IB IL 24 SAFE 1-PAC Order No.: 2861564
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2861564
PHOENIX CONTACT Deutschland GmbH Page 2 / 5
http://www.phoenixcontact.de Feb 8, 2011
Technical data
Interface
Name INTERBUS local bus
Type of connection Inline data jumper
Transmission speed 500 kBaud
Digital outputs
Output name Relay output
Number of outputs 2
Protective circuit Short-circuit and overload protection Fuse (4 A slow-blow)
Maximum output current per channel 4 A
Nominal load, ohmic max. 120 W
Power supply for module electronics
Type of connection Through the potential jumper
Supply voltage 24 V DC (on S11, S21, S41; supply from: main circuit)
Supply voltage range 20.4 V DC ... 27.6 V DC (including ripple)
Supply current max. 4 A (Current carrying capacity of potential jumpers)
General data
Width 73 mm
Height 119.8 mm
Depth 71.5 mm
Weight 250 g
Note on weight specifications Without plug
Mounting type DIN rail
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) 75 % ... 85 % (75% average, 85% seldom)
Permissible humidity (storage/transport) 75 % ... 85 % (75% average, 85% seldom)
Air pressure (operation) 80 kPa ... 106 kPa (up to 2000 m above mean sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above mean sea level)
Degree of protection IP20
Protection class III, IEC 61140, EN 61140, VDE 0140-1