B88069X2840S102

Surge arrester
2-electrode arrester
Series/Type: A81-A150X
Ordering code: B88069X2840****
Version/Date: Issue 05 / 2013-01-10
Version: 6
Content of header bars 1 and 2 of data sheet will be automatically entered in headers and footers! Please fill in the
table and then change the color to "white" (or invisible). This ensures that the table disappears for the customer
PDF. To update the data sheet, click on the symbol "Preview" and then "Close". Please do not alter the header or
footer when copying the content.
Identification/Classification 1:
(header 1 + top left header bar)
Surge arrester
Identification/Classification 2:
(header 2 + bottom left header bar)
2-electrode arrester
Ordering code:
(top right header bar)
B88069X2840****
Series/Type:
(top right header bar)
A81-A150X
EPCOS AG 2015. Reproduction, publication and dissemination of this publication, enclosures hereto and the information
contained therein without EPCOS' prior express consent is prohibited.
EPCOS AG is a TDK Group Company.
Surge arrester B88069X2840****
2-electrode arrester A81-A150X
PPD AB PD / PPD AB PM Issue 05 / 2013-01-10
Please read Cautions and warnings and Page 2 of 4
Important notes at the end of this document.
Features Applications
Standard size
Very high current rating
Fast response time
Stable performance over life
Very low capacitance
High insulation resistance
RoHS-compatible
Consumer electronic
Alarm systems
Electrical specifications
DC spark-over voltage
1) 2)
150
20
V
%
Impulse spark-over voltage
at 100 V/µs - for 99% of measured values
- typical values of distribution
at 1 kV/µs - for 99% of measured values
- typical values of distribution
< 500
< 450
< 600
< 550
V
V
V
V
Service life
10 operations 50 Hz, 1 s 20 A
1 operation 50Hz; 0.18 s 100 A
10 operations [5× (+) & 5× (–)] 8/20 µs 20 kA
1 operation 8/20 µs 25 kA
10 operations [5× (+) & 5× (–)] 10/350 µs 3 kA
300 operations 10/1000 µs 200 A
Insulation resistance at 100 V
DC
> 10
G
Capacitance at 1 MHz < 1.5 pF
Arc voltage at 1 A
Glow to arc transition current
Glow voltage
~ 15
~ 0.6
~ 60
V
A
V
Weight ~ 1.5 g
Operation and storage temperature -40 ... +90 °C
Climatic category (IEC 60068-1) 40/ 90 / 21
Marking, blue negative
150 YY O
150 - Nominal voltage
YY - Year of production
O - Non radioactive
1)
At delivery AQL 0.65 level II, DIN ISO 2859
2)
In ionized mode
Terms in accordance with ITU-T Rec. K.12, IEC 61663-2 and IEC 61643-311.
Surge arrester B88069X2840****
2-electrode arrester A81-A150X
PPD AB PD / PPD AB PM Issue 05 / 2013-01-10
Please read Cautions and warnings and Page 3 of 4
Important notes at the end of this document.
Dimensional drawing in mm
Ordering codes and packing advices
B88069X2840S102 = 100 pcs. on 5 taped stripes B88069X2840T502 = 500 pcs. on tape & reel
Cautions and warnings
Surge arresters must not be operated directly in power supply networks.
Surge arresters may become hot in case of longer periods of current stress (danger of burning).
If the contacts of the surge arrester are defective, current stress can lead to the formation of
sparks and loud noises.
Surge arresters may be used only within their specified values. In case of overload, the lead
contacts may fail or the component may be destroyed.
Damaged surge arresters must not be re-used.