AXL F DO32/1 1F
8124_en_01 PHOENIX CONTACT 7
5 Maximum outputs power consump-
tion when inductive loads are
switched off
Figure 1 Maximum outputs power consumption when
inductive loads are switched off
The specifications in the diagram refer to a maximum
switching frequency of 1Hz.
The diagram displays the maximum amount of energy that
may be fed back into the the corresponding output groups
(outputs 1 to 8, 9 to 16, 17 to 24, 25 to 32) for each switch off
procedure during switching off of an inductive load without
external freewheeling circuit.
The current data refers to the ohmic DC voltage component
of the inductive load.
6 Internal circuit diagram
Figure 2 Internal wiring of the terminal points
Key:
NOTE: Damage to the electronics
When you use an external freewheel limit, the
free-wheeling voltage to a maximum of -15V.
The value must be above -15V, so-12V, for
example.
The external freewheel limit has no function
with a higher negative voltage.
0,1 0,2 0,5 0,6 0,7 0,8 0,9 1,0 1,11,21,31,41,51,61,7 1,8 1,9 2,0 2,12,22,32,40,3 0,4
0
0,05
0,1
0,15
0,2
0,25
0,3
0,35
0,4
0
1
2
3
4
5
1 = 0,5 A
2 = 0,4 A
3 = 0,3 A
4 = 0,2 A
5 = 0,1 A
Inductance [H]
Energy consumption [J]
Only with external free running circuit
Local bus AxiolineF local bus
(hereinafter referred to as local bus)
Microcontroller
Optocoupler
LED
Electrically isolated areas
Output circuit Output configuration
μ
C
D
UO
E1
4x
DO 1...32
U
24 V
O
U
Bus
Local bus
Output circuit
36070600 37
37
07
360600
06
16
26
36
07
17
27
37
32x
µC
AXL F DO32/1 1F
8124_en_01 PHOENIX CONTACT 8
7 Terminal point assignment
Figure 3 Terminal point assignment
8 Connection example
Figure 4 Connection with 1-wire technology
Make sure that the GND of the actuators and the GND for U
O
have the same potential!
Terminal
point
Color Assignment
Supply voltage input
a1, a2 Red 24 V DC
(U
O
)
Supply to digital output
modules (internally jump-
ered)
b1, b2 Blue GND Reference potential of the
supply voltage (internally
jumpered)
Digital outputs
00 ... 07 Orange OUT1 ...
OUT8
Digital outputs 1 ... 8
10 ... 17 Orange OUT9 ...
OUT16
Digital outputs 9 ... 16
20 ... 27 Orange OUT17 ...
OUT24
Digital outputs 17 ... 24
30 ... 37 Orange OUT25 ...
OUT32
Digital outputs 25 ... 32
a1
b1
a2
b2
a1
a2
b1
b2
00
10
20
30
01
11
21
31
04
14
24
34
05
15
25
35
06
16
26
36
07
17
27
37
02
12
22
32
03
13
23
33
00
10
20
30
07
17
27
37
AXL F DO32/1 1F
8124_en_01 PHOENIX CONTACT 9
9 Local status and diagnostic indicators
Figure 5 Local status and diagnostic indicators
Designa-
tion
Color Meaning State Description
DRed/
yellow/
green
Diagnostics of local bus communication
Run Green ON The device is ready for operation, communication within the station is
OK.
All data is valid. There are no faults.
Active Green flash-
ing
The device is ready for operation, communication within the station is
OK.
The data is not valid. Valid data from the controller/higher-level net-
work not available.
There is no fault in the module.
Device applica-
tion not active
Flashing
green/yellow
The device is ready for operation, communication within the station is
OK.
Output data cannot be outputted and/or input data cannot be read.
There is a fault on the periphery side of the module..
Ready Yellow ON The device is ready for operation but did not detect a valid cycle after
power-on.
Connected Yellow flash-
ing
The device is not (yet) part of the active configuration.
Reset Red ON The device is ready for operation but has lost the connection to the
bus head.
Not connected Red flashing The device is ready for operation but there is no connection to the pre-
viously existing device.
Power down OFF Device in (power) reset.
UO Green U
Output
ON Supply of digital output module present.
OFF Supply of digital output modules not present.
E1 Red Peripheral fault ON Breakdown or overload/short-circuit of an output.
OFF No I/O error.
00 ... 37 Red/
yellow
Diagnostics /
Status of the
outputs
Red ON Short-circuit/overload of the output.
Yellow ON Output is set.
OFF No error, output is not set.

2688051