SPECIFICATIONS
150 - 0-150 VAC
250 - 0-250 VAC
500 - 0-500 VAC *
Custom ranges available
* not UL recognized
AC Power Transducer
NOTE: The building installation must have a switch or circuit-breaker that is in close proximity and within easy reach of the operator. The switch or circuit breaker
shall be marked as the disconnecting device for the equipment.
DIN RAIL / PANEL MOUNT, ACTIVE / REACTIVE
Basic Accuracy:......................... 0.5%
Linearity:................................... 10% to 100% FS
Thermal Drift:............................ 500 PPM/°C
Operating Temperature:............ 0°C to +60°C
Installation Category:................. CAT II
Vibration Tested To:................... IEC 60068-2-6,1995
Pollution Degree:........................2
Response Time: ....................... 250 ms max. 0-90% FS
Supply Voltage:......................... 12 to 24 VDC
MTBF:.......................................Greater than 100 K hours
Frequency Range:....................50 Hz - 400 Hz, sine wave
Insulation Voltage:.................... 2500 VDC
Altitude:.................................... 2000 meter max.Output
Load:........................................ 4-20 mADC -0 to 300 Ω
0-5 VDC - 2K Ω or Greater
Cleaning:................. Water-dampened cloth
Relative Humidity:... 80% for temperatures up to
31°C and decreasing linearly
to 50% at 40°C
Supply Current:
CR6210:......................Typical 35mA Max 45mA
CR6220: Typical 75mA Max 110mA
CR6230:......................Typical 50mA Max 70mA
CR6240: Typical 75mA Max 110mA
CR6250:......................Typical 50mA Max 70mA
CR6260: Typical 75mA Max 120mA
Torque Specs.:.............3.0 inch lbs. (0.4Nm)
Weight:.........................0.5 lbs.
5 - 0-5 AAC
25 - 0-25 AAC
-
Add suffix for input range
OUTLINE DRAWING
PART NUMBERS
CR6210
- -
1 Phase, Active Power with 0 - 5 VDC Output
CR6211
- -
1 Phase, Reactive Power with 0 - 5 VDC Output
CR6220
- -
1 Phase, Active Power with 4 - 20 mADC Output
CR6221
- -
1 Phase, Reactive Power with 4 - 20 mADC Output
CR6230
- -
2-Phase, 3-Wire, Active Power with 0 - 5 VDC Output
CR6231
- -
2-Phase, 3-Wire, Reactive Power with 0 - 5 VDC Output
CR6240
- -
2-Phase, 3-Wire, Active Power with 4 - 20 mADC Output
CR6241
- -
2-Phase, 3-Wire, Reactive Power with 4 - 20 mADC Output
CR6250
- -
3-Phase, 4-Wire, Active Power with 0 - 5 VDC Output
CR6251
- -
3-Phase, 4-Wire, Reactive Power with 0 - 5 VDC Output
CR6260
- -
3-Phase, 4-Wire, Active Power with 4 - 20 mADC Output
CR6261
- -
3-Phase, 4-Wire, Reactive Power with 4 - 20 mADC Output
0.26 (6.5) Dia.
1 Hole Single Element
2 Holes two element
3 Holes for three element
CR Magnetics has a wide selection of
current and potential transformers
to extend the range of any part.