https://www.phoenixcontact.com/pi/products/2904477
04/30/2017Page2/3
Filter terminal block-PSR-FTB/20/86-2904477
Technical data
Output data
Limiting continuous current max. 2 A (in total for OUT1 + OUT2)
Connection data, control circuit
Connection name Control circuits
Connection method Push-in connection
Stripping length 8 mm
Conductor cross section solid 0.14 mm² ... 2.5 mm²
Conductor cross section flexible 0.14 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 14
Connection data load circuit
Connection name Load circuit
Connection method Push-in connection
Stripping length 8 mm
Conductor cross section solid 0.14 mm² ... 2.5 mm²
Conductor cross section flexible 0.14 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 14
General
Mounting position Vertical (horizontal DIN rail)
Assembly instructions In rows with zero spacing
Operating mode 100% operating factor
Standards and Regulations
Designation Air clearances and creepage distances between the power circuits
Standards/regulations EN61131
Rated insulation voltage 50 V
Rated surge voltage 1.5 kV
Insulation Basic insulation
Degree of pollution 2
Overvoltage category II
Drawings
Circuit diagram
IN
IN
GND
GND
GND
OUT 2
OUT 1
+ +
Approvals
Approvals