8330-GN10-XDCS-2XAB009-25A

Magnetic and Hydraulic-Magnetic Circuit Breaker 8330-...
www.e-t-a.
de
2013/14
4 - 1
4
1
Description
Typical applications
Technical data
Single and double pole magnetic and hydraulic-magnetic circuit
breaker with trip-free mechanism and toggle, push or push/pull, or
rocker actuation. A choice of fast magnetic only or hydraulically
delayed switching characteristics (S type MO or HM CBE to EN 60934/
IEC 934) ensures suitability for a wide range of applications. Low tem-
perature sensitivity at rated load. Industry standard dimensions and
threadneck or snap in panel mounting.
Approved to CBE standard EN 60934 (IEC 60934).
Power supplies, process control, switchgear and controlgear.
8330-...
Voltage rating AC 125/250 V (50/60 Hz);
DC 80 V
Current rating range 0.1...30 A
Auxiliary circuit SPDT; 7 A AC 250 V; 7 A (Res) DC 28 V;
4 A (Ind.) DC 28 V; 0.25A DC 80 V
Typical life 10,000 operations at I
N
Ambient temperature -40...+85 °C (-40...+185 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664A) withstand voltage degree
2.5 kV 2
reinforced insulation in the operating area
Dielectric strength AC 3750 V
Insulation resistance > 100 MΩ (DC 500 V)
Degree of protection operating area IP40;
(IEC 60529/DIN 40050) terminal area IP00
Vibration 10 g (57-500 Hz) ± 0,76 mm (10-57Hz)
to IEC 60068-2-6, test C
10 frequency cycles/axis
per Method 204C, test Condition A.
Instantaneous curves tested at 80 % of
rated current.
Shock 100 g (6 ms) to IEC 60068-2-27, test Ea
per Method 213, Cond. I. Instantaneous
curves tested at 80 % of rated current.
Corrosion 96 hours at 5% salt mist,
to IEC 600-9-2-11, test Ka
Method 101, Condition A
Humidity 24 hours at 55% RH,
to IEC 60068-2-78, test Cab
Method 106D
Mass approx. 30 g per pole
(depending on version)
Lists UL Recognized and CSA Certified configurations and performance
capabilities as a Component Supplementary Protector
voltage current rating interrupting capacity (A)
max
rating
frequency phase full
load
(A)
general
purpose
(A)
poles
brea-
king
UL /CSA
with without
backup fuse
32 DC 0.02-15 15.1-25 1 1000
50 DC 0.02-7.5 1 1000
65 DC 0.02-15 15.1-25 2 1000
65 DC 0.02-15 15.1-30 1 1000
80 DC 0.02-15 15.1-30 1 600
125 50/60 1 0.02-15 15.1-30 1 1000
250 50/60 1 0.02-12 1 1000
250 50/60 1 0.02-15 15.1-30 2 1000
250 50/60 1 12.1-18 1 1000
Lists TÜV Certified configurations and performance capabilities as a
Component Supplementary Protector
voltage current rating interrupting capacity (A)
max
rating
frequency phase full
load
(A)
general
purpose
(A)
poles
brea-
king
TÜV
with without
backup fuse
32 DC 0.02-15 15.1-25 1 3000 500
50 DC 0.02-7.5 1 3000 500
65 DC 0.02-15 15.1-25 2 3000 500
80 DC 0.10-15 15.1-25 1 600
125 50/60 1 0.02-15 15.1-25 1 3000 500
250 50/60 1 0.02-12 1 3000 500
250 50/60 1 0.02-15 15.1-25 2 3000 500
Lists UL 489A Listed and TÜV Certified configurations and performance
capabilities for use in Communications Equipment
voltage current
rating
interrupting capacity (A)
max
rating
frequency general
purpose
(A)
poles
breaking
with without
backup fuse
UL 489A TÜV
80 DC 0.02-30 1 600
65 DC 0.02-30 1 1000
80 DC 0.10-25 1 600 600
Interrupting capacity
Magnetic and Hydraulic-Magnetic Circuit Breaker 8330-...
www.e-t-a.
de
2013/14
4 - 2
4
Type No.
8330 circuit breaker
Mounting
F flange, black
G threadneck, black
Q flange, grey
M snap-in, black
N flange, white
Size
G panel thickness 1 -2.5 mm (flange)
M 1/2“-32 for actuator B, C, M, P, 1 and 3
N 3/8”-32 for actuator D and 5
S standard fuseholder cut out for mounting -M only
Number of poles
1 single pole
2 double pole
Panel hardware (bulk)
0 without (1 hex nut, threadneck only)
9 rocker guard
E 1 hex, 1 knurled (Ni) threadneck only
F 1 hex, 1 knurled (Ni), legend plate, threadneck only
H 1 hex, 1 knurled (Ni), locking ring, legend plate,
threadneck only
N 1 hex, 1 knurled with collar (Ni), threadneck only
P 1 hex, 1 knurled with collar (Ni), legend plate,
threadneck only
R 1 hex, 1 knurled with collar (Ni), locking ring,
