4 Lineage Power
Data Sheet
April 2008
18 Vdc to 36 Vdc Inputs; 20 W
LC020 Single-Output Series Power Module:
Electrical Specifications (continued)
Table 3. Isolation Specifications
General Specifications
Feature Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature
conditions. .
Parameter Min Typ Max Unit
Isolation Capacitance — 0.002 — µF
Isolation Resistance 10 — — MΩ
Parameter Min Typ Max Unit
Calculated MTBF (I
O = 80% of IO, max; TC = 40 °C) 5,800,000 hours
Weight — — 54 (1.9) g (oz.)
Parameter Device Symbol Min Typ Max Unit
Remote On/Off
(V
I = 0 V to 36 V; open collector or equivalent
compatible; signal referenced to V
I(–) terminal.
See Figure 19 and Feature Descriptions.):
LC020xx Positive Logic
Logic Low—Module Off
Logic High—Module On
LC020xx1 Negative Logic
Logic Low—Module On
Logic High—Module Off
Module Specifications:
On/Off Current—Logic Low
On/Off Voltage:
Logic Low
Logic High (I
on/off = 0)
Open Collector Switch Specifications:
All
All
All
I
on/off
Von/off
Von/off
—
–0.7
—
—
—
—
1.0
1.2
6
mA
V
V
Leakage Current During Logic High
(V
on/off = 6 V)
All I
on/off ——50 µA
Output Low Voltage During Logic Low
(I
on/off = 1 mA)
All V
on/off ——1.2 V
Turn-on Time (I
O = 80% of IO, max;
T
C = 40 °C VO within ±1% of steady state)
All — — — 2 ms
Output Voltage Overshoot (See Figure15) All — — 0 5.0 %
Output Voltage Set-Point Adjustment Range All — 90 — 110 %V
O, nom
Output Overvoltage Protection (clamp) LC020F
LC020A
LC020B
LC020C
VO, clamp
VO, clamp
VO, clamp
VO, clamp
3.9
5.6
13.2
16.5
—
—
—
—
5.0
7.0
16.5
19.0
V
V
V
V