand)
12 7 127 Reserved
12 8 128 Reserved
12 9 129 Reserved
A new address value is only applied on device
power up.
0
2
4
6
8
9
S2
x1
0
2
4
6
8
10
12
S1
x10
AXL E PB DI8 DO8 M12 6M
8430_en_03 PHOENIX CONTACT 12
10 Local status and diagnostic indicators
10.1 Indicators for bus and power supply
Figure 9 LEDs for bus and power supply
Designation Color Meaning State Description
RDY Green/
yellow/
red
Ready Green
ON
Device ready to operate
Yellow
flashing
Firmware update is being performed.
Flashing
green/
yellow
Over- or undervoltage at U
S
Temperature of the device is in the critical area.
Failure of the actuator supply U
A
Surge voltage/undervoltage of the actuator supply U
A
And red US LED: sensor supply overload
Red ON Rotary encoding switches are set to an invalid/reserved position.
OFF Device is not ready for operation.
BF Red Bus Fault Red ON No communication on PROFIBUS
Device is starting up.
No baud rate detected by device.
Red
flashing
Device has not been configured by the master.
Device configuration does not match.
Invalid parameter data received from the master.
Invalid bus address
The device is in the clear or stop state. The outputs are in the safe state.
OFF No error
SF Red Group
error
Red ON Device-specific diagnostics present, e.g., short circuit at the I/O devices.
Hardware is faulty.
Device data or parameter data do not match.
OFF No error
US Green/
red
U
Sensorik
Green
ON
Communications power/sensor voltage present
OFF Communications power/sensor voltage not present or too low.
Red ON Sensor voltage overload
UA Green U
Aktorik
ON Actuator voltage present.
OFF Actuator voltage not present.