legend plate, threadneck only
Terminal design
J screw terminal, 8-32, with upturned lugs
P blade terminal 6.3 mm
X screw terminal, 8-32 (bus type)
W push-in stud
Actuator configuration
B paddle, without legend plate
C baton, without legend plate
D push to reset, no button marking
E dual colour rocker (legend vertical)
»ON« indication
G
dual colour rocker (legend vertical)
»OFF«indication
K flat rocker (legend vertical) illuminated
M paddle, legend plate ON-OFF vertical
P paddle, legend plate I-0 vertical
R rocker (legend vertical)
T flat rocker (legend vertical)
W rocker illuminated (vertical)
1 baton, legend plate ON-OFF vertical
3 baton, legend plate I-0 vertical
5 push pull, rated Amps horizontal
Characteristic curve
00 switch only
BD medium AC/DC
BS medium
CD short AC/DC
CS short
OP instantaneous
Actuator colour and marking details
Rocker not illuminated
A green I-0 ON-OFF
K white I-0 ON/OFF
L black I-0 ON-OFF
V blue I-0 ON-OFF
W gray I-0 ON-OFF
X yellow I-0 ON-OFF
Y red I-0 ON-OFF
Z orange I-0 ON-OFF
Rocker illuminated
T clear I-0 ON-OFF
U red transparent I-0 ON/OFF
V green transparent I-0 ON-OFF
W amber transparent I-0 ON-OFF
X smoke gray transparent I-0 ON-OFF
Y white translucent I-0 ON-OFF
8330 - G M 1 0 - P B BS - ...
Ordering information
This is a metric design and millimeter dimensions take precedence (
mm
)
inch
8330 - G M 1 0 - P B BS - A
Paddle, Baton, Button
1 green
2 white
3 black
4 blue
6 yellow
7 red
8 orange
Illumination voltage
A 120 V, 250 V, neon, external resistor
B 120V, 250V, green, neon,
external resistor
C LED red, external resistor
D LED green, external resistor
E LED amber, external resistor
X no illumination
Auxiliary contacts
A without auxiliary contacts
J 1 changeover, 1st pole,
.06 dia solder turret
K 1 changeover 1st pole,
-058 dia round QC
Internal circuit
A switch only
B series trip
Not used
00
Frequency
4 AC 50/60 Hz
9 DC
M AC + DC
Current rating
0.1...30 A
Approvals
A without
E UL1077,
CSA, TÜV
8330 - G M 1 0 - P B BS - 2 X A B 00 4 - 5A - ...
ordering example
Standard current ratings and typical internal resistance values
Current rating (A) Internal resistance (Ω) per pole
0.1 103
0.25 20
0.5 3.8
0.75 1.5
11
2 0.26
3 0.11
5 0.041
7.5 0.023
10 0.01
12.5 < 0.01
15 < 0.01
20 < 0.01
25 < 0.01
30 < 0.01
Magnetic and Hydraulic-Magnetic Circuit Breaker 8330-...
www.e-t-a.
de
2013/14
4 - 3
4
ø12.70
+0.25
.500 dia
+.010
1.765
±.030
blade terminals 6.3 mm/.0248 in
single pole
Paddle actuator
threadneck mounting
Baton actuator
threadneck mounting
1/2-32
17.27
.680
1.375
15.88
.625
34.93
±
0.508
±
.020
flat
44.83
12.7
35.43
±0.508
28.58
±0.76
.500
1.395
±.020
1.765
±.030
1.125
±.030
ON
OFF
11.94
.470
1/2-32 THD
LOAD
LINE
3.18
.125
15.88
.625
9.02
±0.13
ø3.18
+0.25
panel cut-out
with locking ring
.355
±.005
.125 dia
+.010
ø12.70
+0.25
.500 dia
+.010
without locking ring
5.64
±0.05
.222
±.002
double
44.83
±0.76
12.7
9.40
±0.38
28.58
±0.76
.500
.370
±.015
1.125
±.030
ON
OFF
11.94
.470
1/2-32 THD
LOAD
LINE
3.18
.125
33.12
±0.508
1.304
±.020
flat
39.24
±0.508
1.545
±.020
1.375
34.93
±0.76
terminal
area
2
2
29
1
.079
.079
1.14
.039
line 1
B Series trip, single pole
with auxiliary contacts
A
Switch only with
auxiliary contacts
2
I
>
C
NC NO
line 1
2
C
NC NO
line 1
with illumination
2
I
>
load
3.94
.155
ø1.47
.058 dia
P Blade terminal
(Q.C.)
6.35
.250
9.40
.370
J Screw terminal 8-32
with upturned lugs
9.53
.375
10.41
.410
X Screw terminal 8-32
9.53
.375
10.41
.410
W Push-in stud terminal
3.91
.154
2.54
.100
25.4
19.05
.750
1.00
9.97
.392
23.22
.915
Auxiliary switch terminals:
4.19
.165
ø1.52
.060 dia
J Double solder turret type K Round quick-connect type
.161 dia
+ .002
- .000
Internal connection diagrams
Terminal configurations + design
Dimensions – threadneck mounted version
Installation drawing

8330-GN10-XDCS-2XAB009-25A

Mfr. #:
Manufacturer:
E-T-A Circuit Breakers
Description:
Circuit Breakers
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment: