SHIPPING INFORMATION
CORRUGATED BOX
1.
2. EACH CARTON IS PACKED WITH TWO TRAYS FOR A
PADS (3)
TOTAL OF 114 UNITS PER PACKAGE
(2)
FOAM TRAYS
NOTES:
EACH FOAM TRAY IS FILLED WITH 57 CONVERTERS
SHIPPING BOX
355mm x 250mm x 49mm
(INSIDE DIMENSIONS)
OKX T/10 & T/16-D12 Series
Adjustable DOSA 10/16-Amp SIP DC/DC Converters
MDC_OKX2_T10T16.B06 Page 13 of 16
www.murata-ps.com/support
Input Fusing
Certain applications and/or safety agencies may require fuses at the inputs of
power conversion components. Fuses should also be used when there is the
possibility of sustained input voltage reversal which is not current-limited. We
recommend a time delay fuse installed in the ungrounded input supply line
with a value which is approximately twice the maximum line current, calcu-
lated at the lowest input voltage. Please refer to the Specifi cations.
The installer must observe all relevant safety standards and regulations. For
safety agency approvals, install the converter in compliance with the end-user
safety standard, i.e. IEC/EN/UL 60950-1.
Input Under-Voltage Shutdown and Start-Up Threshold
Under normal start-up conditions, converters will not begin to regulate properly
until the ramping-up input voltage exceeds and remains at the Start-Up
Threshold Voltage (see Specifi cations). Once operating, converters will not
turn off until the input voltage drops below the Under-Voltage Shutdown Limit.
Subsequent restart will not occur until the input voltage rises again above the
Start-Up Threshold. This built-in hysteresis prevents any unstable on/off opera-
tion at a single input voltage.
Users should be aware however of input sources near the Under-Voltage
Shutdown whose voltage decays as input current is consumed (such as poorly
regulated capacitor inputs), the converter shuts off and then restarts as the
external capacitor recharges. Such situations could oscillate. To prevent this,
make sure the operating input voltage is well above the UV Shutdown voltage
AT ALL TIMES.
Start-Up Time
Assuming that the output current is set at the rated maximum, the Vin to Vout
Start-Up Time (see Specifi cations) is the time interval between the point when
the ramping input voltage crosses the Start-Up Threshold and the fully loaded
regulated output voltage enters and remains within its specifi ed accuracy band.
Actual measured times will vary with input source impedance, external input
capacitance, input voltage slew rate and fi nal value of the input voltage as it
appears at the converter.
These converters include a soft start circuit to moderate the duty cycle of its
PWM controller at power up, thereby limiting the input inrush current.
The On/Off Remote Control interval from On command to Vout regulated
assumes that the converter already has its input voltage stabilized above the
Start-Up Threshold before the On command. The interval is measured from the
On command until the output enters and remains within its specifi ed accuracy
band. The specifi cation assumes that the output is fully loaded at maximum
rated current. Similar conditions apply to the On to Vout regulated specifi cation
such as external load capacitance and soft start circuitry.
Input Source Impedance
These converters will operate to specifi cations without external components,
assuming that the source voltage has very low impedance and reasonable
input voltage regulation. Since real-world voltage sources have fi nite imped-
ance, performance is improved by adding external fi lter components. Some-
times only a small ceramic capacitor is suffi cient. Since it is diffi cult to totally
characterize all applications, some experimentation may be needed. Note that
external input capacitors must accept high speed AC switching currents.
TECHNICAL NOTES
Because of the switching nature of DC/DC converters, the input of these
converters must be driven from a source with both low AC impedance and
adequate DC input regulation. Performance will degrade with increasing input
inductance. Excessive input inductance may inhibit operation. The DC input
regulation specifi es that the input voltage, once operating, must never degrade
below the Shut-Down Threshold under all load conditions. Be sure to use
adequate trace sizes and mount components close to the converter.
I/O Filtering, Input Ripple Current and Output Noise
All models in this converter series are tested and specifi ed for input refl ected
ripple current and output noise using designated external input/output compo-
nents, circuits and layout as shown in the fi gures below. External input capaci-
tors (Cin in the fi gure) serve primarily as energy storage elements, minimizing
line voltage variations caused by transient IR drops in the input conductors.
Users should select input capacitors for bulk capacitance (at appropriate
frequencies), low ESR and high RMS ripple current ratings. In the fi gure below,
the Cbus and Lbus components simulate a typical DC voltage bus. Your specifi c
system confi guration may require additional considerations. Please note that
the values of Cin, Lbus and Cbus may vary according to the specifi c converter
model.
In critical applications, output ripple and noise (also referred to as periodic
and random deviations or PARD) may be reduced by adding fi lter elements
such as multiple external capacitors. Be sure to calculate component tempera-
ture rise from refl ected AC current dissipated inside capacitor ESR.
C
IN
V
IN
C
BUS
L
BUS
C
IN
= 2 x 100µF, ESR < 700mΩ @ 100kHz
C
BUS
= 1000µF, ESR < 100mΩ @ 100kHz
L
BUS
= 1µH
+INPUT
-INPUT
CURRENT
PROBE
TO
OSCILLOSCOPE
+
+
Figure 2: Measuring Input Ripple Current
C1
C1 = 1µF
C2 = 10µF
LOAD 2-3 INCHES (51-76mm) FROM MODULE
C2
R
LOAD
SCOPE
+OUTPUT
+SENSE
-OUTPUT
Figure 3: Measuring Output Ripple and Noise (PARD)
OKX T/10 & T/16-D12 Series
Adjustable DOSA 10/16-Amp SIP DC/DC Converters
MDC_OKX2_T10T16.B06 Page 14 of 16
www.murata-ps.com/support
Minimum Output Loading Requirements
All models regulate within specifi cation and are stable under no load to full
load conditions. Operation under no load might however slightly increase
output ripple and noise.
Thermal Shutdown
To prevent many over temperature problems and damage, these converters
include thermal shutdown circuitry. If environmental conditions cause the
temperature of the DC/DC’s to rise above the Operating Temperature Range
up to the shutdown temperature, an on-board electronic temperature sensor
will power down the unit. When the temperature decreases below the turn-on
threshold, the converter will automatically restart. There is a small amount of
temperature hysteresis to prevent rapid on/off cycling. The temperature sensor
is typically located adjacent to the switching controller, approximately in the
center of the unit. See the Performance and Functional Specifi cations.
CAUTION: If you operate too close to the thermal limits, the converter may
shut down suddenly without warning. Be sure to thoroughly test your applica-
tion to avoid unplanned thermal shutdown.
Temperature Derating Curves
The graphs in this data sheet illustrate typical operation under a variety of
conditions. The Derating curves show the maximum continuous ambient air
temperature and decreasing maximum output current which is acceptable
under increasing forced airfl ow measured in Linear Feet per Minute (“LFM”).
Note that these are AVERAGE measurements. The converter will accept brief
increases in current or reduced airfl ow as long as the average is not exceeded.
Note that the temperatures are of the ambient airfl ow, not the converter
itself which is obviously running at higher temperature than the outside air.
Also note that “natural convection” is defi ned as very fl ow rates which are not
using fan-forced airfl ow. Depending on the application, “natural convection” is
usually about 30-65 LFM but is not equal to still air (0 LFM).
Murata Power Solutions makes Characterization measurements in a closed
cycle wind tunnel with calibrated airfl ow. We use both thermocouples and an
infrared camera system to observe thermal performance.
CAUTION: If you routinely or accidentally exceed these Derating guidelines,
the converter may have an unplanned Over Temperature shut down. Also, these
graphs are all collected at slightly above Sea Level altitude. Be sure to reduce
the derating for higher density altitude.
Output Fusing
The converter is extensively protected against current, voltage and temperature
extremes. However your output application circuit may need additional protec-
tion. In the extremely unlikely event of output circuit failure, excessive voltage
could be applied to your circuit. Consider using an appropriate fuse in series
with the output.
Output Current Limiting
As soon as the output current increases to approximately 125% to 150% of
its maximum rated value, the DC/DC converter will enter a current-limiting
mode. The output voltage will decrease proportionally with increases in output
current, thereby maintaining a somewhat constant power output. This is also
commonly referred to as power limiting.
Current limiting inception is defi ned as the point at which full power falls
below the rated tolerance. See the Performance/Functional Specifi cations.
Note particularly that the output current may briefl y rise above its rated value
in normal operation as long as the average output power is not exceeded. This
enhances reliability and continued operation of your application. If the output
current is too high, the converter will enter the short circuit condition.
Output Short Circuit Condition
When a converter is in current-limit mode, the output voltage will drop as the
output current demand increases. If the output voltage drops too low (approxi-
mately 98% of nominal output voltage for most models), the PWM controller
will shut down. Following a time-out period, the PWM will restart, causing the
output voltage to begin ramping up to its appropriate value. If the short-circuit
condition persists, another shutdown cycle will initiate. This rapid on/off cycling
is called “hiccup mode”. The hiccup cycling reduces the average output cur-
rent, thereby preventing excessive internal temperatures and/or component
damage. A short circuit can be tolerated indefi nitely.
Remote Sense Input
The Sense input is normally connected at the load for the respective Sense
polarity (+Sense to the +Vout load). Sense inputs compensate for voltage drops
along the output wiring such as moderate IR drops and the current carrying
capacity of PC board etch. This output drop (the difference between Sense and
Vout when measured at the converter) should not exceed 0.5V. Use heavier
connections if this drop is excessive. Sense inputs also improve the stability of
the converter and load system by optimizing the control loop phase margin.
If the Sense function is not used for remote regulation, the user should con-
nect the Sense to their respective Vout at the converter pins.
Sense lines on the PCB should run adjacent to DC signals, preferably
Ground. Any long, distributed wiring and/or signifi cant inductance introduced
into the Sense control loop can adversely affect overall system stability. If in
doubt, test your applications by observing the converter’s output transient
response during step loads. There should not be any appreciable ringing or
oscillation.
You may also adjust the output trim slightly to compensate for voltage loss
in any external fi lter elements. Do not exceed maximum power ratings. Exces-
sive voltage differences between Vout and Sense together with trim adjustment
of the output can cause the overvoltage protection circuit to activate and shut
down the output.
Power derating of the converter is based on the combination of maximum
output current and the highest output voltage at the ouput pins. Therefore the
designer must insure:
(Vout at pins) x (Iout) ≤ (Max. rated output power)
OKX T/10 & T/16-D12 Series
Adjustable DOSA 10/16-Amp SIP DC/DC Converters
MDC_OKX2_T10T16.B06 Page 15 of 16
www.murata-ps.com/support

OKX-T/16-D12P-C

Mfr. #:
Manufacturer:
Description:
Non-Isolated DC/DC Converters 12Vin 0.75-5.5Vout 16A 80W Pos logic
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union